Bosch Appliances manual ICP-CC404 Installation Guide 22.0 Programming Sheets

Page 91

ICP-CC404 Installation Guide 22.0 Programming Sheets

Location

 

 

 

Options/Notes

 

 

 

 

 

 

 

Default/

 

Function

 

 

 

 

 

 

Programming Entry

 

 

 

 

 

 

 

 

 

368 to 397

The fifth and sixth locations of the output definition provide the time base multiplier. Enter a value between

Outputs

01 and 99.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(continued)

One Shot Mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When you program the output polarity as one shot, the time base is multiplied by the time base multiplier.

 

For example, if the time base = 2 and the multiplier = 05, the output operates for 5 sec.

 

 

 

 

 

 

 

 

Pulsing Mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When you program the output polarity as pulsing, the time base becomes the ON time and the multiplier

 

 

 

becomes the OFF time. The OFF time is the time base, which is multiplied by the multiplier. For example,

 

 

 

if you want the output to pulse 1 sec ON and 5 sec OFF, you would program time base as 2 and the

 

 

 

multiplier as 5.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

398 to 399

 

 

 

Location 398: increments of 1 sec (0 to 15 sec)

 

 

 

4

1

Entry Time 1

 

 

 

Location 399: increments of 16 sec (0 to 240 sec)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refer to page 70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400 to 401

 

 

 

Location 400: increments of 1 sec (0 to 15 sec)

 

 

 

8

2

Entry Time 2

 

 

 

Location 401: increments of 16 sec (0 to 240 sec)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refer to page 71

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

402 to 403

 

 

 

Location 402: increments of 1 sec (0 to 15 sec)

 

 

 

12

3

Exit Time (AWAY/STAY Modes)

 

 

Location 403: increments of 16 sec (0 to 240 sec)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refer to page 71

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

404 to 405

 

 

 

Location 404: increments of 1 sec (0 to 15 sec)

 

 

 

0

0

Entry Guard Time for STAY Mode

 

 

Location 405: increments of 16 sec (0 to 240 sec)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refer to page 71

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

406 to 407

 

 

 

Location 406: increments of 1 sec (0 to 15 sec)

 

 

 

0

0

Delay Alarm Report Time

 

 

Location 407: increments of 16 sec (0 to 240 sec)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refer to page 71

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

408 to 409

 

 

 

Location 408: increments of days (tens digit)

 

 

 

0

0

Sensor Watch Time

 

 

Location 409: increments of days (units digit)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refer to page 71

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

410

 

0

No lockout

 

 

 

 

 

 

 

0

Codepad Lockout Time

 

1 to 15 Increments of 10 sec (10 sec to 150 sec)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refer to page 71

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

411

 

0

No siren time

 

 

 

 

 

 

 

5

Siren Run Time

 

 

1 to 15 Increments of 1 min (1 min to 15 min)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refer to page 71

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

412

 

 

0 to 15 (slowest to fastest frequency)

 

 

 

 

 

 

 

7

Siren Sound Rate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refer to page 71

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

413

 

0

No pre-alert time

 

 

 

 

 

 

 

1

Auto Arming Pre-Alert Time

 

1 to 15 Increments of 5 min (5 min to 75 min)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refer to page 71

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

414 to 417

 

 

 

Location 414: Hour of day (tens digit)

 

 

0

0

0

0

Auto Arming Time

 

 

Location 415: Hour of day (units digit)

 

 

 

 

 

 

 

 

 

Refer to page 72

 

 

Location 416: Minute of day (tens digit)

 

 

 

 

 

 

 

 

 

 

 

 

 

Location 417: Minute of day (units digit)

 

 

 

 

 

 

 

 

 

418 to 421

 

 

 

Location 418: Hour of day (tens digit)

 

 

0

0

0

0

Auto Disarming Time

 

 

Location 419: Hour of day (units digit)

 

 

 

 

 

 

 

 

 

Refer to page 72

 

 

Location 420: Minute of day (tens digit)

 

 

 

 

 

 

 

 

 

 

 

 

 

Location 421: Minute of day (units digit)

 

 

 

 

 

 

 

 

 

422

 

 

0 to 15 Increments of 500 ms (500 ms to 8 sec)

 

 

 

 

 

 

 

3

Kiss-Off Wait Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refer to page 72

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

423

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

424

 

 

1 Bosch smart lockout allowed

 

