EXCITATION

24 Vdc @ 25 mA Not available for:

Low Power Option (-DC) or

Serial Communication Option (-C24)

INSULATION

Power to Input/Output 2300 Vac per 1 min. test

1500 Vac per 1 min. test (Low Voltage/Power Option)

Power to Relays/SSR Outputs

2300 Vac per 1 min. test

Relays/SSR to Relay/SSR Outputs

2300 Vac per 1 min. test

RS-232/485 to Inputs/Outputs 500 Vac per 1 min. test

Approvals

FM, UL, C-UL, and

see CE Approval Section

GENERAL

Line Voltage/Power

90-240 Vac +/-10%, 50-400 Hz* 110-375 Vdc, equivalent voltage 5 W, power consumption

*No CE compliance above 60 Hz

Low Voltage/Power Option

20-36 Vdc, 4 W**, power consumption External power source must meet Safety Agency Approvals.

**Units can be powered safely with 24 Vac but, no Certification for CE/UL are claimed.

External Fuse Required Time-Delay, UL 248-14 listed:

100 mA/250 V

400 mA/250 V (Low Voltage/Power Option) Time-Lag, IEC 127-3 recognized:

100 mA/250 V

400 mA/250 V (Low Voltage/Power Option)

Environmental Conditions 0 to 55°C (32 to 131°F),

90% RH non-condensing

0 to 50°C (32 to 122°F) for UL only.

90% RH non-condensing

Dimensions iDRA

92.5H x 125.2D x 32.1 mm W

(3.64 x 4.93 x 1.27")

204g (0.45lb)

Optional Remote Programmer iDRP: 48H x 96x 39 mm D

(1.89 x 3.78 x 1.55")

159g (0.35lb)

1/8 DIN Panel Cutout

Optional Remote Programmer iDRP: 45 H x 92 mm W

(1.772" x 3.622 ")

56

Page 60
Image 60
a/d/s/ iSeries manual Excitation, Insulation, General