Bosch Appliances ICP-CC404 manual System Functions, Installer Code Functions

Page 27

ICP-CC404 Installation Guide 6.0 System Functions

If horn speaker indication beeps are enabled, one beep sounds from the horn speaker. If strobe indications are enabled, the strobe flashes for 3 sec to indicate the system is disarmed.

5.5.5Panic Alarm

Press and hold both [AWAY] and [STAY] together for 2 sec.

An audible Panic Alarm is initiated that activates the horn speaker, strobe, and internal sirens.

If Option 1 is selected in Location 425 (refer to Section 18.2 System Options 2 on page 73), the remote radio Panic Alarm is also silent.

5.5.6Remote Outputs

The [DOOR] and [AUX] buttons on the four-channel hand-held transmitter can operate two remote outputs. Only the installer can program these outputs. You can use the Output Event Types listed in

Table 18. Refer Section 16.0 Programmable Outputs for more information.

Table 18: Remote Output Event Types

 

 

 

Output

 

 

Event Type

Description

Page

2,11

Radio Control Output 1

67

2,12

Radio Control Output 2

67

2,13

Radio Control Output 1 – not

68

 

armed in AWAY Mode

 

2,14

Radio Control Output 2 – not

68

 

armed in AWAY Mode

 

To turn Output 1 on:

Press and hold [DOOR] for 2 sec.

Output 1 turns on.

To turn Output 1 off:

Press and hold [DOOR] for 2 sec.

Output 1 turns off.

To turn Output 2 on:

Press and hold [AUX] for 2 sec.

Output 2 turns on.

To turn Output 2 off:

Press and hold [AUX] for 2 sec.

Output 2 turns off.

All reset times for the [DOOR] and [AUX] buttons are referenced to Polarities 1 and 8. Reset times vary depending on the polarity used.

6.0 System Functions

This section explains more advanced features, such as Installer Code, Master Code, and hold-down functions used for testing and regular maintenance of the system.

6.1Installer Code Functions

Installer Code functions allow the installer to perform various system tests and tasks without knowing a Master Code.

To access the required Installer Code function, enter the Installer Code and corresponding function digit, and press [AWAY]. The Installer Code functions are listed in Table 19.

You can only access these functions when the system is disarmed.

Table 19: Installer Code Functions

Function

Description

0Reserved

1Set the number of days until the first Test Report

(Section 6.1.1)

2Change domestic telephone numbers (Section 6.1.2)

3Change the Telco arming or disarming sequence

(Section 6.1.3 on page 28)

4Setting STAY Mode 2 zones (Section 6.1.4 on page 30)

5Satellite Siren (EDMSAT) Service Mode (Section 6.1.5 on page 30)

6Turn Telephone Monitor Mode on and off (Section 6.1.6 on page 31)

7Walk Test Mode

(Section 6.1.7 on page 31)

8Event Memory Recall Mode (Section 6.1.8 on page 31)

9Reserved

6.1.1Set the Number of Days until the First Test Report

This function determines when the system sends the first Test Report (Contact ID Event Code 602). If you do not use this Installer Code Function, the first Test Report is sent to the base station receiver after the repeat interval programmed in Location 366 (refer to Section 15.21 Test Reporting Time on page 63). If you want the system to send the first Test Report sooner than the repeat interval, use this function to set when the first Test Report is sent.

