ICP-CC404 Installation Guide 15.0 System Reporting Information

Location 332 (Section 15.5 Zone Status Reporting Options on page 61) is ignored when programming the Alarm Restore code and is global for all zones. A zone Restore Report is sent only to the receiving party to which the zone is allocated (for example, Receiver 1 or Receiver 2).

15.5Zone Status Reporting Options

Use Location 332 to select whether Zone Status Reports are sent to Receiver 1 (the default), Receiver 2, or both, Receiver 2 only when Receiver 1 fails, or there is no reporting at all. Table 46 lists the reporting options.

Table 46: Zone Status Reporting Options

Option Description

0No report required

1

Receiver 1

2

Receiver 2

4Receiver 1 and Receiver 2

8Receiver 2 only when Receiver 1 fails

15.6Open/Close Reports

Program the Open Report value in Location 333 (the default value is 11) and the Close Report value in Location 334 (default 12).

An Opening Report (Contact ID Event Code 401) is sent to the base station receiver when the system is disarmed from AWAY Mode. A Closing Report (Contact ID Event Code 401) is sent at the end of Exit Time when the system is armed in AWAY Mode.

If an expanded format is selected, this code is used as the Expansion Code and the user number that armed or disarmed the system follows in the same transmission.

To enable Open and Close Reports in STAY Mode, select Option 2 in Location 178 (refer to Section 12.2 Dialer Options 2 on page 50). To enable Open and Close Reports only after a previous alarm, select Option 1 in Location 178.

If Open and Close Reports are not required, program Locations 333 and 334 as 0.

15.7Open/Close Reporting Options

Use Location 335 to select whether Zone Status Reports are sent to Receiver 1 (the default), Receiver 2, or both, Receiver 2 only when Receiver 1 fails, or there is no reporting at all. Table 47 lists the reporting options.

Table 47: Open/Close Reporting Options

Option Description

0No Open/Close Reports required

1

Receiver 1

2

Receiver 2

4Receiver 1 and Receiver 2

8Receiver 2 only when Receiver 1 fails

15.8Codepad Duress Report

Program the Codepad Duress Report value in Location 336.

The default value is 6.

A Duress Report (Contact ID Event Code 121) is sent to the base station receiver when a user adds 9 to the end of any valid User Code used to disarm the system. This alarm is always silent. A Duress Alarm can be activated during Exit Time (in other words, if the system is armed and then disarmed with a 9 at the end of the User Code before Exit Time expires, a Duress Report is sent). Adding 9 to the end of a User Code when arming the system does not cause a Duress Alarm.

If you want a 3 to activate a Codepad Duress Alarm instead of 9, select Option 2 in Location 430 (refer to Section 18.7 Consumer Options 3 on page 75).

Restore Reports are not sent for this event.

If Duress Reports are not required, program Location 336 as 0.

15.9Codepad Panic Report

Program the Codepad Panic Report value in Location 337 (tens digit) and Location 338 (units digit).

The default values are 7 (tens) and 15 (units).

A Panic Alarm Report (Contact ID Event Code 120) is sent to the base station receiver when a user presses either [1] and [3] or [STAY] and [AWAY] at the same time. A Panic Alarm is audible, but you can program the alarm as silent by selecting Option 1 in Location 425 (refer to Section 18.2 System Options 2 on page 73).

Restore Reports are not sent for this event.

If Panic Reports are not required, program Locations 337 and 338 as 0.

15.10 Codepad Fire Report

Program the Codepad Fire Report value in Location 339 (tens digit) and Location 340 (units digit).

The default values are 7 (tens) and 14 (units).

