Toshiba VF-S11 manual Fcvibn

Page 70

E6581160

QTable of output terminal functions 3

Function

Code

Function

Action

 

 

No.

 

 

 

 

 

 

 

35

FCVIBN

Inversion of frequency VIB selection

Inversion of FCVIB

 

 

36

FLR

Fault signal (put out also at the time of a retry)

ON: When inverter trips or retries

 

 

 

 

 

OFF: When inverter does not trip or retry

 

 

37

FLRN

Inversion of failure signal (put out also at the time

Inversion of FLR

 

 

 

 

of a retry)

 

 

 

38

OUT0

Specified data output 1

ON: Specified data from remote control FA50:

 

 

 

 

 

BIT0= 1

 

 

 

 

 

OFF: Specified data from remote control FA50:

 

 

 

 

 

BIT0= 0

 

 

39

OUT0N

Inversion of specified data output 1

Inversion of OUT0 setting

 

 

40

OUT1

Specified data output 2

ON: Specified data from remote control FA50:

 

 

 

 

 

BIT1= 1

 

 

 

 

 

OFF: Specified data from remote control FA50:

 

 

 

 

 

BIT1= 0

 

 

41

OUT1N

Inversion of specified data output 2

Inversion of OUT1 setting

 

 

42

COT

Cumulative operation time alarm

ON: Cumulative operation time is equal to or

 

 

 

 

 

longer than H

 

 

 

 

 

OFF: Cumulative operation time is shorter than

 

 

 

 

 

H

 

 

43

COTN

Inversion of cumulative operation time alarm

Inversion of COT

 

 

44

LTA

Parts replacement alarm

ON: Calculation for parts replacement time is

 

 

 

 

 

equal to or longer than the preset time

 

 

 

 

 

ON: Calculation for parts replancement time is

 

 

 

 

 

shorter than the preset time

 

 

45

LTAN

Inversion of replacement alarm

Inversion of LTA

 

 

7

46

BR

Braking sequence output

ON: Braking retention signal

 

 

 

 

OFF: Braking release signal

 

47

BRN

Inversion of braking sequence output

Inversion of BR

 

 

 

 

 

 

 

48

LI1

F terminal input signal

ON: The signal input to F terminal is ON

 

 

 

 

OFF: The signal input to F terminal is OFF

 

 

49

LI1N

Inversion of F terminal input signal

Inversion of LI1

 

 

50

LI2

R terminal input signal

ON: The signal input to R terminal is ON

 

 

 

 

 

OFF: The signal input to R terminal is OFF

 

 

51

LI2N

Inversion of R terminal input signal

Inversion of LI2

 

 

52

PIDF

Signal in accordance of frequency command

ON: Frequency commanded by HOQF or

 

 

 

 

 

H and that by VIA show the same

 

 

 

 

 

value.

 

 

 

 

 

OFF: Frequency commanded by HOQF or

 

 

 

 

 

H and that by VIA show different

 

 

 

 

 

values.

 

 

53

PIDFN

Inversion of signal in accordance of frequency

Inversion of PIDF setting

 

 

 

 

command

 

 

 

54

MOFF

Undervoltage detection

ON: Undervoltage detected

 

 

 

 

 

OFF: Other than undervoltage

 

 

55

MOFFN

Inversion of undervoltage detection

Inversion of MOFF

 

 

56-253

Disabled

Invalid settings, always OFF (ignored)

Invalid settings, always OFF (ignored)

 

 

254

AOFF

Always OFF

Always OFF

 

 

255

AON

Always ON

Always ON

 

 

69

Image 70
Contents For 3-phase induction motors Industrial InverterSafety precautions Safety precautionsMeanings of symbols Explanation of markingsGeneral Operation Transportation & installation WiringOperations When retry function is selected inverter Maintenance and inspection Contents  Read first Check product purchaseCD-ROM E6581167 Contents of the product InstallationStandard connections Standard connection diagramConnection VF-S11FLA FLCFLB PLC OUTPower circuit Power circuit terminalsSelection of wiring materials Description of terminalsControl circuit terminals 24VDC PLC Control circuit terminalsSW1 VIAPTC FLB FLARY RC Slide switch SW1PLC Source Positive logic SW1 Source PLC Sink Eoqf OperationsSimplified Operation of the VF-S11 HoqfCoast stop How to start and stopStart and stop using the operation panel keys EOQF= HOQF= How to set the frequencyExample of operating a run from the panel Setting the frequency using the operation panel HOQF= or  Frequency settingHow to operate the VF-S11 Running and stopping using the operation panelEx.2 Running and stopping using external signals Ex.3VIA Panel jog mode Status monitor mode Mode for monitoring all inverter statusBasic VF-S11 operations Standard monitor mode Flow of status monitor modePast trip record detained monitor mode When you adjust the inverter repeatedly using How to set parametersParameters for detailed and special setting. See Same parameter. Parameter name CWJ. See How to set the basic parameters⇔HJ  How to set extended parameters~H Example of parameter setting Search and resetting of changed parameters I4WHow to search and reprogram parameters   ⇔ CEE Parameters that cannot be changed while running How to use the history function⇔CEE How to save/load the user setting parameters Returning all parameters to standard default settingKpkv Monitoring the operation status Status monitor modeStatus monitor under normal conditions Iiii Pgtt ⇔ Display of detailed information on a past trip Display of trip information at the occurrence of a trip Display of trip informationTrip code display Example of call-up of trip informationOFF VIA VIB RES QR ⇔Cumulative E6581160 Measures to satisfy the standards How to cope with the CE directiveAbout the EMC directive Measures to satisfy the EMC directive Three-phase 500V class Example of wiring About the low-voltage directiveMeasures to satisfy the low-voltage directive Compliance with InstallationCompliance with UL Standard and CSA Standard Compliance with ConnectionAIC a AIC, Fuse and Wire sizesMotor thermal protection AWGBasic parameters Table of parameters and dataUser parameters Four navigation functionsCEE QNO Extended parameters Input/output parametersFrequency parameters   Operation mode parameters   Torque boost parameters Acceleration/deceleration time parameters Protection parameters  Output parameters Operation panel parametersCommunication parameters PM motor parameters Default settings by inverter rating XD/H       Table of input terminal functions AD2+SS3+AD2 , H, H, HTable of output terminal functions AD3On QE-,QR-,QJ, ,QJ,WR,GH,WE,QN-,QNT Fcvibn Models and their standard specifications SpecificationsStandard specifications Common specification CharacteristicsSpecification Outside dimensions and mass Outside dimensions and massOutline drawing VF-S11Fig.D Before making a service call Trip information and remedies Trip causes/warnings and remediesQNT   Industrial and Power Systems & Services Company