Toshiba VF-S11 manual 

Page 79

 

 

 

 

 

 

 

 

E6581160

 

 

 

 

(Continued)

 

 

 

 

 

 

 

Error code

Failure code

Problem

 

Possible causes

Remedies

 

 

 

QJ

002E

External thermal trip

An external thermal trip is input.

Check the external thermal input.

 

 

 

G

0011

Emergency stop

During automatic operation or remote

Reset the inverter.

 

 

 

 

 

 

 

operation, a stop command is entered

 

 

 

 

 

 

 

 

from the operation panel or a remote

 

 

 

 

 

 

 

 

input device.

 

 

 

 

GGR

0012

EEPROM fault 1

A data writing error occurs.

Turn off the inverter, then turn it again. If it

 

 

 

 

 

 

 

 

does not recover from the error, make a

 

 

 

 

 

 

 

 

service call.

 

 

 

GGR

0013

EEPROM fault 2

Power supply is cut off during V[R

Turn the power off temporarily and turn it

 

 

 

 

 

 

 

operation and data writing is aborted.

back on, and then try V[R operation

 

 

 

 

 

 

 

 

again.

 

 

 

GGR

0014

EEPROM fault 3

A data reading error occurred.

Turn off the inverter, then turn it again. If it

 

 

 

 

 

 

 

 

does not recover from the error, make a

 

 

 

 

 

 

 

 

service call.

 

 

 

GTT

0015

Main unit RAM fault

The control RAM is defective.

Make a service call.

 

 

 

GTT

0016

Main unit ROM fault

The control ROM is defective.

Make a service call.

 

 

 

GTT

0017

CPU fault 1

The control CPU is defective.

Make a service call.

 

 

 

GTT

0018

Remote control error

An error arises during remote operation.

Check the remote control device, cables,

 

 

 

 

 

 

 

 

etc.

 

 

 

GTT

001A

Current detector fault

The current detector is defective.

Make a service call.

 

 

 

GTT

001B

Optional circuit board

An optional circuit board in a different

Check again to be sure that the circuit

 

 

 

 

 

format error

 

format is installed.

board is connected correctly, and then

 

 

 

 

 

 

 

 

reset the power supply.

 

 

 

 

 

 

 

 

Replace the circuit board with a correctly

 

 

 

 

 

 

 

 

formatted one.

 

 

 

*

001D

Low-current

The output current decreased to a low-

Enable H (low-current detection).

 

 

 

WE

 

operation

 

current detection level during operation.

Check the suitable detection level for the

 

 

 

 

Trip

 

 

system (H, H).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Make a service call if the setting is

 

 

 

 

 

 

 

 

correct.

 

 

 

*

001E

Undervoltage trip

The input voltage (in the main circuit) is

Check the input voltage.

9

 

 

WR

 

(main circuit)

 

too low.

Enable H (undervoltage trip

 

 

 

 

 

 

selection).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To cope with a momentary stop due to

 

 

 

 

 

 

 

 

undervoltage, enable H (ride-

 

 

 

 

 

 

 

 

through control) and H (auto-

 

 

 

 

 

 

 

 

restart).

 

 

 

GH

0022

Ground fault trip

A ground fault occurs in the output cable

Check the cable and the motor for ground

 

 

 

 

 

 

 

or the motor.

faults.

 

 

 

GVP

0054

Auto-tuning error

Check the motor parameter H to H.

 

 

 

 

 

 

The motor with the capacity of 2 classes or less than the inverter is used.

 

 

 

 

 

 

The output cable is too thin.

 

 

 

 

 

 

 

The motor is rotating.

 

 

 

 

 

 

 

The inverter is used for loads other than those of three-phase induction motors.

 

 

 

GV[R

0029

Inverter

Circuit board is changed.

Make a service call.

 

 

 

 

 

type error

 

(Or main circuit/drive circuit board)

 

 

 

 

*

0032

Brea in analog signal

The signal input via VIA is below the

Check the cables for breaks. And check

 

 

 

G

 

cable

 

analog sinal detectio level set with

the setting of input signal or setting value

 

 

 

 

 

 

H.

of H.

