Economizer Motor Ð All control of the motor (i.e., enthalpy changeover, minimum position control and mixed air control) is accomplished from the main unit microproces- sor through a relay board. Service and installation instruc- tions for the unit should be consulted to verify proper op- eration of these controls. The economizer motor may be checked out separately. See Fig. 52 for VAV economizer motor con- nection information.
Motor Test
Apply 24 volt AC power to terminals T1 and T2 of motor. Connections to motor terminals 2 and 3 must be disconnected
A Motor Test | A Expected Result and Response |
Jumper 1 to | Motor drives open; if not, |
2 at motor | replace motor. |
B Motor Test | B Expected Result and Response |
Jumper 1 to | Motor drives closed; if not, |
3 at motor | replace motor. |
LIMIT SWITCHES |
|
|
|
CAPACITOR |
|
|
|
|
| 3 |
|
CW |
|
| ECONOMIZER |
WINDING | 2 | ||
(OPEN) |
| MOTOR | |
CCW |
|
|
|
WINDING |
| T1 |
|
(CLOSE) |
|
| |
|
|
| |
1 |
| T2 |
|
BRAKE |
| 1 | |
|
| ||
| WINDING |
|
|
CW |
| 1 |
|
|
|
| |
|
| 2 |
|
FEEDBACK |
|
|
|
POTENTIOMETER |
|
| |
|
| 3 |
|
|
|
| BLU |
|
|
| RED |
|
|
| YEL |
AUX. SWITCH
LEGEND
CCW Ð Counterclockwise
CW Ð Clockwise
Fig. 52 Ð Damper Motor Connection Diagram (VAV)
Variable Frequency Drive
NOTE: The VFDs (part no.
STANDARD TRANSDUCER CONTROL Ð The VFD moni- tors and controls duct pressure (DP) via a differential pres- sure transducer. The pressure transducer is located in the auxiliary control box
The DP transducer monitors the static pressure in the sup- ply duct and provides a 4 to 20 mA signal directly to the VFD. (Refer to Table 13 for transducer output signal (mA) for actual duct static pressure.) The internal logic of the VFD compares this signal representing actual duct pressure to the
EXTERNAL SIGNAL CONTROL Ð If the VFD is to be controlled by an external control system other than the fac- tory supplied pressure transducer, the internal PID logic func- tion of the VFD must be disabled. To disable the PID control:
1.Disconnect all power to the unit and the VFD.
2.Install a jumper across
3.Remove
4.Remove other end of the same cable from the pressure sensor.
5.Connect ®eld supplied speed reference (4 to 20mA) across terminals
6.Disable the supply fan motor operation.
7.Reconnect power to the unit and VFD.
8.Reprogram the VFD to accept an external reference (in the Utility parameters group [Gr.Ut], set parameter item Fnod [no.312] = 4).
9.Enable supply fan motor and return power to the unit.
SUPPLY FAN MOTOR OVERLOAD PROTECTION Ð The VFD provides operating overload protection for the supply fan motor. The factory has programmed the VFD overload function to match the
NOTE: Variable frequency drive size is matched to factory- installed motor size. Do not increase motor size without also changing to equivalent VFD size.
52