9.Before making a service call
- Trip information and remedies
9.1Trip causes/warnings and remedies
When a problem arises, diagnose it in accordance with the following table.
If it is found that replacement of parts is required or the problem cannot be solved by any remedy described in the table, contact your Toshiba dealer.
[Trip information]
|
| Error code | Failure code | Problem | Possible causes | Remedies | |
|
| QE | 0001 | Overcurrent during | • The acceleration time CEE is too short. | • Increase the acceleration time CEE. | |
|
| QER | 0025 | acceleration | • The V/F setting is improper. | • Check the V/F parameter. | |
|
|
|
| Overcurrent flowing | • A restart signal is imput to the rotating | • Use H | |
|
|
|
| in element during | motor after a momentary stop, etc. | ||
|
|
|
| acceleration | • A special motor (e.g. motor with a small | • Adjust the carrier frequency H. | |
|
|
|
|
| impedance) is used. | • Set the carrier frequency control mode | |
|
|
|
|
|
| selection parameter f316 to 1 or 3 | |
|
|
|
|
|
| (carrier frequency decreased | |
|
|
|
|
|
| automatically). | |
|
| QE | 0002 | Overcurrent during | • The deceleration time FGE is too short. | • Increase the deceleration time FGE. | |
|
| QER | 0026 | deceleration |
| • Set the carrier frequency control mode | |
|
|
|
| Overcurrent flowing |
| selection parameter f316 to 1 or 3 | |
|
|
|
| in element during |
| (carrier frequency decreased | |
|
|
|
| decelearion |
| automatically). | |
|
| QE | 0003 | Overcurrent during | • The load fluctuates abruptly. | • Reduce the load fluctuation. | |
9 | |||||||
| QER | 0027 | constant speed | • The load is in an abnormal condition. | • Check the load (operated machine). | ||
|
|
| operation |
| • Set the carrier frequency control mode | ||
|
|
| Overcurrent flowing |
| selection parameter f316 to 1 or 3 | ||
|
|
|
| in element during |
| (carrier frequency decreased | |
|
|
|
| operation |
| automatically). | |
|
| ER | 0025 | Ground fault trip | • A current leaked from an output cable or | • Check cables, connectors, and so on for | |
|
| ER | 0026 | Arm overcurrent at | the motor to ground. | ground faults. | |
|
| 0027 | • A main circuit elements is defective. | • Make a service call. | |||
|
| ER |
| (for 11 and 15 kW |
|
| |
|
|
|
| models only) |
|
| |
|
| QEN | 0004 | Overcurrent (An | • The insulation of the output main circuit or | • Check the cables and wires for defective | |
|
|
|
| overcurrent on the | motor is defective. | insulation. | |
|
|
|
| load side at | • The motor has too small impedance. | • When using a 11 or 15 kW model, check | |
|
|
|
|
| • A 11 or 15 kW model was started, | cables, connectors, and so on for ground | |
|
|
|
|
| although a current is leaked from an | faults. | |
|
|
|
|
| output cable or the motor to ground. |
| |
|
| QEC | 0005 | Arm overcurrent at | • A main circuit elements is defective. | • Make a service call. | |
|
|
|
|
|
| ||
|
| * | 0008 | Input phase failure | • A phase failure occured in the input line of | • Check the main circuit input line for phase | |
|
| GRJ |
|
| the main circuit. | failure. | |
|
|
|
| • The capacitor in the main circuit lacks | • Enable H (input phase failure | ||
|
|
|
|
| |||
|
|
|
|
| capacitance. | detection). | |
|
|
|
|
|
| • Check the capacitor in the main circuit for | |
|
|
|
|
|
| exhaustion. | |
|
| * | 0009 | Output phase failure | • A phase failure occurred in the output line | • Check the main circuit output line, motor, | |
|
| GRJQ |
|
| of the main circuit. | etc. for phase failure. | |
|
|
|
|
| • Enable H (Output phase failure | ||
|
|
|
|
|
| ||
|
|
|
|
|
| detection). |
*You can select a trip ON/OFF by parameters. (Continued overleaf)