 

 

 

 

 

 

 

 

 

 

G

0033

CPU

A communications error occurs between

Make a service call.

 

 

 

 

 

communications

 

control CPUs.

 

 

 

 

 

 

error

 

 

 

 

 

 

G

0034

Excessive torque

The torque boost parameter H is

Decrease the setting of the torque boost

 

 

 

 

 

boosted

 

set too high.

parameter H.

 

 

 

 

 

 

The motor has too small impedance.

 

 

 

 

G

0035

CPU fault 2

The control CPU is defective.

Make a service call.

 

 

 

UQWV

002F

Step-out

The motor shaft is locked.

Unlock the motor shaft.

 

 

 

 

 

(For PM motor only)

One output phase is open.

Check the interconnect cables between

 

 

 

 

 

 

An impact load is applied.

the inverter and the motor.

*You can select a trip ON/OFF by parameters.

78

Image 79
Contents Industrial Inverter For 3-phase induction motorsExplanation of markings Safety precautionsMeanings of symbols Safety precautionsGeneral Operation Wiring Transportation & installationOperations Maintenance and inspection When retry function is selected inverter Contents  Check product purchase Read firstCD-ROM E6581167 Installation Contents of the productVF-S11 Standard connection diagramConnection Standard connectionsPLC OUT FLCFLB FLADescription of terminals Power circuit terminalsSelection of wiring materials Power circuitControl circuit terminals VIA Control circuit terminalsSW1 24VDC PLCFLB FLA PTCRY RC Slide switch SW1PLC Source Positive logic SW1 Source PLC Sink Hoqf OperationsSimplified Operation of the VF-S11 Eoqf How to start and stopStart and stop using the operation panel keys EOQF= Coast stopHOQF= How to set the frequencyExample of operating a run from the panel Frequency setting Setting the frequency using the operation panel HOQF= or Running and stopping using the operation panel How to operate the VF-S11Ex.2 Ex.3 Running and stopping using external signalsVIA Panel jog mode Status monitor mode Mode for monitoring all inverter statusBasic VF-S11 operations Standard monitor mode Flow of status monitor modePast trip record detained monitor mode Same parameter. Parameter name CWJ. See How to set parametersParameters for detailed and special setting. See When you adjust the inverter repeatedly using How to set the basic parameters⇔HJ  How to set extended parameters~H Example of parameter setting Search and resetting of changed parameters I4WHow to search and reprogram parameters   ⇔ CEE Parameters that cannot be changed while running How to use the history function⇔CEE How to save/load the user setting parameters Returning all parameters to standard default settingKpkv Monitoring the operation status Status monitor modeStatus monitor under normal conditions Iiii  Pgtt ⇔Display of detailed information on a past trip Example of call-up of trip information Display of trip informationTrip code display Display of trip information at the occurrence of a tripQR ⇔ OFF VIA VIB RESCumulative E6581160 Measures to satisfy the standards How to cope with the CE directiveAbout the EMC directive Measures to satisfy the EMC directive Three-phase 500V class About the low-voltage directive Example of wiringCompliance with Connection Compliance with InstallationCompliance with UL Standard and CSA Standard Measures to satisfy the low-voltage directiveAWG AIC, Fuse and Wire sizesMotor thermal protection AIC aFour navigation functions Table of parameters and dataUser parameters Basic parametersCEE  QNOInput/output parameters Extended parametersFrequency parameters   Operation mode parameters   Torque boost parameters Protection parameters Acceleration/deceleration time parameters  Operation panel parameters Output parametersCommunication parameters PM motor parameters XD/H        Default settings by inverter ratingAD2 Table of input terminal functions, H, H, H +SS3+AD2AD3 Table of output terminal functionsOn QE-,QR-,QJ, ,QJ,WR,GH,WE,QN-,QNT Fcvibn Models and their standard specifications SpecificationsStandard specifications Characteristics Common specificationSpecification Outside dimensions and mass Outside dimensions and massVF-S11 Outline drawingFig.D Trip causes/warnings and remedies Before making a service call Trip information and remediesQNT   Industrial and Power Systems & Services Company