Bosch Appliances ICP-CC404 manual Remote Radio Transmitter Operations

Page 24

ICP-CC404 Installation Guide 5.0 Remote Radio Transmitter Operations

AC MAINS Failure

An AC MAINS supply failure automatically flashes the MAINS indicator. If the AC MAINS supply is disconnected continuously longer than 2 min, the remote codepad beeps the codepad buzzer once per minute. If the control panel is programmed to report an AC MAINS fail to a base station receiver, it sends an AC Fail Report (Contact ID Event Code 301).

The MAINS indicator stops flashing when the AC MAINS supply is reconnected. When the AC MAINS supply is continuously connected for 2 min, the codepad stops the once per minute beep and the control panel sends an AC Fail Restore Report to the base station receiver.

If the Enable AC Fail in 1 Hour option (1) is selected in Location 426 (refer to Section 18.3 System Options 3 on page 74), the MAINS indicator flashes when the AC MAINS supply is disconnected, but does not activate the dialer or the codepad buzzer unless the AC MAINS supply is disconnected continuously for 1 hour.

If the Ignore AC MAINS Fail option (2) is selected in Location 426 (refer to Section 18.3 System Options 3 on page 74), the codepad does not indicate when the AC MAINS supply fails, but the control panel still sends an AC Fail Report, if enabled.

5.0 Remote Radio Transmitter Operations

You can operate the ICP-CC404 Control Panel remotely using hand-held remote radio transmitters. You can use either a two-channel or a four-channel hand-held transmitter to operate the system.

Both the two-channel and four-channel hand-held transmitters can remotely arm and disarm the system in AWAY Mode or STAY Mode 1, and can activate remote Panic Alarms. The four-channel hand-held transmitter can also operate the control panel’s programmable outputs to activate a garage door or outside lights, for example.

Before a hand-held radio transmitter can operate the control panel, you must teach the transmitter’s radio code to the control panel. Refer to Section 5.3 Changing or Deleting Remote Radio User Codes for more information.

5.1Indications from Remote Radio Transmitter Operations

When using the two-channel or four-channel hand- held transmitter to operate the system, the horn speakers or the strobe can provide audible or visual indications, or both. These indications allow using the system from outside the premises with confidence. The installer can program audible and visual indication beeps by selecting Options 4 and 8 in Location 424 (refer to Section 18.1 System Options 1 on page 73).

Table 15: Horn Speaker Indication Beeps for Remote Operations

 

 

No. of Beeps

System Status

One

System disarmed

Two

System armed in AWAY Mode

One two-tone beep

System armed in STAY Mode 1

Table 16: Strobe Indications for Remote Operations

 

 

Strobe Duration

System Status

3 sec

System disarmed

6 sec

System armed in AWAY Mode

 

 

6 sec

System armed in STAY Mode 1

 

 

5.2Remote Radio User Code Priority Levels

You can only program the remote radio hand-held transmitters to operate as User Codes 9 to 16. You can assign priority levels to each hand-held transmitter, for example, allowing the transmitter to arm the system only, or to arm and disarm the system. Refer to Section 13.3 User Code Priority on page 52 for more information.

Before a hand-held radio transmitter can operate the control panel, you must teach the transmitter’s radio code to the control panel. Refer to Section 5.3 Changing or Deleting Remote Radio User Codes for more information.

5.3Changing or Deleting Remote Radio User Codes

You can use up to eight remote radio hand-held transmitters (User Codes 9 to 16) to operate the system. Before the control panel accepts a signal from a remote radio hand-held transmitter, the control panel must learn the transmitter’s code.

You can substitute the Installer Code for the Master Code to change or delete remote radio User Codes.

