Fan and Heater
FLAME DETECTOR KIT INSTALLATION
1994-1995 PNEG-286
Flame Detector Kit Installation
Part Number HF-7136
1.Mount the detector module inside the heater control box. Module can be mounted in any position, but install so that moisture cannot get inside unit.
2.Run white wire to common or neutral of 120V power source.
3.Run black wire to terminal that is 110V when heater gets power. (Wire module power in parallel with main solenoid if it is 110V.)
4.Run green and red wires down to sens- ing probe. Red wire should go to flame probe electrode and green wire should go to flame probe ground. For proper operation the ground wire should be connected as close to probe as possible.
5.The remaining three wires are the normally open or normally closed relay contacts that replace the mechanical
flame probe. The
6.110 volt igniton transformer may be connected to (2) 1/4" male spade con- nectors. This will turn off igniton after flame is established.
7.Mount the sensing probe so the sensing portion will be in the flame at its highest and lowest operating conditions.
8.On the side of the flame detector is a red neon light. This light should be on when flame is being sensed and will go out when flame out condition is detected.
| V | (NOT USED NORMALLY) | |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
CONNECT WHERE |
| NORMALLY OPEN |
|
|
|
| WHITE/BLUE |
|
| ||||||||||
|
|
|
|
|
| ||||||||||||||
MECHANICAL PROBE |
| COMMON |
|
|
|
|
|
|
| BLUE/BLACK |
|
| |||||||
|
|
| |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
| |||||||||
WIRES WERE CONNECTED |
| NORMALLY CLOSED |
|
|
| WHITE/BROWN |
| ||||||||||||
|
|
| |||||||||||||||||
TO FLAME SENSOR | ELECTRODE |
|
|
|
|
|
| RED |
|
|
| ||||||||
|
|
|
|
|
|
|
|
| |||||||||||
VGROUND |
|
|
|
|
|
|
| GREEN |
| ||||||||||
|
|
|
|
|
|
|
|
|
| ||||||||||
|
| V |
|
|
|
| BLACK |
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
TO 110V POWER |
|
| WHITE |
|
|
|
|
| |
| 110 VOLT IGNITION TRANSFORMER | |||
| CONNECTION (1/4" MALE SPADES) |
FLAME
DETECTOR
MODULE
85