Bosch Security Systems, Inc. 12/08 F01U089401-02

61

Image 61
Contents ICP-CC404 Installation GuideCopyright Notice ICP-CC404 Installation Guide Copyright NoticeContents ICP-CC404 Installation Guide Contents Figures Tables ICP-CC404 Installation Guide 1.0 Introduction FeaturesIntroduction Quick StartZone Defaults Setting the Date and TimeExample Zone TypesCodepad Indicators ICP-CC404 Installation Guide 2.0 ProgrammingProgramming Programming with the Remote CodepadInstaller’s Programming Mode Commands Installer’s Programming CommandsProgramming with the Programming Key Programming Option BitsCommand 959 Test the Programming Key Command 958 Enable/Disable Zone Status ModeCommand 963 Copy the Programming Key to the Control Panel Command 960 Exit from the Installers Programming ModeCommand 965 Set Up Domestic Dialing Format Command 964 Erase the Programming KeyCommand 966 Enable or Disable Auto Step Mode Example Auto Step Mode Enabled Command 965 DefaultsExample Auto Step Mode Disabled ProgrammingUsing this feature is not recommended Disable Factory DefaultsICP-CC404 Installation Guide 3.0 Codepad Indicators Codepad IndicatorsICP-CP508W Eight Zone LED Codepad ICP-CP508LW Eight Zone LCD Codepad Audible IndicatorsSystem Disarmed Arming the System in Away Mode Disarming the System from Away ModeICP-CC404 Installation Guide 4.0 System Operations System OperationsDisarming the System from Stay Mode Arming the System in Stay ModeEntry Guard Timer for Stay Mode Arming the System in Stay Mode Codepad Panic Alarm Codepad Duress AlarmCodepad Fire Alarm Codepad Medical AlarmFault Descriptions Fault Analysis ModeFault Indicators Low BatteryDate and Time Telephone Line FaultSensor Watch Horn Speaker MonitorIndications from Remote Radio Transmitter Operations Remote Radio Transmitter OperationsRemote Radio User Code Priority Levels Changing or Deleting Remote Radio User CodesArming in Away Mode Codepad Indicators for Remote Radio User NumbersDisarming from Away Mode Arming in Stay ModePanic Alarm Disarming from Stay ModeFour-Channel Remote Radio Hand- Held Transmitter Operations ICP-CC404 Installation Guide 6.0 System Functions Installer Code FunctionsSystem Functions Changing Domestic Phone Numbers Codepad Indicators When Changing Phone NumbersDomestic Dialing Digits Change Telco Arming or Disarming SequenceTelco Arming or Disarming Dialing Digits Codepad Indicators When ChangingTelco Arming or Disarming SequenceSatellite Siren Service Mode Setting Stay Mode 2 ZonesTelephone Monitor Mode Indications Turning Telephone Monitor Mode On and OffEvent Memory Recall Mode Master Code FunctionsMaster Code Functions Remote Radio Numbers Displayed by the Codepad IndicatorsChanging and Deleting User Codes Changing and Deleting Remote Radio User CodesCodepad Indicators When Changing Domestic Telephone Numbers Change Telco Arming or Disarming Sequence Setting Stay Mode 2 Zones Turning Outputs On/Off Hold-Down Functions Remote Arming by Telephone ICP-CC404 Installation Guide 7.0 Remote Arming by TelephoneICP-CC404 Installation Guide 8.0 Alarm Link Software Alarm Link SoftwareRemote Connect ICP-CC404 Installation Guide 9.0 Domestic Dialing Alarm Link OptionsDomestic Dialing Domestic Dialing FunctionSetting Up and Programming Domestic Reporting Dialer Reporting Formats ICP-CC404 Installation Guide 10.0 Dialer Reporting FormatsTransmission Formats Contact ID Format10.1.3 4 + 2 Express Reporting Format Point ID CodesExample Reporting in 4 + 2 Express Format + 2 Express Reporting FormatBasic Pager Reporting Format +2 Express Transmission Code DescriptionsSubscriber ID Number Basic Pager Display InformationZone Status Zone Status