| E6581160 |
|
|
|
| (Continued) |
|
|
|
|
|
|
| Error code | Failure code | Problem |
| Possible causes | Remedies |
|
|
| QJ | 002E | External thermal trip | • An external thermal trip is input. | • Check the external thermal input. | |
|
|
| G | 0011 | Emergency stop | • During automatic operation or remote | • Reset the inverter. | |
|
|
|
|
|
|
| operation, a stop command is entered |
|
|
|
|
|
|
|
| from the operation panel or a remote |
|
|
|
|
|
|
|
| input device. |
|
|
|
| GGR | 0012 | EEPROM fault 1 | • A data writing error occurs. | • Turn off the inverter, then turn it again. If it | |
|
|
|
|
|
|
|
| does not recover from the error, make a |
|
|
|
|
|
|
|
| service call. |
|
|
| GGR | 0013 | EEPROM fault 2 | • Power supply is cut off during V[R | • Turn the power off temporarily and turn it | |
|
|
|
|
|
|
| operation and data writing is aborted. | back on, and then try V[R operation |
|
|
|
|
|
|
|
| again. |
|
|
| GGR | 0014 | EEPROM fault 3 | • A data reading error occurred. | • Turn off the inverter, then turn it again. If it | |
|
|
|
|
|
|
|
| does not recover from the error, make a |
|
|
|
|
|
|
|
| service call. |
|
|
| GTT | 0015 | Main unit RAM fault | • | The control RAM is defective. | • Make a service call. |
|
|
| GTT | 0016 | Main unit ROM fault | • | The control ROM is defective. | • Make a service call. |
|
|
| GTT | 0017 | CPU fault 1 | • | The control CPU is defective. | • Make a service call. |
|
|
| GTT | 0018 | Remote control error | • An error arises during remote operation. | • Check the remote control device, cables, | |
|
|
|
|
|
|
|
| etc. |
|
|
| GTT | 001A | Current detector fault | • The current detector is defective. | • Make a service call. | |
|
|
| GTT | 001B | Optional circuit board | • An optional circuit board in a different | • Check again to be sure that the circuit | |
|
|
|
|
| format error |
| format is installed. | board is connected correctly, and then |
|
|
|
|
|
|
|
| reset the power supply. |
|
|
|
|
|
|
|
| • Replace the circuit board with a correctly |
|
|
|
|
|
|
|
| formatted one. |
|
|
| * | 001D | • The output current decreased to a low- | • Enable H | ||
|
|
| WE |
| operation |
| current detection level during operation. | • Check the suitable detection level for the |
|
|
|
| Trip |
|
| system (H, H). | |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| • Make a service call if the setting is |
|
|
|
|
|
|
|
| correct. |
|
|
| * | 001E | Undervoltage trip | • The input voltage (in the main circuit) is | • Check the input voltage. | |
9 |
|
| WR |
| (main circuit) |
| too low. | • Enable H (undervoltage trip |
|
|
|
|
|
| selection). | ||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| • To cope with a momentary stop due to | |
|
|
|
|
|
|
|
| undervoltage, enable H (ride- |
|
|
|
|
|
|
|
| through control) and H (auto- |
|
|
|
|
|
|
|
| restart). |
|
|
| GH | 0022 | Ground fault trip | • A ground fault occurs in the output cable | • Check the cable and the motor for ground | |
|
|
|
|
|
|
| or the motor. | faults. |
|
|
| GVP | 0054 | • Check the motor parameter H to H. | |||
|
|
|
|
|
| • The motor with the capacity of 2 classes or less than the inverter is used. | ||
|
|
|
|
|
| • The output cable is too thin. |
| |
|
|
|
|
|
| • The motor is rotating. |
| |
|
|
|
|
|
| • The inverter is used for loads other than those of | ||
|
|
| GV[R | 0029 | Inverter | • | Circuit board is changed. | • Make a service call. |
|
|
|
|
| type error |
| (Or main circuit/drive circuit board) |
|
|
|
| * | 0032 | Brea in analog signal | • The signal input via VIA is below the | • Check the cables for breaks. And check | |
|
|
| G |
| cable |
| analog sinal detectio level set with | the setting of input signal or setting value |
|
|
|
|
|
| H. | of H. | |
|
|
|
|
|
|
| ||
|
|
| G | 0033 | CPU | • A communications error occurs between | • Make a service call. | |
|
|
|
|
| communications |
| control CPUs. |
|
|
|
|
|
| error |
|
|
|
|
|
| G | 0034 | Excessive torque | • The torque boost parameter H is | • Decrease the setting of the torque boost | |
|
|
|
|
| boosted |
| set too high. | parameter H. |
|
|
|
|
|
| • The motor has too small impedance. |
| |
|
|
| G | 0035 | CPU fault 2 | • | The control CPU is defective. | • Make a service call. |
|
|
| UQWV | 002F | • The motor shaft is locked. | • Unlock the motor shaft. | ||
|
|
|
|
| (For PM motor only) | • One output phase is open. | • Check the interconnect cables between | |
|
|
|
|
|
| • An impact load is applied. | the inverter and the motor. |
*You can select a trip ON/OFF by parameters.
78