Toshiba VF-S11 manual Cee

Page 52

 

 

 

 

 

 

 

 

 

 

 

E6581160

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Communication

 

 

Minimum

 

 

 

 

 

 

 

 

 

 

Title

Function

Unit

setting unit

 

 

Adjustment range

Default

User

 

Reference

 

 

 

No.

Panel/Commun

 

 

setting

setting

 

E6581158

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ication

 

 

 

 

 

 

 

 

 

 

HOUN

0005

Meter selection

-

-

0:

Output frequency

0

 

 

5.5

 

 

 

 

 

 

 

 

1:

Output current

 

 

 

 

 

 

 

 

 

 

 

 

2:

Set frequency

 

 

 

 

 

 

 

 

 

 

 

 

3:

DC voltage

 

 

 

 

 

 

 

 

 

 

 

 

4:

Output voltage command value

 

 

 

 

 

 

 

 

 

 

 

 

5:

Input power

 

 

 

 

 

 

 

 

 

 

 

 

6:

Output power

 

 

 

 

 

 

 

 

 

 

 

 

7:

Torque

 

 

 

 

 

 

 

 

 

 

 

 

8:

Torque current

 

 

 

 

 

 

 

 

 

 

 

 

9:

Motor cumulative load factor

 

 

 

 

 

 

 

 

 

 

 

 

10: Inverter cumulative load factor

 

 

 

 

 

 

 

 

 

 

 

 

11: PBR (braking reactor) cumulative

 

 

 

 

 

 

 

 

 

 

 

 

 

load factor

 

 

 

 

 

 

 

 

 

 

 

 

12: Frequency setting value (after

 

 

 

 

 

 

 

 

 

 

 

 

 

PID)

 

 

 

 

 

 

 

 

 

 

 

 

13: VIA Input value

 

 

 

 

 

 

 

 

 

 

 

 

14: VIB Input value

 

 

 

 

 

 

 

 

 

 

 

 

15: Fixed output 1 (Output current:

 

 

 

 

 

 

 

 

 

 

 

 

 

100%)

 

 

 

 

 

 

 

 

 

 

 

 

16: Fixed output 2 (Output current:

 

 

 

 

 

 

 

 

 

 

 

 

 

50%)

 

 

 

 

 

 

 

 

 

 

 

 

17: Fixed output 3 (Other than the

 

 

 

 

 

 

 

 

 

 

 

 

 

output current: 100%)

 

 

 

 

 

 

 

 

 

 

 

 

18: Serial communication data

 

 

 

 

 

 

 

 

 

 

 

 

19: For adjustments (HO set value is

 

 

 

 

 

 

 

 

 

 

 

 

 

displayed.)

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HO

0006

Meter adjustment

-

-

-

 

 

-

 

 

5.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V[R

0007

Default setting

-

-

0: -

 

 

0

 

 

4.2.6

 

 

 

 

 

 

 

 

1: 50Hz default setting

 

 

 

4.2.7

 

 

 

 

 

 

 

 

2: 60Hz default setting

 

 

 

5.6

 

 

 

 

 

 

 

 

3: Default setting (Initialization)

 

 

 

 

 

 

 

 

 

 

 

 

4: Trip record clear

 

 

 

 

 

 

 

 

 

 

 

 

5: Cumulative operation time clear

 

 

 

 

 

 

 

 

 

 

 

 

6: Initialization of type information

 

 

 

 

 

 

 

 

 

 

 

 

7: Save user-setting parameters

 

 

 

 

 

 

 

 

 

 

 

 

8. Load user-setting parameters

 

 

 

 

 

 

 

 

 

 

 

 

9. Cumulative fan operation time

 

 

 

 

 

 

 

 

 

 

 

 

record clears

 

 

 

 

 

 

 

HT

0008

Forward/reverse

-

-

0: Forward run

0

 

 

5.7

 

 

 

 

 

run selection

 

 

1: Reverse run

 

 

 

 

 

 

 

 

 

(Operation panel)

 

 

2: Forward run (F/R switching

 

 

 

 

 

 

 

 

 

 

 

 

possible)

 

 

 

 

 

 

 

 

 

 

 

 

3: Reverse run (F/R switching

 

 

 

 

 

 

 

 

 

 

 

 

possible)

 

 

 

 

 

 

 

CEE

0009

Acceleration time

S

0.1/0.1

0.0-3200

10.0

 

 

5.1.2

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

FGE

0010

Deceleration time

S

0.1/0.1

0.0-3200

10.0

 

