Toshiba VF-S11 manual Qnt

Page 78

 

 

 

 

 

 

E6581160

 

 

 

 

(Continued)

 

 

 

 

 

 

 

Error code

Failure code

Problem

Possible causes

 

Remedies

 

 

 

QR

000A

Overvoltage during

The imput voltage fluctuates abnormally.

Insert a suitable input reactor.

 

 

 

 

 

acceleration

(1) The power supply has a capacity of

 

 

 

 

 

 

 

 

200kVA or more.

 

 

 

 

 

 

 

 

(2) A power factor improvement capacitor is

 

 

 

 

 

 

 

 

opened or closed.

 

 

 

 

 

 

 

 

(3) A system using a thyrister is connected

 

 

 

 

 

 

 

 

to the same power distribution line.

 

Use H (auto-restart) and H

 

 

 

 

 

 

A restart signal is input to the rotating

 

 

 

 

 

 

motor after a momentary stop, etc.

 

(ride-through control).

 

 

 

QR

000B

Overvoltage during

The deceleration time FGE is too short.

Increase the deceleration time FGE.

 

 

 

 

 

deceleration

(Regenerative energy is too large.)

Install a dynamic braking resistor.

 

 

 

 

 

 

H (dynamic braking resistor) is off.

Enable H (dynamic braking

 

 

 

 

 

 

H (overvoltage limit operation) is

 

resistor).

 

 

 

 

 

 

off.

Enable H (overvoltage limit

 

 

 

 

 

 

The input voltage fluctuates abnormally.

 

operation).

 

 

 

 

 

 

(1) The power supply has a capacity of

Insert a suitable input reactor.

 

 

 

 

 

 

200kVA or more.

 

 

 

 

 

 

 

 

(2) A power factor improvement capacitor is

 

 

 

 

 

 

 

 

opened and closed.

 

 

 

 

 

 

 

 

(3) A system using a thyrister is connected

 

 

 

 

 

 

 

 

to the same power distribution line.

 

 

 

 

 

QR

000C

Overvoltage during

The input voltage fluctuates abnormally.

Insert a suitable input reactor.

 

 

 

 

 

constant-speed

(1) The power supply has a capacity of

 

 

 

 

 

 

 

operation

200kVA or more.

 

 

 

 

 

 

 

 

(2) A power factor improvement capacitor is

 

 

 

 

 

 

 

 

opened or closed.

 

 

 

 

 

 

 

 

(3) A system using a thyrister is connected

 

 

 

 

 

 

 

 

to the same power distribution line.

 

 

 

 

 

 

 

 

The motor is in a regenerative state

Install a dynamic braking resistor.

 

 

 

 

 

 

because the load causes the motor to run

 

 

 

 

 

 

 

 

at a frequency higher than the inverter

 

 

 

 

 

 

 

 

output frequency.

 

 

 

 

 

QN

000D

Inverter overload

The acceleration time ACC is too short.

Increase the acceleration time CEE.

 

 

 

 

 

 

The DC braking amout is too large.

Reduce the DC braking amount H

 

9

 

 

 

 

The V/F setting is improper.

 

and the DC braking time H.

 

 

 

 

 

A restart signal is input to the rotating

Check the V/F parameter setting.

 

 

 

 

 

motor after a momentary stop, etc.

Use H (auto-restart) and H

 

 

 

 

 

 

The load is too large.

 

(ride-through control).

 

 

 

 

 

 

 

Use an inverter with a larger rating.

 

 

 

QN

000E

Motor overload

The V/F setting is improper.

Check the V/F parameter setting.

 

 

 

 

 

 

The motor is locked up.

Check the load (operated machine).

 

 

 

 

 

 

Low-speed operation is performed

Adjust QNO to the overload that the

 

 

 

 

 

 

continuously.

 

motor can withstand during operation in a

 

 

 

 

 

 

An excessive load is applied to the motor

 

low speed range.

 

 

 

 

 

 

during operation.

 

 

 

 

 

QNT

000F

Dynamic braking

The deceleration time is too short.

Increase the deceleration time FGE.

 

 

 

 

 

resistor

Dynamic braking is too large.

Increase the capacity of dynamic braking

 

 

 

 

 

overload trip

 

 

resistor (wattage) and adjust PBR

 

 

 

 

 

 

 

 

capacity parameter H.