24

Bosch Security Systems, Inc. 12/08 F01U089401-02

Image 24
Contents Installation Guide ICP-CC404ICP-CC404 Installation Guide Copyright Notice Copyright NoticeContents ICP-CC404 Installation Guide Contents Figures Tables Features ICP-CC404 Installation Guide 1.0 IntroductionIntroduction Quick StartSetting the Date and Time Zone DefaultsExample Zone TypesICP-CC404 Installation Guide 2.0 Programming Codepad IndicatorsProgramming Programming with the Remote CodepadInstaller’s Programming Commands Installer’s Programming Mode CommandsProgramming with the Programming Key Programming Option BitsCommand 958 Enable/Disable Zone Status Mode Command 959 Test the Programming KeyCommand 960 Exit from the Installers Programming Mode Command 963 Copy the Programming Key to the Control PanelCommand 964 Erase the Programming Key Command 965 Set Up Domestic Dialing FormatCommand 966 Enable or Disable Auto Step Mode Command 965 Defaults Example Auto Step Mode EnabledExample Auto Step Mode Disabled ProgrammingDisable Factory Defaults Using this feature is not recommendedCodepad Indicators ICP-CC404 Installation Guide 3.0 Codepad IndicatorsICP-CP508W Eight Zone LED Codepad Audible Indicators ICP-CP508LW Eight Zone LCD CodepadSystem Disarmed Disarming the System from Away Mode Arming the System in Away ModeICP-CC404 Installation Guide 4.0 System Operations System OperationsArming the System in Stay Mode Disarming the System from Stay ModeEntry Guard Timer for Stay Mode Arming the System in Stay Mode Codepad Duress Alarm Codepad Panic AlarmCodepad Fire Alarm Codepad Medical AlarmFault Analysis Mode Fault DescriptionsFault Indicators Low BatteryTelephone Line Fault Date and TimeSensor Watch Horn Speaker MonitorRemote Radio Transmitter Operations Indications from Remote Radio Transmitter OperationsRemote Radio User Code Priority Levels Changing or Deleting Remote Radio User CodesCodepad Indicators for Remote Radio User Numbers Arming in Away ModeDisarming from Away Mode Arming in Stay ModeDisarming from Stay Mode Panic AlarmFour-Channel Remote Radio Hand- Held Transmitter Operations Installer Code Functions ICP-CC404 Installation Guide 6.0 System FunctionsSystem Functions Codepad Indicators When Changing Phone Numbers Changing Domestic Phone NumbersDomestic Dialing Digits Change Telco Arming or Disarming SequenceCodepad Indicators When Changing Telco Arming or Disarming Dialing DigitsTelco Arming or Disarming SequenceSetting Stay Mode 2 Zones Satellite Siren Service ModeTurning Telephone Monitor Mode On and Off Telephone Monitor Mode IndicationsEvent Memory Recall Mode Master Code FunctionsRemote Radio Numbers Displayed by the Codepad Indicators Master Code FunctionsChanging and Deleting User Codes Changing and Deleting Remote Radio User CodesCodepad Indicators When Changing Domestic Telephone Numbers Change Telco Arming or Disarming Sequence Setting Stay Mode 2 Zones Turning Outputs On/Off Hold-Down Functions ICP-CC404 Installation Guide 7.0 Remote Arming by Telephone Remote Arming by TelephoneAlarm Link Software ICP-CC404 Installation Guide 8.0 Alarm Link SoftwareRemote Connect Alarm Link Options ICP-CC404 Installation Guide 9.0 Domestic DialingDomestic Dialing Domestic Dialing FunctionSetting Up and Programming Domestic Reporting ICP-CC404 Installation Guide 10.0 Dialer Reporting Formats Dialer Reporting FormatsTransmission Formats Contact ID FormatPoint ID Codes 10.1.3 4 + 2 Express Reporting FormatExample Reporting in 4 + 2 Express Format + 2 Express Reporting Format+2 Express Transmission Code Descriptions Basic Pager Reporting FormatBasic Pager Display Information Subscriber ID NumberZone Status Zone Status