ICP-CC404 Installation Guide 15.0 System Reporting Information

A Battery Test Failure Report (Contact ID Event Code 309) is sent to the base station receiver when the system’s battery voltage falls below 11.2 VDC or when a dynamic battery test detects that a low capacity battery.

The control panel continually monitors the battery voltage. Refer to Section 4.13 Fault Descriptions on page 22 for more information. A dynamic battery test is performed every time the system is armed and every four hours after the control panel is powered up.

If Low Battery Reports are not required, program Locations 352 and 353 as 0.

Outputs 1 to 4 do not operate when the control panel detects a low battery.

15.18System Status – Low Battery Restore Report

Program the Low Battery Restore Report value in Location 354 (tens digit) and Location 355 (units digit).

The default values are 10 (tens) and 6 (units).

A Low Battery Restore Report is sent if the backup battery is restored the next time the system is armed, or when the next dynamic battery test reports the battery test is OK.

If Low Battery Restore Reports are not required, program Locations 354 and 355 as 0.

15.19 System Status – Access Denied

Program the Code Retry Limit in Location 356. The default value is 6.

Program 0 to allow unlimited retries.

Program the Access Denied Report value in Location 357 (tens digit) and Location 358 (units digit).

The default values are 7 (tens) and 12 (units).

An Access Denied Report (Contact ID Event Code

421)is sent to the base station receiver when the number of incorrect code attempts equals the number programmed in Location 356. An Access Denied Alarm is audible, but you can program the alarm as silent by selecting Option 8 in Location 425 (refer to Section 18.2 System Options 2 on page 73).

Restore reports for this event are not sent.

If Access Denied reports are not required, program Locations 357 and 358 as 0.

Code Retries

The Code Retries feature restricts the number of times an invalid User Code can be entered in an attempt to operate the system. Location 356 sets the number of incorrect code attempts that causes an alarm. When the number of incorrect code attempts equals the number programmed in this location, the system performs these actions:

Activates the sirens, internal screamers, and strobes connected to the control panel. Select Option 8 in Location 425 (refer to Section 18.2 System Options 2 on page 73) to change this alarm to silent.

Shuts down all codepads connected to the control panel and locks them out for the time period programmed in Location 410 (refer to Section 17.8 Codepad Lockout Time on page 71).

Sends an Access Denied Report (Contact ID Event Code 421) to the base station receiver.

Each time the system is armed or disarmed, the Code Retries counter is reset. You can program the counter to a value from 1 to 15. If you want the number of incorrect code attempts to be unlimited, program a 0 in Location 356. In this case, the Access Denied Report is never generated and the system does not perform the three actions listed above. This function works when the system is armed or disarmed.

15.20 System Status Reporting Options

Use Location 359 to select whether System Status Reports are sent to Receiver 1 (the default), Receiver 2, or both, Receiver 2 only when Receiver 1 fails, or there is no reporting at all. Table 47 lists the reporting options.

Table 49: System Status Reporting Options

Option Description

0No System Status Reports required

1

Receiver 1

2

Receiver 2

 

 

4Receiver 1 and Receiver 2

8Receiver 2 only when Receiver 1 fails

15.21 Test Reporting Time

Program the Test Reporting Time into Locations 360 to 366 as described in Table 50 on page 64.

