Toshiba VF-S11 manual +SS3+AD2, , H, H, H

Page 67

E6581160

QTable of input terminal functions 2

 

 

Function

Code

Function

Action

 

 

No.

 

 

 

 

 

 

 

34

F+SS3+AD2

Combination of forward run, preset-speed

ON: Simultaneous input from F, SS3 and AD2

 

 

 

 

command 3 and acceleration/deceleration 2

 

 

 

35

R+SS3+AD2

Combination of reverse run, preset-speed

ON: Simultaneous input from R, SS3 and AD2

 

 

 

 

command 3 and acceleration/deceleration 2

 

 

 

36

F+SS4+AD2

Combination of forward run, preset-speed

ON: Simultaneous input from F, SS4 and AD2

 

 

 

 

command 4 and acceleration/deceleration 2

 

 

 

37

R+SS4+AD2

Combination of reverse run, preset-speed

ON: Simultaneous input from R, SS4 and AD2

 

 

 

 

command 4 and acceleration/deceleration 2

 

 

 

38

FCHG

Frequency command forced switching

ON: H(If H = )

 

 

 

 

 

OFF: HOQF

 

 

39

VF2

No.2 Switching of V/F setting

ON: No.2 V/F setting

 

 

 

 

 

(RV=0, H, H, H, H)

 

 

 

 

 

OFF: No.1 V/F setting

 

 

 

 

 

(Set value of RV, XN, XNX, XD, VJT)

 

 

40

MOT2

No.2 motor switching

ON: No.2 motor

 

 

 

 

VF2AD2OCS2

(RV=0, H, H, H, H,

 

 

 

 

 

H, H, H, H)

 

 

 

 

 

OFF: No.1 motor (Set value of RV, XN, XNX,

 

 

 

 

 

XD, VJT, CEE, FGE, H, H)

 

 

41

UP

Frequency UP signal input from external contacts

ON: Increase in frequency

 

 

42

DOWN

Frequency DOWN signal input from external

ON: Reduction in frequency

 

 

 

 

contacts

 

 

 

43

CLR

Frequency UP/DOWN cancellation signal input

OFFON: Resetting of UP/DOWN frequency by

 

 

 

 

from external contacts

means of external contacts

 

 

44

CLR+RES

Combination of frequency UP/DOWN cancellation

ON: Simultaneous input from CLR and RES

7

 

 

 

and reset by means of external contacts

 

 

45

EXTN

Inversion of trip stop command from external

OFF: G Trip stop

 

 

 

device

 

 

 

46

OH

Thermal trip stop signal input from external device

ON: QJ Trip stop

 

 

47

OHN

Inversion of thermal trip stop command from

OFF: QJ Trip stop

 

 

 

 

external device

 

 

 

48

SC/LC

Forced switching from remote to local control

Enabled when remote control is exercised

 

 

 

 

 

ON: Local control (setting of cmod, HOQF and

 

 

 

 

 

H)

 

 

 

 

 

OFF: Remote control

 

 

49

HD

Operation holding (stop of 3-wire operation)

ON: F (forward run)/R: (reverse run) held, 3-wire

 

 

 

 

 

operation

 

 

 

 

 

OFF: Slowdown stop

 

 

50

CMTP

Forced switching of command mode and terminal

ON: Terminal board operation

 

 

 

 

board command

OFF: Setting of EOQF

 

 

51

CKWH

Display cancellation of the cumulative power

ON: Monitor display cancellation of the cumulative

 

 

 

 

amount (kWh)

power amount (kWh)

 

 

52

FORCE

Forced operation (factory configuration required)

ON: Forced operation mode in which operation is

 

 

 

 

 

not stopped in the event of the occurrence of

 

 

 

 

 

a soft fault (preset speed operation frequency

 

 

 

 

 

15) To use this function, the inverter needs to

 

 

 

 

 

be so configured at the factory.

 

 

 

 

 

OFF: Normal operation

 

 

53

FIRE

Fire-speed control

ON: Fire-speed operation (preset speed operation

 

 

 

 

 

frequency 15)

 

 

 

 

 

OFF: Normal operation

Note. When function 1, 10-12, 15-17, 38, 41-45 or 48 is assigned to an input terminal board, the input terminal board is enabled even if the parameter command mode selection cmod is set at 1 (panel).

66

Image 67
Contents Industrial Inverter For 3-phase induction motorsExplanation of markings Safety precautionsMeanings of symbols Safety precautionsGeneral Operation Wiring Transportation & installationOperations Maintenance and inspection When retry function is selected inverter Contents  Check product purchase Read firstCD-ROM E6581167 Installation Contents of the productVF-S11 Standard connection diagramConnection Standard connectionsPLC OUT FLCFLB FLADescription of terminals Power circuit terminalsSelection of wiring materials Power circuitControl circuit terminals VIA Control circuit terminalsSW1 24VDC PLCFLB FLA PTCRY RC Slide switch SW1PLC Source Positive logic SW1 Source PLC Sink Hoqf OperationsSimplified Operation of the VF-S11 Eoqf How to start and stopStart and stop using the operation panel keys EOQF= Coast stopHOQF= How to set the frequencyExample of operating a run from the panel Frequency setting Setting the frequency using the operation panel HOQF= or Running and stopping using the operation panel How to operate the VF-S11Ex.2 Ex.3 Running and stopping using external signalsVIA Panel jog mode Status monitor mode Mode for monitoring all inverter statusBasic VF-S11 operations Standard monitor mode Flow of status monitor modePast trip record detained monitor mode Same parameter. Parameter name CWJ. See How to set parametersParameters for detailed and special setting. See When you adjust the inverter repeatedly using How to set the basic parameters⇔HJ  How to set extended parameters~H Example of parameter setting Search and resetting of changed parameters I4WHow to search and reprogram parameters   ⇔ CEE Parameters that cannot be changed while running How to use the history function⇔CEE How to save/load the user setting parameters Returning all parameters to standard default settingKpkv Monitoring the operation status Status monitor modeStatus monitor under normal conditions Iiii  Pgtt ⇔Display of detailed information on a past trip Example of call-up of trip information Display of trip informationTrip code display Display of trip information at the occurrence of a tripQR ⇔ OFF VIA VIB RESCumulative E6581160 Measures to satisfy the standards How to cope with the CE directiveAbout the EMC directive Measures to satisfy the EMC directive Three-phase 500V class About the low-voltage directive Example of wiringCompliance with Connection Compliance with InstallationCompliance with UL Standard and CSA Standard Measures to satisfy the low-voltage directiveAWG AIC, Fuse and Wire sizesMotor thermal protection AIC aFour navigation functions Table of parameters and dataUser parameters Basic parametersCEE  QNOInput/output parameters Extended parametersFrequency parameters   Operation mode parameters   Torque boost parameters Protection parameters Acceleration/deceleration time parameters  Operation panel parameters Output parametersCommunication parameters PM motor parameters XD/H        Default settings by inverter ratingAD2 Table of input terminal functions, H, H, H +SS3+AD2AD3 Table of output terminal functionsOn QE-,QR-,QJ, ,QJ,WR,GH,WE,QN-,QNT Fcvibn Models and their standard specifications SpecificationsStandard specifications Characteristics Common specificationSpecification Outside dimensions and mass Outside dimensions and massVF-S11 Outline drawingFig.D Trip causes/warnings and remedies Before making a service call Trip information and remediesQNT   Industrial and Power Systems & Services Company