 

 

 

 

 

 

1

System Options 1

 

2 Horn speaker monitor

 

 

 

 

 

 

 

 

 

Refer to page 73

 

4 Strobe indication for radio arm/disarm

 

 

 

 

 

 

 

 

 

 

 

 

8 Horn speaker beeps for radio arm/disarm

 

 

 

 

 

 

 

 

 

Bosch Security Systems, Inc. 12/08 F01U089401-02

91

Image 91
Contents ICP-CC404 Installation GuideCopyright Notice ICP-CC404 Installation Guide Copyright NoticeContents ICP-CC404 Installation Guide Contents Figures Tables Quick Start FeaturesICP-CC404 Installation Guide 1.0 Introduction IntroductionZone Types Setting the Date and TimeZone Defaults ExampleProgramming with the Remote Codepad ICP-CC404 Installation Guide 2.0 ProgrammingCodepad Indicators ProgrammingProgramming Option Bits Installer’s Programming CommandsInstaller’s Programming Mode Commands Programming with the Programming KeyCommand 959 Test the Programming Key Command 958 Enable/Disable Zone Status ModeCommand 963 Copy the Programming Key to the Control Panel Command 960 Exit from the Installers Programming ModeCommand 965 Set Up Domestic Dialing Format Command 964 Erase the Programming KeyCommand 966 Enable or Disable Auto Step Mode Programming Command 965 DefaultsExample Auto Step Mode Enabled Example Auto Step Mode DisabledUsing this feature is not recommended Disable Factory DefaultsICP-CC404 Installation Guide 3.0 Codepad Indicators Codepad IndicatorsICP-CP508W Eight Zone LED Codepad ICP-CP508LW Eight Zone LCD Codepad Audible IndicatorsSystem Disarmed System Operations Disarming the System from Away ModeArming the System in Away Mode ICP-CC404 Installation Guide 4.0 System OperationsDisarming the System from Stay Mode Arming the System in Stay ModeEntry Guard Timer for Stay Mode Arming the System in Stay Mode Codepad Medical Alarm Codepad Duress AlarmCodepad Panic Alarm Codepad Fire AlarmLow Battery Fault Analysis ModeFault Descriptions Fault IndicatorsHorn Speaker Monitor Telephone Line FaultDate and Time Sensor WatchChanging or Deleting Remote Radio User Codes Remote Radio Transmitter OperationsIndications from Remote Radio Transmitter Operations Remote Radio User Code Priority LevelsArming in Stay Mode Codepad Indicators for Remote Radio User NumbersArming in Away Mode Disarming from Away ModePanic Alarm Disarming from Stay ModeFour-Channel Remote Radio Hand- Held Transmitter Operations ICP-CC404 Installation Guide 6.0 System Functions Installer Code FunctionsSystem Functions Change Telco Arming or Disarming Sequence Codepad Indicators When Changing Phone NumbersChanging Domestic Phone Numbers Domestic Dialing DigitsSequence Codepad Indicators When ChangingTelco Arming or Disarming Dialing Digits Telco Arming or DisarmingSatellite Siren Service Mode Setting Stay Mode 2 ZonesMaster Code Functions Turning Telephone Monitor Mode On and OffTelephone Monitor Mode Indications Event Memory Recall ModeChanging and Deleting Remote Radio User Codes Remote Radio Numbers Displayed by the Codepad IndicatorsMaster Code Functions Changing and Deleting User CodesCodepad Indicators When Changing Domestic Telephone Numbers Change Telco Arming or Disarming Sequence Setting Stay Mode 2 Zones Turning Outputs On/Off Hold-Down Functions Remote Arming by Telephone ICP-CC404 Installation Guide 7.0 Remote Arming by TelephoneICP-CC404 Installation Guide 8.0 Alarm Link Software Alarm Link SoftwareRemote Connect Domestic Dialing Function Alarm Link OptionsICP-CC404 Installation Guide 9.0 Domestic Dialing Domestic DialingSetting Up and Programming Domestic Reporting Contact ID Format ICP-CC404 Installation Guide 10.0 Dialer Reporting FormatsDialer Reporting Formats Transmission Formats+ 2 Express Reporting Format Point ID Codes10.1.3 4 + 2 Express Reporting Format Example Reporting in 4 + 2 Express FormatBasic Pager