Bosch Security Systems, Inc. 12/08 F01U089401-02

27

Image 27
Contents ICP-CC404 Installation GuideCopyright Notice ICP-CC404 Installation Guide Copyright NoticeContents ICP-CC404 Installation Guide Contents Figures Tables Quick Start FeaturesICP-CC404 Installation Guide 1.0 Introduction IntroductionZone Types Setting the Date and TimeZone Defaults ExampleProgramming with the Remote Codepad ICP-CC404 Installation Guide 2.0 ProgrammingCodepad Indicators ProgrammingProgramming Option Bits Installer’s Programming CommandsInstaller’s Programming Mode Commands Programming with the Programming KeyCommand 959 Test the Programming Key Command 958 Enable/Disable Zone Status ModeCommand 963 Copy the Programming Key to the Control Panel Command 960 Exit from the Installers Programming ModeCommand 964 Erase the Programming Key Command 965 Set Up Domestic Dialing FormatCommand 966 Enable or Disable Auto Step Mode Programming Command 965 DefaultsExample Auto Step Mode Enabled Example Auto Step Mode DisabledUsing this feature is not recommended Disable Factory DefaultsCodepad Indicators ICP-CC404 Installation Guide 3.0 Codepad IndicatorsICP-CP508W Eight Zone LED Codepad Audible Indicators ICP-CP508LW Eight Zone LCD CodepadSystem Disarmed System Operations Disarming the System from Away ModeArming the System in Away Mode ICP-CC404 Installation Guide 4.0 System OperationsArming the System in Stay Mode Disarming the System from Stay ModeEntry Guard Timer for Stay Mode Arming the System in Stay Mode Codepad Medical Alarm Codepad Duress AlarmCodepad Panic Alarm Codepad Fire AlarmLow Battery Fault Analysis ModeFault Descriptions Fault IndicatorsHorn Speaker Monitor Telephone Line FaultDate and Time Sensor WatchChanging or Deleting Remote Radio User Codes Remote Radio Transmitter OperationsIndications from Remote Radio Transmitter Operations Remote Radio User Code Priority LevelsArming in Stay Mode Codepad Indicators for Remote Radio User NumbersArming in Away Mode Disarming from Away ModeDisarming from Stay Mode Panic AlarmFour-Channel Remote Radio Hand- Held Transmitter Operations Installer Code Functions ICP-CC404 Installation Guide 6.0 System FunctionsSystem Functions Change Telco Arming or Disarming Sequence Codepad Indicators When Changing Phone NumbersChanging Domestic Phone Numbers Domestic Dialing DigitsSequence Codepad Indicators When ChangingTelco Arming or Disarming Dialing Digits Telco Arming or DisarmingSatellite Siren Service Mode Setting Stay Mode 2 ZonesMaster Code Functions Turning Telephone Monitor Mode On and OffTelephone Monitor Mode Indications Event Memory Recall ModeChanging and Deleting Remote Radio User Codes Remote Radio Numbers Displayed by the Codepad IndicatorsMaster Code Functions Changing and Deleting User CodesCodepad Indicators When Changing Domestic Telephone Numbers Change Telco Arming or Disarming Sequence Setting Stay Mode 2 Zones Turning Outputs On/Off Hold-Down Functions Remote Arming by Telephone ICP-CC404 Installation Guide 7.0 Remote Arming by TelephoneAlarm Link Software ICP-CC404 Installation Guide 8.0 Alarm Link SoftwareRemote Connect Domestic Dialing Function Alarm Link OptionsICP-CC404 Installation Guide 9.0 Domestic Dialing Domestic DialingSetting Up and Programming Domestic Reporting Contact ID Format ICP-CC404 Installation Guide 10.0 Dialer Reporting FormatsDialer Reporting Formats Transmission Formats+ 2 Express Reporting Format Point ID Codes10.1.3 4 + 2 Express Reporting Format Example Reporting in 4 + 2 Express FormatBasic Pager Reporting Format +2 Express Transmission Code DescriptionsZone Status Display Descriptions Basic Pager Display InformationSubscriber