Toshiba VF-S11 manual Connection, Standard connections, Standard connection diagram

Page 11
Protective function FLB activation output
Low-speed
signal output RC 24Vdc input PLC
FLA
FLC
Meter
FM
+
RY
R/L1
S/L2
T/L3
*1

E6581160

2. Connection

2.1 Standard connections

2

2.1.1 Standard connection diagram 1

This diagram shows a standard wiring of the main circuit.

Standard connection diagram - SINK (Negative) (common:CC)

DC reactor (DCL) *2 (option)

Braking resistor (option)

P0 PA/+ PB PC/-

Main circuit power supply

MCCB

240V class: three-phase 200-240V

 

 

-50/60Hz

500V class: three-phase 380-500V -50/60Hz

600V class: three-phase 525-600V

 

 

-50/60Hz

 

 

MCCB(2P)

Power supply

R/L1

1

200~240V

 

-50/60Hz

S/L2

 

 

 

 

 

 

U/T1

Motor

 

 

 

 

 

Noise

Power circuit

 

 

V/T2

I M

filter *5

 

 

W/T3

 

 

 

 

 

Control

 

F

 

Forward

 

circuit

 

R

 

Reverse

 

 

 

 

 

VF-S11

RES

 

Reset

 

 

 

 

 

 

Operation panel S1

 

Preset-speed 1

 

Connector for

 

S2

 

Preset-speed 2

 

common serial

S3

 

Preset-speed 3

 

communications

 

 

*1: The T/L3 terminal is not provided for single-phase models.

Use the R/L1 and S/L2 terminal as input terminals.

*2: The inverter is supplied with the PO

SW1

FM

VIA

CC

Common

SOURCE

V

V

 

 

PLC

P24

 

Speed reach

OUT

Ry

signal output

 

 

and the PA/+ terminals shorted by means of a shorting bar.

Before installing the DC reactor (DCL), remove the bar.

*3: When using the OUT output terminal in sink logic mode, short the NO and CC terminals.

*4: If you are using a 600V model, be sure to connect an input reactor (ACL).

*5: 600V models have no noise filter inside.

Frequency meter (ammeter)

-

7.5V-1mA (or 4-20mA)

SINK

I

I NO

*3

 

 

 

CC

CC VIA

VIB

PP

 

 

 

 

 

 

+

Voltage signal: 0-10V

 

 

 

-

 

 

 

(Current signal: 4-20mA)

 

 

 

 

External potentiometer (1~10kΩ)

(or input voltage signal across VIB-CC terminals: 0-10V)

10

Image 11
Contents Industrial Inverter For 3-phase induction motorsExplanation of markings Safety precautionsMeanings of symbols Safety precautionsGeneral Operation Wiring Transportation & installationOperations Maintenance and inspection When retry function is selected inverter Contents  Check product purchase Read firstCD-ROM E6581167 Installation Contents of the productVF-S11 Standard connection diagramConnection Standard connectionsPLC OUT FLCFLB FLADescription of terminals Power circuit terminalsSelection of wiring materials Power circuitControl circuit terminals VIA Control circuit terminalsSW1 24VDC PLCFLB FLA PTCRY RC Slide switch SW1PLC Source Positive logic SW1 Source PLC Sink Hoqf OperationsSimplified Operation of the VF-S11 Eoqf How to start and stopStart and stop using the operation panel keys EOQF= Coast stopExample of operating a run from the panel How to set the frequencyHOQF= Frequency setting Setting the frequency using the operation panel HOQF= or Running and stopping using the operation panel How to operate the VF-S11Ex.2 Ex.3 Running and stopping using external signalsVIA Basic VF-S11 operations Status monitor mode Mode for monitoring all inverter statusPanel jog mode Past trip record detained monitor mode Flow of status monitor modeStandard monitor mode Same parameter. Parameter name CWJ. See How to set parametersParameters for detailed and special setting. See When you adjust the inverter repeatedly using⇔HJ How to set the basic parameters ~H How to set extended parameters How to search and reprogram parameters Search and resetting of changed parameters I4WExample of parameter setting  ⇔ CEE  ⇔CEE How to use the history functionParameters that cannot be changed while running Kpkv Returning all parameters to standard default settingHow to save/load the user setting parameters Status monitor under normal conditions Status monitor modeMonitoring the operation status Iiii  Pgtt ⇔Display of detailed information on a past trip Example of call-up of trip information Display of trip informationTrip code display Display of trip information at the occurrence of a tripQR ⇔ OFF VIA VIB RESCumulative E6581160 About the EMC directive How to cope with the CE directiveMeasures to satisfy the standards Measures to satisfy the EMC directive Three-phase 500V class About the low-voltage directive Example of wiringCompliance with Connection Compliance with InstallationCompliance with UL Standard and CSA Standard Measures to satisfy the low-voltage directiveAWG AIC, Fuse and Wire sizesMotor thermal protection AIC aFour navigation functions Table of parameters and dataUser parameters Basic parametersCEE  QNOInput/output parameters Extended parametersFrequency parameters   Operation mode parameters   Torque boost parameters Protection parameters Acceleration/deceleration time parameters  Operation panel parameters Output parametersCommunication parameters PM motor parameters XD/H        Default settings by inverter ratingAD2 Table of input terminal functions, H, H, H +SS3+AD2AD3 Table of output terminal functionsQN-,QNT ,QJ,WR,GH,WE,On QE-,QR-,QJ, Fcvibn Standard specifications SpecificationsModels and their standard specifications Characteristics Common specificationSpecification Outside dimensions and mass Outside dimensions and massVF-S11 Outline drawingFig.D Trip causes/warnings and remedies Before making a service call Trip information and remediesQNT   Industrial and Power Systems & Services Company