Reporting Format +2 Express Transmission Code DescriptionsZone Status Display Descriptions Basic Pager Display InformationSubscriber ID Number Zone StatusSystem Status ICP-CC404 Installation Guide 11.0 Dialer InformationDialer Information Primary Telephone Number for Receiver 1 and ReceiverSubscriber ID Number for Receiver 1 and Receiver Secondary Telephone Number for Receiver 1 and ReceiverHandshake Tone for Receiver 1 and Receiver Transmission Format for Receiver 1 and ReceiverTelco Arming Sequence Dialing FormatTelco Disarming Sequence Answering Machine Bypass Telephone Line Fault OptionsCall Back Telephone Number Ring CountDialer Options ICP-CC404 Installation Guide 12.0 Dialer OptionsDialer Options User Codes Access CodeInstaller Code ICP-CC404 Installation Guide 13.0 Access CodeUser Code Priority EOL Resistor Value Day Alarm InformationICP-CC404 Installation Guide 14.0 Zone Information Zone InformationZone Reporting Information Zone ProgrammingZone Operating Information Zone OptionsZone Types Instant Zone Zone Programming DefaultsDelay-1 Zone Delay-2 Zone12 24-Hour Burglary Zone Keyswitch ZoneHour Holdup Zone Hour Tamper ZoneLatching Arm and Disarm in Away Mode Delay Alarm ReportingSilent Alarm Keyswitch Zone OptionsLatching Disarm from Stay Mode 1 or Stay Mode Latching Disarm from Away Mode, Stay Mode 1, or Stay ModeLatching Arm and Disarm in Stay Mode Latching Arm in Stay ModeSwinger Shutdown Count for Dialer Swinger Shutdown Count for SirenZone Status Trouble Reports Zone Status Alarm Restore CodeSystem Reporting Information Zone Status Bypass ReportsCodepad Duress Report Zone Status Reporting OptionsOpen/Close Reports Open/Close Reporting OptionsSystem Status Low Battery Report System Status AUX Power Supply Fail ReportSystem Status AUX Power Supply Fail Restore Report System Status AC Fail Restore ReportTest Reporting Time System Status Low Battery Restore ReportSystem Status Access Denied System Status Reporting OptionsRedirecting Outputs to the Codepad Buzzer ICP-CC404 Installation Guide 16.0 Programmable OutputsProgrammable Outputs Test Reporting Dialer OptionsOutput Event Types Codepad Medical Alarm Day Alarm EnabledAUX Power Supply Fail Sensor Watch AlarmMimic System Fault Codepad Tamper Access DeniedAlarm When in Stay Mode Alarm When in Away ModeOutput Polarity Event Type Polarities Normally Open, One-Shot Low with ResetNormally Open, One-Shot Low with Alarm Normally Low, One-Shot Open with ResetSystem Event Timers Sensor Watch Time Entry Guard Timer for Stay ModeDelay Alarm Reporting Time Exit TimeKiss-Off Wait Time Auto Arming Pre-Alert TimerAuto Arming Time Auto Disarming TimeSystem Options System and Consumer OptionsArm/Disarm Tracking on Power Up Silent Access Denied Code RetriesSequential Handover Delay Panel Powers Up DisarmedConsumer Options Optional Equipment 19.10 TF008 Plug Pack TF008 19.9 PS101 Power Supply Module19.7 CP5 Eight Zone LCD Codepad CP508LW 19.8 CP105A Night Arm StationTerminal Descriptions Terminals and DescriptionsGlossary Of Terms This mode. Only the installer can program these zones Domestic alarm reportsThat an alarm was sent out Stay ModeICP-CC404 Wiring Diagram DiagramsICP-CC404 Component Overlay 4 not connected ICP-CC404 Installation Guide 21.0 Specifications SpecificationsWarranty Statement Advice to UsersProgramming Sheets ICP-CC404 Installation Guide 22.0 Programming Sheets22.0 Programming Sheets Burglary zones and four 24-hr zones Programming Sheets 22.0ICP-CC404 Installation Guide 22.0 Programming Sheets 374 to 392 to Strobe Output ICP-CC404 Installation Guide 22.0 Programming Sheets 22.0 Programming Sheets PRC Country CodesICP-CC404 Installation Guide Contents Index ICP-CC404 Installation Guide IndexHold Down Function Pulse Count Bosch Security Systems, Inc. F01U089401-02