Toshiba VF-S11 manual Control circuit terminals, SW1, 24VDC PLC, Via

Page 15

2

E6581160

QControl circuit terminals

Terminal

Input/output

 

Function

Electrical

 

Inverter internal circuits

symbol

 

specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shorting across F-CC causes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F

Input

input

forward rotation; open causes slow-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

down and stop. (When ST is always

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

contact

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shorting across R-CC causes

 

 

 

24V

SW1

R

Input

reverse rotation; open causes slow-

No voltage

 

 

 

SINK

PLC

down and stop. (When ST is always

 

 

 

 

 

 

SOURCE

 

 

programmable

contact input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24Vdc-5mA or less

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This inverter protective function is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

disabled if RES are CC is connected.

 

 

PLC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RES

Input

Shorting RES and CC has no effect

*Sink/Source/PLC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

when the inverter is in a normal

selectable using

 

820

 

 

 

 

 

 

 

 

 

 

 

 

 

Multifunction

condition.

SW1

 

 

4.7K

 

 

 

 

 

 

 

 

 

 

 

 

 

Shorting across S1-CC causes

 

 

 

 

 

 

 

 

 

 

 

 

 

S1

Input

 

F

S3

 

 

 

 

 

 

 

 

 

 

 

 

 

preset speed operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S2

Input

Shorting across S2-CC causes

 

Factory default setting

preset speed operation.

 

S3

Input

Shorting across S3-CC causes

 

WN, AN type : SINK side

 

 

 

 

WP type : SOURCE side

 

preset speed operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

External 24Vdc power input

24VDC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PLC

When the source logic is used, a common

(Insulation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(common)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

terminal is connected.

resistance: DC50V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC

Common to

Control circuit's equipotential terminal (3

 

 

CC

 

 

 

 

 

 

 

 

 

 

 

Input/output

terminals)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+24V

PP

Output

Analog power supply output

10Vdc

PP

conversion

(permissible load

 

 

 

 

Voltage

 

 

 

current: 10mA)

 

 

 

 

 

 

 

0.47

 

 

 

Multifunction programmable analog input.

 

 

 

 

 

 

Factory default setting: 0~10Vdc and

 

 

 

 

 

 

0~60Hz (0~50Hz) frequency input.

 

 

 

 

 

 

The function can be changed to

10Vdc

 

 

+5V

 

 

4~20mAdc (0~20mA) current input by

(internal impedance:

 

 

 

 

 

flipping the dip switch to the I position.

 

15k

300

 

 

30kΩ)

 

VIA

Input

 

 

VIA

 

By changing parameter setting, this

 

VIA

V

15k

 

 

 

 

 

 

terminal can also be used as a

4-20mA

I

 

 

 

 

 

 

multifunction programmable contact input

(internal impedance:

 

 

 

 

 

terminal. When using the sink logic, be

250Ω)

 

 

250

 

 

sure to insert a resistor between P24-VIA

 

 

 

 

 

 

 

 

 

 

 

(4.7 kΩ―1/2 W). Also move the VIA dip

 

 

 

 

 

 

switch to the V position.

 

 

 

 

14

Image 15
Contents Industrial Inverter For 3-phase induction motorsExplanation of markings Safety precautionsMeanings of symbols Safety precautionsGeneral Operation Wiring Transportation & installationOperations Maintenance and inspection When retry function is selected inverter Contents  Check product purchase Read firstCD-ROM E6581167 Installation Contents of the productVF-S11 Standard connection diagramConnection Standard connections PLC OUT FLC FLB FLADescription of terminals Power circuit terminalsSelection of wiring materials Power circuitControl circuit terminals VIA Control circuit terminalsSW1 24VDC PLCFLB FLA PTCRY RC Slide switch SW1PLC Source Positive logic SW1 Source PLC Sink Hoqf OperationsSimplified Operation of the VF-S11 Eoqf How to start and stopStart and stop using the operation panel keys EOQF= Coast stopHow to set the frequency HOQF=Example of operating a run from the panel Frequency setting Setting the frequency using the operation panel HOQF= or Running and stopping using the operation panel How to operate the VF-S11Ex.2 Ex.3 Running and stopping using external signalsVIA Status monitor mode Mode for monitoring all inverter status Panel jog modeBasic VF-S11 operations Flow of status monitor mode Standard monitor modePast trip record detained monitor mode Same parameter. Parameter name CWJ. See How to set parametersParameters for detailed and special setting. See When you adjust the inverter repeatedly usingHow to set the basic parameters ⇔HJ How to set extended parameters ~H Search and resetting of changed parameters I4W Example of parameter settingHow to search and reprogram parameters   ⇔ CEE How to use the history function Parameters that cannot be changed while running⇔CEE Returning all parameters to standard default setting How to save/load the user setting parametersKpkv Status monitor mode Monitoring the operation statusStatus monitor under normal conditions Iiii  Pgtt ⇔Display of detailed information on a past trip Example of call-up of trip information Display of trip informationTrip code display Display of trip information at the occurrence of a tripQR ⇔ OFF VIA VIB RESCumulative E6581160 How to cope with the CE directive Measures to satisfy the standardsAbout the EMC directive Measures to satisfy the EMC directive Three-phase 500V class About the low-voltage directive Example of wiringCompliance with Connection Compliance with InstallationCompliance with UL Standard and CSA Standard Measures to satisfy the low-voltage directiveAWG AIC, Fuse and Wire sizesMotor thermal protection AIC aFour navigation functions Table of parameters and dataUser parameters Basic parametersCEE  QNOInput/output parameters Extended parametersFrequency parameters   Operation mode parameters   Torque boost parameters Protection parameters Acceleration/deceleration time parameters  Operation panel parameters Output parametersCommunication parameters PM motor parameters XD/H        Default settings by inverter ratingAD2 Table of input terminal functions, H, H, H +SS3+AD2AD3 Table of output terminal functions,QJ,WR,GH,WE, On QE-,QR-,QJ,QN-,QNT Fcvibn Specifications Models and their standard specificationsStandard specifications Characteristics Common specificationSpecification Outside dimensions and mass Outside dimensions and massVF-S11 Outline drawingFig.D Trip causes/warnings and remedies Before making a service call Trip information and remediesQNT   Industrial and Power Systems & Services Company