 

5.1.2

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

HJ

0011

Maximum

Hz

0.1/0.01

30.0-500.0

80.0

 

 

5.8

 

 

 

 

 

frequency

 

 

 

 

 

 

 

 

 

 

 

 

WN

0012

Upper limit

Hz

0.1/0.01

0.5-

HJ

50.0 (WP)

 

 

5.9

 

 

 

 

 

frequency

 

 

 

 

 

60.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(WN, AN)

 

 

 

 

 

 

NN

0013

Lower limit

Hz

0.1/0.01

0.0-

WN

0.0

 

 

5.9

 

 

 

 

 

frequency

 

 

 

 

 

 

 

 

 

 

 

 

XN

0014

Base frequency 1

Hz

0.1/0.01

25-500.0

50.0 (WP)

 

 

5.10

 

 

 

 

 

 

 

 

 

 

 

60.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(WN, AN)

 

 

 

 

 

 

XNX

0409

Base frequency

V

1/0.1

50-330 (240V class)

*3

 

 

5.10

 

 

 

 

 

voltage 1

 

 

50-660 (500/600V class)

 

 

 

6.13.6

 

 

*3 : 230 (240V class), 460 (500V class), 575V (600V class)

51

Image 52
Contents For 3-phase induction motors Industrial InverterSafety precautions Meanings of symbolsSafety precautions Explanation of markingsGeneral Operation Transportation & installation WiringOperations When retry function is selected inverter Maintenance and inspection Contents  Read first Check product purchaseCD-ROM E6581167 Contents of the product InstallationStandard connection diagram ConnectionStandard connections VF-S11FLC FLBFLA PLC OUTPower circuit terminals Selection of wiring materialsPower circuit Description of terminalsControl circuit terminals Control circuit terminals SW124VDC PLC VIAPTC FLB FLARY RC Slide switch SW1PLC Source Positive logic SW1 Source PLC Sink Operations Simplified Operation of the VF-S11Eoqf HoqfHow to start and stop Start and stop using the operation panel keys EOQF=Coast stop HOQF= How to set the frequencyExample of operating a run from the panel Setting the frequency using the operation panel HOQF= or  Frequency settingHow to operate the VF-S11 Running and stopping using the operation panelEx.2 Running and stopping using external signals Ex.3VIA Panel jog mode Status monitor mode Mode for monitoring all inverter statusBasic VF-S11 operations Standard monitor mode Flow of status monitor modePast trip record detained monitor mode How to set parameters Parameters for detailed and special setting. SeeWhen you adjust the inverter repeatedly using Same parameter. Parameter name CWJ. See How to set the basic parameters⇔HJ  How to set extended parameters~H Example of parameter setting Search and resetting of changed parameters I4WHow to search and reprogram parameters   ⇔ CEE Parameters that cannot be changed while running How to use the history function⇔CEE How to save/load the user setting parameters Returning all parameters to standard default settingKpkv Monitoring the operation status Status monitor modeStatus monitor under normal conditions Iiii Pgtt ⇔ Display of detailed information on a past trip Display of trip information Trip code displayDisplay of trip information at the occurrence of a trip Example of call-up of trip informationOFF VIA VIB RES QR ⇔Cumulative E6581160 Measures to satisfy the standards How to cope with the CE directiveAbout the EMC directive Measures to satisfy the EMC directive Three-phase 500V class Example of wiring About the low-voltage directiveCompliance with Installation Compliance with UL Standard and CSA StandardMeasures to satisfy the low-voltage directive Compliance with ConnectionAIC, Fuse and Wire sizes Motor thermal protectionAIC a AWGTable of parameters and data User parametersBasic parameters Four navigation functionsCEE QNO Extended parameters Input/output parametersFrequency parameters   Operation mode parameters   Torque boost parameters Acceleration/deceleration time parameters Protection parameters  Output parameters Operation panel parametersCommunication parameters PM motor parameters Default settings by inverter rating XD/H       Table of input terminal functions AD2+SS3+AD2 , H, H, HTable of output terminal functions AD3On QE-,QR-,QJ, ,QJ,WR,GH,WE,QN-,QNT Fcvibn Models and their standard specifications SpecificationsStandard specifications Common specification CharacteristicsSpecification Outside dimensions and mass Outside dimensions and massOutline drawing VF-S11Fig.D Before making a service call Trip information and remedies Trip causes/warnings and remediesQNT   Industrial and Power Systems & Services Company