Carrier JK034-074, 50FK, 48FK specifications Remote Sasp Wiring

Page 21

EXTERNAL ALARM SIGNAL Ð The unit controls pro- vide an external alarm status signal via a 115-vac output sig- nal at the relay board J5, available at TB2-4 and TB2-5 (common). This signal can be forwarded to the BMS by add- ing a signal relay at the alarm output, placing its coil across terminals TB2-4 and TB2-5 and using its contacts to control a discrete input to the BMS (see Fig. 31).

The alarm signal output is energized when any of the di- agnostic codes is tripped.

034-048: TB3

054-104: TB4

R

12

15

P

TRANSDUCER

BMS

CONTROL

(4 TO 20 MA

OR

2 TO 10 VDC

SIGNAL)

REMOTE ECONOMIZER CONTROL Ð Economizer con- trol is tightly integrated into the unit's capacity control al- gorithms and diagnostic routines. Consequently, control modi®cations that interfere with this standard operating se- quence are not recommended.

Economizer position is determined by the unit processor board based on current outdoor air enthalpy status and cool- ing capacity demand. The economizer damper actuator is a ¯oating point device with an internal brake and spring re- turn. Its position is determined by the sequencing of relays EOR (Economizer Open Relay) and ECR (Economizer Close Relay). The economizer's current position is sensed by the processor board through position feedback potentiometer P2.

Whenever the economizer position potentiometer signal is not consistent with the processor board's commanded po- sition, a fault condition is determined by the processor board and an alarm signal is initiated. The processor board also attempts to return the economizer damper to its fully closed position during this fault condition by energizing the ECR relay.

Any attempt to effect an external control of the econo- mizer actuator will lead to an alarm condition and an auto- matic response by the unit control to attempt to close the dampers.

Smoke Control Modes Ð It is common practice to use rooftop units for aid in building smoke control in the event of a building ®re. The available functions include: Fire Shutdown, Pressurization, Evacuation, and Smoke Purge. These functions are enhanced when multiple rooftop units are used to zone a building.

Implementation of the various Smoke Control modes on these units requires the installer to modify the unit wiring to add contacts (via either manual switches or relays) that will selectively interrupt and override standard factory control se- quences. See Table 5.

FIRE SHUTDOWN MODE Ð Fire Shutdown mode termi- nates all unit operation (cooling, heating, supply fan and power exhaust). This mode prevents recirculation of contaminated air back into the space or the admission into the space of unsuitable outside air.

PRESSURIZATION MODE Ð Pressurization mode is in- tended to keep smoke out of a zone. Factory-installed op- tional economizer is required for this function. Pressuriza- tion is accomplished by:

·opening the economizer (option)

·running the supply fan (optional inlet guide vanes open or optional VFD (variable frequency drive) at normal duct static pressure set point)

·closing the power exhaust dampers (if installed as option or accessory)

·shutting off the power exhaust fans (if installed as option or accessory)

This allows the space to be overpressurized relative to ad- jacent zones and prevents or slows entry of smoke into this space from adjacent zones.

LEGEND

PÐ Manual Potentiometer R Ð Fixed Resistor

Field Wiring

Fig. 30 Ð Remote SASP Wiring

TB2

TB2

4

5

 

LIGHT

 

R

 

RELAY

SIGNAL TO BMS

LEGEND

RÐ Resistor (Factory Installed) Factory Wiring

Field Wiring

Fig. 31 Ð External Alarm Indication

EVACUATION MODE Ð Evacuation mode removes smoke or undesirable air from interior spaces without reintroducing unsuitable air. Factory-installed, optional economizer with optional or accessory power exhaust are required for this func- tion. Evacuation is accomplished by:

·turning supply fan off

·opening the economizer (option required for this function)

·running the exhaust fans (must be provided via option or accessory)

·opening the exhaust dampers

SMOKE PURGE MODE Ð Smoke Purge mode removes smoke from the interior spaces and replaces it with fresh out- side air. Factory-option economizer with optional or acces- sory power exhaust are required for this function. Smoke purge is accomplished by:

·turning supply fan on

·opening the economizer (option required for this function)

·running the exhaust fans (must be provided via option or accessory)

·opening the exhaust dampers

21

Image 21
Contents Contents Controls Operation TroubleshootingGeneral Safety ConsiderationsConnector J1 Temperature Unit Size Terminal no Input Pin Terminal Connector J1 Thermistor InputsDIP EXVConnector J2 Status Switch Unit Size Terminal no Status Switch Inputs034-104 RNT Ð ReturnPage Output PIN Name Rating Device Terminal Output Pin and Terminal AssignmentsHIR IFCCompressor Operation Thermistor T1 Location, 50FK,JK034-048 Units Thermistor T1 Location, 50FK,JK054-074 Units Thermistor T2 Location, Size 034-048 Units Thermistor T3 and T4 Locations, Size 054-104 Units Input Integrated CircuitSpace Temperature Reset Controls InstallationUnit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes 088 Thermistor Resistance Voltage Drop CharacteristicsSpace Temperature Sensor Averaging Single-Step Demand Limit MSP = Sasp + Remote Sasp Wiring Smoke Control Modes Smoke Control Switches Required for Each ModeTubing Size Switch FunctionsDPS Ð Differential Pressure Switch SwitchTerminal Block START-UP Modulating Power Exhaust Differential Pressure Switch SizesConguration Header DIP Switch Factory Settings Potentiometer Inputs and RangesConguration Header Jumpers Switch Function Meaning Position DIP SwitchesInlet Guide Vane Motor 50FK,JK034-074 Units Variable Frequency Drive Keypad Jumper Removal to Disable MotorChanging the VFD Set Point Frequency Command VFD Set Point Frequency Command for Duct PressureControl Signal Pressure VFD SET Point PressureStart Unit Quick Normal Description Control Switch Test Display Step no Quick Test, Unit Conguration and Switch CheckQuick Test, Output Relay Check Quick Test, Thermistor and Potentiometer CheckQuick Normal Description Thermistor or Test Quick Normal Test Description Relay NumberSensor Resistance Values Operating InformationPage Component Arrangement, 034-048 Units Component Arrangement, 054-104 Units Page Modulating Power Exhaust Component Locations Sizes Modulating Power Exhaust Component Locations Sizes Page Compressor Loading and Unloading Sequences Cooling Size 064 Units Cooling Size 054 UnitsCooling Size 088 Units Cooling Size 104 UnitsControls Troubleshooting TroubleshootingSymptoms Probable Causes Solutions Operation Status CodesDiagnostic Codes Codes 71 to 76 THERMISTOR/RESISTOR Failure Page Test PIN Voltage DC TP3 Terminals Voltage ACTP4 TP6PIN Terminal Voltage DC Quick Test J9 PIN Numbers Step noPin Terminal Connector J2 Voltages Pin Terminal Connector J1 VoltagesTerminal Strip J6 Connection Resistance Reading PIN Voltage TerminalTerminal Strip J5 Connector Resistance Reading Enthalpy Sensor CheckoutQuick Test J5 PIN Numbers Step no Variable Frequency Drive Parameter Group Default Value Carrier Default Program Parameter ValuesMotor Overload Settings Required User Adjusted DefaultsLAT ALMLPS MTRPage Page Call for Free Catalog Service TrainingPRE-START-UP II. Preliminary Checklist ItemsIV. Notes III. START-UP