Carrier JK034-074, 50FK, 48FK specifications DIP Switches, Switch Function Meaning Position

Page 27

DIP SWITCH NO. 1 Ð Supply Air Set Point (SASP) Reset Type. Factory setting is OFF. Do not change.

DIP SWITCH NO. 2 Ð SASP Reset Enabled. Factory set- ting is OFF (no SASP reset enabled). If SASP reset has been installed, enable it by changing switch position to ON.

DIP SWITCH NO. 3 Ð Economizer option. If economizer option has been installed, this switch will be ON. If there is no economizer installed, this switch will be OFF. Con®rm setting per Table 10. Change only if in error.

DIP SWITCH NO. 4 Ð Morning Warm-Up. For 48FK,JK models, this switch will be ON (morning warm-up enabled). For 50FK,JK units with factory-installed electric heaters, this switch will be ON. For all other units, this switch will be OFF. If accessory electric heaters are installed (for 50FK,JK without plenum option), change this switch to ON.

DIP SWITCH NO. 5 Ð Demand Limit. Factory setting is OFF (demand limit not enabled). If Demand Limit (single- step or 2-step accessory) has been installed, change this switch to ON.

DIP SWITCHES NO. 6 AND NO. 7 Ð Unloader Con®gu- ration. These are factory set to match unit size. Con®rm set- tings per Table 12. Change only if in error.

Table 12 Ð DIP Switches

SWITCH

FUNCTION

SWITCH

MEANING

NO.

POSITION*

 

 

1

Reset

Off

Space or Outdoor-Air Reset

Mode

(DO NOT CHANGE)

 

 

2

Reset

On

Reset Used

Select

Off

Reset Not Used

 

3

Economizer

On

Enable Economizer

Off

Disable Economizer²

 

 

4

Morning

On

Enable Morning Warm-Up**

Warm-Up

Off

Disable Morning Warm-Up**

 

5

Demand

On

Enable Demand Limit

Limit

Off

Disable Demand Limit

 

6,7

 

Off, Off

No Unloaders

Unloaders

On, Off

1 Unloader

 

 

Off, On

2 Unloaders

8

Not Used

Off

No Signi®cance

 

 

 

 

LEGEND

DIP Ð Dual, In-Line Package

*Control circuit breaker must be off before changing the setting of the DIP switch. ²No economizer.

**And/or electric heat (50FK,JK units without plenum only).

Adjusting Set Points Ð Set points for unit operation are established via potentiometer settings. Set points for Sup- ply Fan controls are set at the VFD keypad (if installed) or at the IGV differential pressure switch (DPS1) (if IGV op- tion installed). Set points for modulating power exhaust (op- tion or accessory) are set at the differential pressure switch (DPS2).

Potentiometers Ð All of the set point potentiometers must be set before the unit is started in order for the unit to function properly. Each of the potentiometers has a valid range that is used by the control. The valid range is de®ned as the potentiometer's resistance value that the control will not con- sider to be in error. This is usually between 10% and 90% of the potentiometer's total resistance. The control has been programmed to accept an operational range for the poten- tiometer, which may not be the same as the valid range.

Potentiometer inputs and ranges are summarized in Table 9. Information on individual set point potentiometers (including function, location and range data) are shown below:

SUPPLY AIR SET POINT (Leaving-Air Temperature) (P1)

ÐThis potentiometer establishes the set point for cooling cycle operation of the VAV unit. The VAV control uses a valid control range of 45 to 70 F, and the potentiometer has a valid range of −22 to 70 F. If the set point is between −22 and 45 F, the control will use a value of 45 F. If the set point is outside the valid range (less than −22 F or greater than 70 F), an alarm condition will be signaled and a default value of 70 F will be used.

ECONOMIZER MINIMUM POSITION (P5) Ð This po- tentiometer speci®es the minimum opening position for the optional economizer during running periods. It has both a valid range and an operational range of 0 to 100%.

SASP RESET TEMPERATURE (P7) Ð This potentiometer establishes the space temperature at which the control will initiate the reset of the SASP (i.e., the unit control begins to raise the base SASP, to prevent overcooling of the space). The potentiometer has a valid range of 40 to 100 F. Refer to Space Temperature Reset section on page 16 for further dis- cussion of SASP Reset operation.

RESET LIMIT (P3) Ð Used in conjunction with P7 poten- tiometer, this potentiometer establishes the maximum tem- perature for the modi®ed SASP value during the Reset func- tion. This potentiometer has a valid range of 0° to 80 F.

DEMAND LIMIT, SINGLE-STEP (P4) Ð This potentiom- eter establishes the maximum amount of compressor capac- ity permitted by the unit control when single-step demand limit operation is implemented (by closing contact set to po- tentiometer wiper arm). This potentiometer is ®eld-supplied and -installed and will be located in the main control box. The valid range is 0% to 100%, which is also the operational range.