Bosch Security Systems, Inc. 12/08 F01U089401-02

63

Image 63
Contents ICP-CC404 Installation GuideCopyright Notice ICP-CC404 Installation Guide Copyright NoticeContents ICP-CC404 Installation Guide Contents Figures Tables Quick Start FeaturesICP-CC404 Installation Guide 1.0 Introduction IntroductionZone Types Setting the Date and TimeZone Defaults ExampleProgramming with the Remote Codepad ICP-CC404 Installation Guide 2.0 ProgrammingCodepad Indicators ProgrammingProgramming Option Bits Installer’s Programming CommandsInstaller’s Programming Mode Commands Programming with the Programming KeyCommand 959 Test the Programming Key Command 958 Enable/Disable Zone Status ModeCommand 963 Copy the Programming Key to the Control Panel Command 960 Exit from the Installers Programming ModeCommand 964 Erase the Programming Key Command 965 Set Up Domestic Dialing FormatCommand 966 Enable or Disable Auto Step Mode Programming Command 965 DefaultsExample Auto Step Mode Enabled Example Auto Step Mode DisabledUsing this feature is not recommended Disable Factory DefaultsCodepad Indicators ICP-CC404 Installation Guide 3.0 Codepad IndicatorsICP-CP508W Eight Zone LED Codepad Audible Indicators ICP-CP508LW Eight Zone LCD CodepadSystem Disarmed System Operations Disarming the System from Away ModeArming the System in Away Mode ICP-CC404 Installation Guide 4.0 System OperationsArming the System in Stay Mode Disarming the System from Stay ModeEntry Guard Timer for Stay Mode Arming the System in Stay Mode Codepad Medical Alarm Codepad Duress AlarmCodepad Panic Alarm Codepad Fire AlarmLow Battery Fault Analysis ModeFault Descriptions Fault IndicatorsHorn Speaker Monitor Telephone Line FaultDate and Time Sensor WatchChanging or Deleting Remote Radio User Codes Remote Radio Transmitter OperationsIndications from Remote Radio Transmitter Operations Remote Radio User Code Priority LevelsArming in Stay Mode Codepad Indicators for Remote Radio User NumbersArming in Away Mode Disarming from Away ModeDisarming from Stay Mode Panic AlarmFour-Channel Remote Radio Hand- Held Transmitter Operations Installer Code Functions ICP-CC404 Installation Guide 6.0 System FunctionsSystem Functions Change Telco Arming or Disarming Sequence Codepad Indicators When Changing Phone NumbersChanging Domestic Phone Numbers Domestic Dialing DigitsSequence Codepad Indicators When ChangingTelco Arming or Disarming Dialing Digits Telco Arming or DisarmingSatellite Siren Service Mode Setting Stay Mode 2 ZonesMaster Code Functions Turning Telephone Monitor Mode On and OffTelephone Monitor Mode Indications Event Memory Recall ModeChanging and Deleting Remote Radio User Codes Remote Radio Numbers Displayed by the Codepad IndicatorsMaster Code Functions Changing and Deleting User CodesCodepad Indicators When Changing Domestic Telephone Numbers Change Telco Arming or Disarming Sequence Setting Stay Mode 2 Zones Turning Outputs On/Off Hold-Down Functions Remote Arming by Telephone ICP-CC404 Installation Guide 7.0 Remote Arming by TelephoneAlarm Link Software ICP-CC404 Installation Guide 8.0 Alarm Link SoftwareRemote Connect Domestic Dialing Function Alarm Link OptionsICP-CC404 Installation Guide 9.0 Domestic Dialing Domestic DialingSetting Up and Programming Domestic Reporting Contact ID Format ICP-CC404 Installation Guide 10.0 Dialer Reporting FormatsDialer Reporting Formats Transmission Formats+ 2 Express Reporting Format Point ID Codes10.1.3 4 + 2 Express Reporting Format Example Reporting in 4 + 2 Express FormatBasic Pager Reporting Format +2 Express Transmission Code DescriptionsZone Status Display Descriptions Basic Pager Display InformationSubscriber ID Number Zone StatusSystem Status ICP-CC404 Installation Guide 11.0 Dialer InformationDialer Information Primary Telephone Number for Receiver 1 and ReceiverSubscriber ID Number for Receiver 1 and Receiver Secondary Telephone Number for Receiver 1 and ReceiverHandshake Tone for Receiver 1 and Receiver Transmission Format for Receiver 1 and ReceiverDialing Format Telco Arming SequenceTelco Disarming Sequence Answering Machine Bypass Telephone Line Fault OptionsCall Back Telephone Number Ring CountICP-CC404 Installation Guide 12.0 Dialer Options Dialer OptionsDialer Options User Codes Access CodeInstaller Code ICP-CC404 Installation Guide 13.0 Access CodeUser Code Priority EOL Resistor Value Day Alarm InformationICP-CC404 Installation Guide 14.0 Zone Information Zone InformationZone Reporting Information Zone ProgrammingZone Operating Information Zone OptionsZone Types Instant Zone Zone Programming DefaultsDelay-1 Zone Delay-2 Zone12 24-Hour Burglary Zone Keyswitch ZoneHour Holdup Zone Hour Tamper ZoneLatching Arm and Disarm in Away Mode Delay Alarm ReportingSilent Alarm Keyswitch Zone OptionsLatching Disarm from Stay Mode 1 or Stay Mode Latching Disarm from Away Mode, Stay Mode 1, or Stay ModeLatching Arm and Disarm in Stay Mode Latching Arm in Stay ModeSwinger Shutdown Count for Dialer Swinger Shutdown Count for SirenZone Status Trouble Reports Zone Status Alarm Restore CodeSystem Reporting Information Zone Status Bypass ReportsCodepad Duress Report Zone Status Reporting OptionsOpen/Close Reports Open/Close Reporting OptionsSystem Status Low Battery Report System Status AUX Power Supply Fail ReportSystem Status AUX Power Supply Fail Restore Report System Status AC Fail Restore ReportTest Reporting Time System Status Low Battery Restore ReportSystem Status Access Denied System Status Reporting OptionsRedirecting Outputs to the Codepad Buzzer ICP-CC404 Installation Guide 16.0 Programmable OutputsProgrammable Outputs Test Reporting Dialer OptionsOutput Event Types Codepad Medical Alarm Day Alarm EnabledAUX Power Supply Fail Sensor Watch AlarmMimic System Fault Codepad Tamper Access DeniedAlarm When in Stay Mode Alarm When in Away ModeOutput Polarity Event Type Polarities Normally Open, One-Shot Low with ResetNormally Open, One-Shot Low with Alarm Normally Low, One-Shot Open with ResetSystem Event Timers Sensor Watch Time Entry Guard Timer for Stay ModeDelay Alarm Reporting Time Exit TimeKiss-Off Wait Time Auto Arming Pre-Alert TimerAuto Arming Time Auto Disarming TimeSystem Options System and Consumer OptionsArm/Disarm Tracking on Power Up Silent Access Denied Code RetriesSequential Handover Delay Panel Powers Up DisarmedConsumer Options Optional Equipment 19.10 TF008 Plug Pack TF008 19.9 PS101 Power Supply Module19.7 CP5 Eight Zone LCD Codepad CP508LW 19.8 CP105A Night Arm StationTerminal Descriptions Terminals and DescriptionsGlossary Of Terms This mode. Only the installer can program these zones Domestic alarm reportsThat an alarm was sent out Stay ModeICP-CC404 Wiring Diagram DiagramsICP-CC404 Component Overlay 4 not connected ICP-CC404 Installation Guide 21.0 Specifications SpecificationsWarranty Statement Advice to UsersProgramming Sheets ICP-CC404 Installation Guide 22.0 Programming Sheets22.0 Programming Sheets Burglary zones and four 24-hr zones Programming Sheets 22.0ICP-CC404 Installation Guide 22.0 Programming Sheets 374 to 392 to Strobe Output ICP-CC404 Installation Guide 22.0 Programming Sheets 22.0 Programming Sheets PRC Country CodesICP-CC404 Installation Guide Contents Index ICP-CC404 Installation Guide IndexHold Down Function Pulse Count Bosch Security Systems, Inc. F01U089401-02