ICP-CC404 Installation Guide 17.0 System Event Timers
13 – Normally Low, One-Shot Open with Alarm
This
14 – Normally Low, Latching Open
This polarity is normally 0 V and switches to an open circuit when the event occurs. The output switches back to 0 V when the user holds down [7] on the remote codepad until two beeps sound. Time parameters do not apply to this polarity.
16.4Output Timing
The timing of outputs is calculated by the time base and a multiplier. These two values play different roles depending on the selected polarity. When you program outputs to pulse, you can set both the On and Off times. You can program
The maximum value you can program in the two multiplier locations is 9,9.
Table 55: Time Base Settings
Option | Description |
1200 ms
21 sec
31 minute
41 hour
You can only set the time base settings to one of the values listed in Table 55. The multiplier value is a two- digit decimal number from 00 to 99. For greater accuracy, use 60 sec for
16.5Pulsing Polarities
When programming pulsing polarities, you must set both the On and Off times. The duration, or On time, for an output is determined by the time base selected from one of the options in Table 55. In other words, there are only four possible On times.
The Off time is calculated by multiplying the On time by a decimal number between 00 and 99. If you want an output to operate for 200 ms every 5 sec, program the time settings as:
On Time: 1
Off Time: 2 5
Table 56: Pulsing Time Settings
|
|
|
|
On Time | Off Time | Increments | Tolerance |
|
|
|
|
200 ms | 200 ms to | 200 ms | ±200 ms |
| 19.8 sec |
|
|
1 sec | 1 to 99 sec | 1 sec | ±1 sec |
|
|
|
|
1 min | 1 to 99 min | 1 min | ±1 min |
1 hour | 1 to 99 hr | 1 hr | ± hr |
16.6One-Shot Polarities
The duration, or On time, of an output is the product of the time base and the multiplier.
If you want an output to operate for 5 sec, program the time settings as:
Time Base: 2
Multiplier: 0 5
The On time is calculated by multiplying the time base setting (1 sec) by the multiplier value (05) (for example, 1 x 05 = 5 sec).
Table 57: One-Shot Time Settings
|
|
|
|
On Time | Increments | Tolerance | |
|
|
| |
200 ms to 19.8 sec | 200 ms | ±200 ms | |
1 to 99 sec | 1 sec | ±1 sec | |
1 to | 99 min | 1 min | ±1 min |
1 to | 99 hr | 1 hr | ± hour |
|
|
|
|
17.0 System Event Timers
This section covers the features that involve timing, such as Entry and Exit Times, Sensor Watch Time, Siren Run Time, and System Date and Time.
17.1Programming Entry/Exit Timers
There are two programming locations for Entry Timer 1, Entry Timer 2, Exit Time For AWAY Mode, and Entry Guard Time For STAY Mode.
The first location of the timer allows you to set the timer in increments of 1 sec. The second location allows you to set the timer in increments of 16 sec. Add these two locations together for the total time.
Example
To set the Entry Time to 18 sec, program Location 410 as 2 (2 x 1 sec = 2 sec) and Location 411 as 1 (1 x 16 sec = 16 sec) for a total time of 18 sec (2 + 16 = 18).
17.2Entry Timer 1
Program Entry Timer 1 into Locations 398 (increments of 1 sec) and 399 (increments of 16 sec). The default value for Entry Timer 1 is 20 sec (4 1).
70 | Bosch Security Systems, Inc. 12/08 |