If the wiper arm is open, all capacity stages can be used. When the wiper arm is closed, the capacity is reduced by the amount set on potentiometer P4.

DEMAND LIMIT, 2-STEP Ð The accessory 2-step demand limit control is a 2-potentiometer system. The demand limit control board (DLCM) accessory board is ®eld-installed in the main control box; the 2 control poten- tiometers are located on the DLCM. Potentiometer DLCM-P1 establishes the maximum amount of compressor capacity avail- able when SW1 is closed and has a valid range is 50% to 100%. Potentiometer DLCM-P2 establishes the maximum amount of compressor capacity available when SW2 is closed and has a valid range is 0% to 49%.

If no power is supplied to the DLCM, all capacity stages can be used. When power is supplied to terminal IN1 only, the ®rst step of demand limit control is energized and the capacity is reduced by the amount set on potentiometer P1. When power is supplied to IN2 (or IN1 and IN2), the ca- pacity is reduced by the amount set on potentiometer P2.

MORNING WARM-UP (P6) Ð This potentiometer estab- lishes the set point temperature for the Morning Warm-Up function. This is the temperature at which the morning warm-up sequence is terminated and VAV cooling operation begins. The valid control range is 0° to 95 F, but the control is pro- grammed to accept a range of 40 to 80 F. If the set point is between 0° and 40 F, the control will use a value of 40 F. If the set point is between 80 and 95 F, the control will use a value of 80 F. If the set point is outside the valid range (less than 0° F or greater than 95 F, an alarm condition will be signaled and a default value of 40 F will be used.

27

Image 27
Contents Contents Controls Operation TroubleshootingGeneral Safety ConsiderationsEXV Pin Terminal Connector J1 Thermistor InputsConnector J1 Temperature Unit Size Terminal no Input DIPRNT Ð Return Status Switch InputsConnector J2 Status Switch Unit Size Terminal no 034-104Page IFC Output Pin and Terminal AssignmentsOutput PIN Name Rating Device Terminal HIRCompressor Operation Thermistor T1 Location, 50FK,JK034-048 Units Thermistor T1 Location, 50FK,JK054-074 Units Thermistor T2 Location, Size 034-048 Units Thermistor T3 and T4 Locations, Size 054-104 Units Input Integrated CircuitSpace Temperature Reset Controls InstallationUnit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes 088 Thermistor Resistance Voltage Drop CharacteristicsSpace Temperature Sensor Averaging Single-Step Demand Limit MSP = Sasp + Remote Sasp Wiring Smoke Control Modes Smoke Control Switches Required for Each ModeTubing Size Switch FunctionsDPS Ð Differential Pressure Switch SwitchTerminal Block START-UP Modulating Power Exhaust Differential Pressure Switch SizesConguration Header DIP Switch Factory Settings Potentiometer Inputs and RangesConguration Header Jumpers Switch Function Meaning Position DIP SwitchesInlet Guide Vane Motor 50FK,JK034-074 Units Variable Frequency Drive Keypad Jumper Removal to Disable MotorPressure VFD Set Point Frequency Command for Duct PressureChanging the VFD Set Point Frequency Command Control Signal Pressure VFD SET PointStart Unit Quick Normal Description Control Switch Test Display Step no Quick Test, Unit Conguration and Switch CheckQuick Normal Test Description Relay Number Quick Test, Thermistor and Potentiometer CheckQuick Test, Output Relay Check Quick Normal Description Thermistor or TestSensor Resistance Values Operating InformationPage Component Arrangement, 034-048 Units Component Arrangement, 054-104 Units Page Modulating Power Exhaust Component Locations Sizes Modulating Power Exhaust Component Locations Sizes Page Compressor Loading and Unloading Sequences Cooling Size 104 Units Cooling Size 054 UnitsCooling Size 064 Units Cooling Size 088 UnitsOperation Status Codes TroubleshootingControls Troubleshooting Symptoms Probable Causes SolutionsDiagnostic Codes Codes 71 to 76 THERMISTOR/RESISTOR Failure Page TP6 Terminals Voltage ACTest PIN Voltage DC TP3 TP4PIN Terminal Voltage DC Quick Test J9 PIN Numbers Step noPIN Voltage Terminal Pin Terminal Connector J1 VoltagesPin Terminal Connector J2 Voltages Terminal Strip J6 Connection Resistance ReadingTerminal Strip J5 Connector Resistance Reading Enthalpy Sensor CheckoutQuick Test J5 PIN Numbers Step no Variable Frequency Drive Parameter Group Default Value Carrier Default Program Parameter ValuesMotor Overload Settings Required User Adjusted DefaultsMTR ALMLAT LPSPage Page Call for Free Catalog Service TrainingPRE-START-UP II. Preliminary Checklist ItemsIV. Notes III. START-UP