Display DescriptionsICP-CC404 Installation Guide 11.0 Dialer Information Dialer InformationPrimary Telephone Number for Receiver 1 and Receiver System StatusSecondary Telephone Number for Receiver 1 and Receiver Handshake Tone for Receiver 1 and ReceiverTransmission Format for Receiver 1 and Receiver Subscriber ID Number for Receiver 1 and ReceiverDialing Format Telco Arming SequenceTelco Disarming Sequence Telephone Line Fault Options Call Back Telephone NumberRing Count Answering Machine BypassICP-CC404 Installation Guide 12.0 Dialer Options Dialer OptionsDialer Options Access Code Installer CodeICP-CC404 Installation Guide 13.0 Access Code User CodesUser Code Priority Day Alarm Information ICP-CC404 Installation Guide 14.0 Zone InformationZone Information EOL Resistor ValueZone Programming Zone Operating InformationZone Options Zone Reporting InformationZone Programming Defaults Delay-1 ZoneDelay-2 Zone Zone Types Instant ZoneKeyswitch Zone Hour Holdup ZoneHour Tamper Zone 12 24-Hour Burglary ZoneDelay Alarm Reporting Silent AlarmKeyswitch Zone Options Latching Arm and Disarm in Away ModeLatching Disarm from Away Mode, Stay Mode 1, or Stay Mode Latching Arm and Disarm in Stay ModeLatching Arm in Stay Mode Latching Disarm from Stay Mode 1 or Stay ModeSwinger Shutdown Count for Siren Swinger Shutdown Count for DialerZone Status Alarm Restore Code System Reporting InformationZone Status Bypass Reports Zone Status Trouble ReportsZone Status Reporting Options Open/Close ReportsOpen/Close Reporting Options Codepad Duress ReportSystem Status AUX Power Supply Fail Report System Status AUX Power Supply Fail Restore ReportSystem Status AC Fail Restore Report System Status Low Battery ReportSystem Status Low Battery Restore Report System Status Access DeniedSystem Status Reporting Options Test Reporting TimeICP-CC404 Installation Guide 16.0 Programmable Outputs Programmable OutputsTest Reporting Dialer Options Redirecting Outputs to the Codepad BuzzerOutput Event Types Day Alarm Enabled AUX Power Supply FailSensor Watch Alarm Codepad Medical AlarmCodepad Tamper Access Denied Alarm When in Stay ModeAlarm When in Away Mode Mimic System FaultOutput Polarity Normally Open, One-Shot Low with Reset Normally Open, One-Shot Low with AlarmNormally Low, One-Shot Open with Reset Event Type PolaritiesSystem Event Timers Entry Guard Timer for Stay Mode Delay Alarm Reporting TimeExit Time Sensor Watch TimeAuto Arming Pre-Alert Timer Auto Arming TimeAuto Disarming Time Kiss-Off Wait TimeSystem and Consumer Options System OptionsSilent Access Denied Code Retries Sequential Handover DelayPanel Powers Up Disarmed Arm/Disarm Tracking on Power UpConsumer Options Optional Equipment 19.9 PS101 Power Supply Module 19.7 CP5 Eight Zone LCD Codepad CP508LW19.8 CP105A Night Arm Station 19.10 TF008 Plug Pack TF008Terminals and Descriptions Terminal DescriptionsGlossary Of Terms Domestic alarm reports That an alarm was sent outStay Mode This mode. Only the installer can program these zonesDiagrams ICP-CC404 Wiring DiagramICP-CC404 Component Overlay 4 not connected Specifications Warranty StatementAdvice to Users ICP-CC404 Installation Guide 21.0 SpecificationsICP-CC404 Installation Guide 22.0 Programming Sheets Programming Sheets22.0 Programming Sheets Burglary zones and four 24-hr zones 22.0 Programming SheetsICP-CC404 Installation Guide 22.0 Programming Sheets 374 to 392 to Strobe Output ICP-CC404 Installation Guide 22.0 Programming Sheets 22.0 Programming Sheets Country Codes PRCICP-CC404 Installation Guide Contents ICP-CC404 Installation Guide Index IndexHold Down Function Pulse Count Bosch Security Systems, Inc. F01U089401-02