Toshiba VF-S11 manual Measures to satisfy the EMC directive

Page 46

 

 

 

 

E6581160

 

 

Table 1 EMC standards

 

 

 

 

 

 

 

Category

Subcategory

Product

Test standard and level

 

standards

 

 

 

 

 

Emission

Radiation noise

 

EN55011 Class A Group 1

 

Transmission noise

 

EN55011 Class A Group 1

 

 

 

 

 

Static discharge

 

IEC61000-4-2

 

 

Radioactive radio-frequency

 

IEC61000-4-3

 

 

magnetic contactor field

IEC 61800-3

 

 

Immunity

First transient burst

IEC61000-4-4

 

 

 

Lightning surge

 

IEC61000-4-5

 

 

 

 

 

Radio-frequency

 

IEC61000-4-6

 

 

induction/transmission interference

 

 

 

 

Voltage dip/Interruption of power

 

IEC61000-4-11

Emission standards other than the above are applied to inverters when used in a commercial environment but not an industrial environment.

Category

Subcategory

Product

Test standard and level

standards

 

 

 

Emission

Radiation noise

IEC 61800-3

EN55011 Class B Group 1

Transmission noise

EN55011 Class B Group 1

 

 

 

 

 

6.1.2Measures to satisfy the EMC directive

6

This subsection explains what measures must be taken to satisfy the EMC directive.

(1)Insert a recommended EMI filter (Table 2) on the input side of the inverter to reduce and transmission noise and radiation noise from input cables.

In the combinations listed in Table 2, Inverters are tested in these combination to see if they comply with transmission noise standards. For inverters used in Japan, it is recommended to use the NF series of noise filters.

Table 2 lists noise filters recommended for the inverters.

 

Table 2

Combinations of inverter and EMI filter

Three-phase 240V class

 

 

 

 

Combination of inverter and filter

Inverter

 

Transmission noise

 

Transmission noise

 

EN55011 Class A Group 1

EN55011 Class B Group 1

 

 

Applicable filters

 

Applicable filters

 

(Length of motor connecting cable:

(Length of motor connecting cable:

 

 

Max. 5 m)

 

Max. 1 m)

VFS11-2002PM

 

 

EMFS11

-2007AZ

VFS11-2004PM

 

 

EMFS11-2007AZ

VFS11-2005PM

 

 

EMFS11-2007AZ

VFS11-2007PM

 

 

EMFS11-2007AZ

VFS11-2015PM

 

 

EMFS11-4015BZ

VFS11-2022PM

 

 

EMFS11-4015BZ

VFS11-2037PM

 

 

EMFS11-4025CZ

VFS11-2055PM

 

 

EMFS11-4047DZ

VFS11-2075PM

 

 

EMFS11-4047DZ

VFS11-2110PM

 

 

EMFS11-2083EZ

VFS11-2150PM

 

 

EMFS11-2083EZ

45

Image 46
Contents For 3-phase induction motors Industrial InverterSafety precautions Safety precautionsMeanings of symbols Explanation of markingsGeneral Operation Transportation & installation WiringOperations When retry function is selected inverter Maintenance and inspection Contents  Read first Check product purchaseCD-ROM E6581167 Contents of the product InstallationStandard connections Standard connection diagramConnection VF-S11FLA FLCFLB PLC OUTPower circuit Power circuit terminalsSelection of wiring materials Description of terminalsControl circuit terminals 24VDC PLC Control circuit terminalsSW1 VIAPTC FLB FLARY RC Slide switch SW1PLC Source Positive logic SW1 Source PLC Sink Eoqf OperationsSimplified Operation of the VF-S11 HoqfCoast stop How to start and stopStart and stop using the operation panel keys EOQF= HOQF= How to set the frequencyExample of operating a run from the panel Setting the frequency using the operation panel HOQF= or  Frequency settingHow to operate the VF-S11 Running and stopping using the operation panelEx.2 Running and stopping using external signals Ex.3VIA Panel jog mode Status monitor mode Mode for monitoring all inverter statusBasic VF-S11 operations Standard monitor mode Flow of status monitor modePast trip record detained monitor mode When you adjust the inverter repeatedly using How to set parametersParameters for detailed and special setting. See Same parameter. Parameter name CWJ. See How to set the basic parameters⇔HJ  How to set extended parameters~H Example of parameter setting Search and resetting of changed parameters I4WHow to search and reprogram parameters   ⇔ CEE Parameters that cannot be changed while running How to use the history function⇔CEE How to save/load the user setting parameters Returning all parameters to standard default settingKpkv Monitoring the operation status Status monitor modeStatus monitor under normal conditions Iiii Pgtt ⇔ Display of detailed information on a past trip Display of trip information at the occurrence of a trip Display of trip informationTrip code display Example of call-up of trip informationOFF VIA VIB RES QR ⇔Cumulative E6581160 Measures to satisfy the standards How to cope with the CE directiveAbout the EMC directive Measures to satisfy the EMC directive Three-phase 500V class Example of wiring About the low-voltage directiveMeasures to satisfy the low-voltage directive Compliance with InstallationCompliance with UL Standard and CSA Standard Compliance with ConnectionAIC a AIC, Fuse and Wire sizesMotor thermal protection AWGBasic parameters Table of parameters and dataUser parameters Four navigation functionsCEE QNO Extended parameters Input/output parametersFrequency parameters   Operation mode parameters   Torque boost parameters Acceleration/deceleration time parameters Protection parameters  Output parameters Operation panel parametersCommunication parameters PM motor parameters Default settings by inverter rating XD/H       Table of input terminal functions AD2+SS3+AD2 , H, H, HTable of output terminal functions AD3On QE-,QR-,QJ, ,QJ,WR,GH,WE,QN-,QNT Fcvibn Models and their standard specifications SpecificationsStandard specifications Common specification CharacteristicsSpecification Outside dimensions and mass Outside dimensions and massOutline drawing VF-S11Fig.D Before making a service call Trip information and remedies Trip causes/warnings and remediesQNT   Industrial and Power Systems & Services Company