2.3.2 Thermocouple Input
The figure below shows the wiring hookup for any thermocouple type.
For example, for Type K hookup, connect the yellow wire to the "2" terminal and
the red wire to the "1(-)" terminal.
When configuring your controller, select Thermocouple and Thermocouple Type
in the Input Type menu (see Part 3).
Figure 2.4 Thermocouple Wiring Hookup
If the input wires of the meter get disconnected or broken, it will display
+OPN “Input (+) Open” message. For safety purpose you may want to
set up your alarm to be triggered when input is open. See Alarm 1 and 2
chapters for details.
8
TYPE Input Connector Jacket (external insulation)
Terminal 1 (-) Terminal 2 (+) Extension Grade
JRed White dark-Brown Black
KRed Yellow dark-Brown Yellow
TRed Blue dark-Brown Blue
ERed Purple dark-Brown Purple
NRed Orange dark-Brown Brown
RRed Black - Green
SRed Black - Green
BRed Gray - Black
Table 2.4 TC Wire Color Chart