Display DescriptionsDialer Information ICP-CC404 Installation Guide 11.0 Dialer InformationPrimary Telephone Number for Receiver 1 and Receiver System StatusHandshake Tone for Receiver 1 and Receiver Secondary Telephone Number for Receiver 1 and ReceiverTransmission Format for Receiver 1 and Receiver Subscriber ID Number for Receiver 1 and ReceiverTelco Arming Sequence Dialing FormatTelco Disarming Sequence Call Back Telephone Number Telephone Line Fault OptionsRing Count Answering Machine BypassDialer Options ICP-CC404 Installation Guide 12.0 Dialer OptionsDialer Options Installer Code Access CodeICP-CC404 Installation Guide 13.0 Access Code User CodesUser Code Priority ICP-CC404 Installation Guide 14.0 Zone Information Day Alarm InformationZone Information EOL Resistor ValueZone Operating Information Zone ProgrammingZone Options Zone Reporting InformationDelay-1 Zone Zone Programming DefaultsDelay-2 Zone Zone Types Instant ZoneHour Holdup Zone Keyswitch ZoneHour Tamper Zone 12 24-Hour Burglary ZoneSilent Alarm Delay Alarm ReportingKeyswitch Zone Options Latching Arm and Disarm in Away ModeLatching Arm and Disarm in Stay Mode Latching Disarm from Away Mode, Stay Mode 1, or Stay ModeLatching Arm in Stay Mode Latching Disarm from Stay Mode 1 or Stay ModeSwinger Shutdown Count for Dialer Swinger Shutdown Count for SirenSystem Reporting Information Zone Status Alarm Restore CodeZone Status Bypass Reports Zone Status Trouble ReportsOpen/Close Reports Zone Status Reporting OptionsOpen/Close Reporting Options Codepad Duress ReportSystem Status AUX Power Supply Fail Restore Report System Status AUX Power Supply Fail ReportSystem Status AC Fail Restore Report System Status Low Battery ReportSystem Status Access Denied System Status Low Battery Restore ReportSystem Status Reporting Options Test Reporting TimeProgrammable Outputs ICP-CC404 Installation Guide 16.0 Programmable OutputsTest Reporting Dialer Options Redirecting Outputs to the Codepad BuzzerOutput Event Types AUX Power Supply Fail Day Alarm EnabledSensor Watch Alarm Codepad Medical AlarmAlarm When in Stay Mode Codepad Tamper Access DeniedAlarm When in Away Mode Mimic System FaultOutput Polarity Normally Open, One-Shot Low with Alarm Normally Open, One-Shot Low with ResetNormally Low, One-Shot Open with Reset Event Type PolaritiesSystem Event Timers Delay Alarm Reporting Time Entry Guard Timer for Stay ModeExit Time Sensor Watch TimeAuto Arming Time Auto Arming Pre-Alert TimerAuto Disarming Time Kiss-Off Wait TimeSystem Options System and Consumer OptionsSequential Handover Delay Silent Access Denied Code RetriesPanel Powers Up Disarmed Arm/Disarm Tracking on Power UpConsumer Options Optional Equipment 19.7 CP5 Eight Zone LCD Codepad CP508LW 19.9 PS101 Power Supply Module19.8 CP105A Night Arm Station 19.10 TF008 Plug Pack TF008Terminal Descriptions Terminals and DescriptionsGlossary Of Terms That an alarm was sent out Domestic alarm reportsStay Mode This mode. Only the installer can program these zonesICP-CC404 Wiring Diagram DiagramsICP-CC404 Component Overlay 4 not connected Warranty Statement SpecificationsAdvice to Users ICP-CC404 Installation Guide 21.0 SpecificationsProgramming Sheets ICP-CC404 Installation Guide 22.0 Programming Sheets22.0 Programming Sheets Burglary zones and four 24-hr zones Programming Sheets 22.0ICP-CC404 Installation Guide 22.0 Programming Sheets 374 to 392 to Strobe Output ICP-CC404 Installation Guide 22.0 Programming Sheets 22.0 Programming Sheets PRC Country CodesICP-CC404 Installation Guide Contents Index ICP-CC404 Installation Guide IndexHold Down Function Pulse Count Bosch Security Systems, Inc. F01U089401-02