 

 

 

*

0020

Over-torque trip

Over-torque reaches to a detection level

Enable H (over-torque trip

 

 

 

QV

 

 

during operation.

 

selection).

 

 

 

 

 

 

Check system error.

 

 

 

 

 

 

 

 

 

 

QJ

0010

Overheat

The cooling fan does not rotate.

Restart the operation by resetting the

 

 

 

 

 

 

The ambient temperature is too high.

 

inverter after it has cooled down enough.

 

 

 

 

 

 

The vent is blocked up.

The fan requires replacement if it does

 

 

 

 

 

 

A heat generating device is installed close

 

not rotate during operation.

 

 

 

 

 

 

to the inverter.

Secure sufficient space around the

 

 

 

 

 

 

The thermistor in the unit is broken.

 

inverter.

 

 

 

 

 

 

 

Do not place any heat generating device

 

 

 

 

 

 

 

 

near the inverter.

 

 

 

 

 

 

 

Make a service call.

 

 

*You can select a trip ON/OFF by parameters. (Continued overleaf)

77

Image 78
Contents For 3-phase induction motors Industrial InverterSafety precautions Safety precautionsMeanings of symbols Explanation of markingsGeneral Operation Transportation & installation WiringOperations When retry function is selected inverter Maintenance and inspection Contents  Read first Check product purchaseCD-ROM E6581167 Contents of the product InstallationStandard connections Standard connection diagramConnection VF-S11FLA FLCFLB PLC OUTPower circuit Power circuit terminalsSelection of wiring materials Description of terminalsControl circuit terminals 24VDC PLC Control circuit terminalsSW1 VIAPTC FLB FLARY RC Slide switch SW1PLC Source Positive logic SW1 Source PLC Sink Eoqf OperationsSimplified Operation of the VF-S11 HoqfCoast stop How to start and stopStart and stop using the operation panel keys EOQF= How to set the frequency HOQF=Example of operating a run from the panel Setting the frequency using the operation panel HOQF= or  Frequency settingHow to operate the VF-S11 Running and stopping using the operation panelEx.2 Running and stopping using external signals Ex.3VIA Status monitor mode Mode for monitoring all inverter status Panel jog modeBasic VF-S11 operations Flow of status monitor mode Standard monitor modePast trip record detained monitor mode When you adjust the inverter repeatedly using How to set parametersParameters for detailed and special setting. See Same parameter. Parameter name CWJ. SeeHow to set the basic parameters ⇔HJ How to set extended parameters ~H Search and resetting of changed parameters I4W Example of parameter settingHow to search and reprogram parameters   ⇔ CEE How to use the history function Parameters that cannot be changed while running⇔CEE Returning all parameters to standard default setting How to save/load the user setting parametersKpkv Status monitor mode Monitoring the operation statusStatus monitor under normal conditions Iiii Pgtt ⇔ Display of detailed information on a past trip Display of trip information at the occurrence of a trip Display of trip informationTrip code display Example of call-up of trip informationOFF VIA VIB RES QR ⇔Cumulative E6581160 How to cope with the CE directive Measures to satisfy the standardsAbout the EMC directive Measures to satisfy the EMC directive Three-phase 500V class Example of wiring About the low-voltage directiveMeasures to satisfy the low-voltage directive Compliance with InstallationCompliance with UL Standard and CSA Standard Compliance with ConnectionAIC a AIC, Fuse and Wire sizesMotor thermal protection AWGBasic parameters Table of parameters and dataUser parameters Four navigation functionsCEE QNO Extended parameters Input/output parametersFrequency parameters   Operation mode parameters   Torque boost parameters Acceleration/deceleration time parameters Protection parameters  Output parameters Operation panel parametersCommunication parameters PM motor parameters Default settings by inverter rating XD/H       Table of input terminal functions AD2+SS3+AD2 , H, H, HTable of output terminal functions AD3,QJ,WR,GH,WE, On QE-,QR-,QJ,QN-,QNT Fcvibn Specifications Models and their standard specificationsStandard specifications Common specification CharacteristicsSpecification Outside dimensions and mass Outside dimensions and massOutline drawing VF-S11Fig.D Before making a service call Trip information and remedies Trip causes/warnings and remediesQNT   Industrial and Power Systems & Services Company