ID Number Zone StatusSystem Status ICP-CC404 Installation Guide 11.0 Dialer InformationDialer Information Primary Telephone Number for Receiver 1 and ReceiverSubscriber ID Number for Receiver 1 and Receiver Secondary Telephone Number for Receiver 1 and ReceiverHandshake Tone for Receiver 1 and Receiver Transmission Format for Receiver 1 and ReceiverDialing Format Telco Arming SequenceTelco Disarming Sequence Answering Machine Bypass Telephone Line Fault OptionsCall Back Telephone Number Ring CountICP-CC404 Installation Guide 12.0 Dialer Options Dialer OptionsDialer Options User Codes Access CodeInstaller Code ICP-CC404 Installation Guide 13.0 Access CodeUser Code Priority EOL Resistor Value Day Alarm InformationICP-CC404 Installation Guide 14.0 Zone Information Zone InformationZone Reporting Information Zone ProgrammingZone Operating Information Zone OptionsZone Types Instant Zone Zone Programming DefaultsDelay-1 Zone Delay-2 Zone12 24-Hour Burglary Zone Keyswitch ZoneHour Holdup Zone Hour Tamper ZoneLatching Arm and Disarm in Away Mode Delay Alarm ReportingSilent Alarm Keyswitch Zone OptionsLatching Disarm from Stay Mode 1 or Stay Mode Latching Disarm from Away Mode, Stay Mode 1, or Stay ModeLatching Arm and Disarm in Stay Mode Latching Arm in Stay ModeSwinger Shutdown Count for Dialer Swinger Shutdown Count for SirenZone Status Trouble Reports Zone Status Alarm Restore CodeSystem Reporting Information Zone Status Bypass ReportsCodepad Duress Report Zone Status Reporting OptionsOpen/Close Reports Open/Close Reporting OptionsSystem Status Low Battery Report System Status AUX Power Supply Fail ReportSystem Status AUX Power Supply Fail Restore Report System Status AC Fail Restore ReportTest Reporting Time System Status Low Battery Restore ReportSystem Status Access Denied System Status Reporting OptionsRedirecting Outputs to the Codepad Buzzer ICP-CC404 Installation Guide 16.0 Programmable OutputsProgrammable Outputs Test Reporting Dialer OptionsOutput Event Types Codepad Medical Alarm Day Alarm EnabledAUX Power Supply Fail Sensor Watch AlarmMimic System Fault Codepad Tamper Access DeniedAlarm When in Stay Mode Alarm When in Away ModeOutput Polarity Event Type Polarities Normally Open, One-Shot Low with ResetNormally Open, One-Shot Low with Alarm Normally Low, One-Shot Open with ResetSystem Event Timers Sensor Watch Time Entry Guard Timer for Stay ModeDelay Alarm Reporting Time Exit TimeKiss-Off Wait Time Auto Arming Pre-Alert TimerAuto Arming Time Auto Disarming TimeSystem Options System and Consumer OptionsArm/Disarm Tracking on Power Up Silent Access Denied Code RetriesSequential Handover Delay Panel Powers Up DisarmedConsumer Options Optional Equipment 19.10 TF008 Plug Pack TF008 19.9 PS101 Power Supply Module19.7 CP5 Eight Zone LCD Codepad CP508LW 19.8 CP105A Night Arm StationTerminal Descriptions Terminals and DescriptionsGlossary Of Terms This mode. Only the installer can program these zones Domestic alarm reportsThat an alarm was sent out Stay ModeICP-CC404 Wiring Diagram DiagramsICP-CC404 Component Overlay 4 not connected ICP-CC404 Installation Guide 21.0 Specifications SpecificationsWarranty Statement Advice to UsersProgramming Sheets ICP-CC404 Installation Guide 22.0 Programming Sheets22.0 Programming Sheets Burglary zones and four 24-hr zones Programming Sheets 22.0ICP-CC404 Installation Guide 22.0 Programming Sheets 374 to 392 to Strobe Output ICP-CC404 Installation Guide 22.0 Programming Sheets 22.0 Programming Sheets PRC Country CodesICP-CC404 Installation Guide Contents Index ICP-CC404 Installation Guide IndexHold Down Function Pulse Count Bosch Security Systems, Inc. F01U089401-02