28
ALARM ENABLE/DISABLE AT POWER ON:
Press d15) Display flashes previous selection. Press bto ENBL enable
or DSBL disable.
Press d16) Display shows STRD stored message. momentarily and
then advances to ALR.L only, if it was changed, otherwise press
ato advance to the ALR.LAlarm 1 Low Value Submenu.
If the alarm is enabled at Power On, the alarm will be active right after
reset. If the alarm is disabled at Power On, the alarm will become
enabled when the process value enters the non alarm area. The alarm is
not active while the process value is approaching Setpoint 1.
ALARM 1 LOW VALUE SUBMENU:
Press d17) Display flashes 1st digit of previous value. Use band cto
enter new value.
Press b& c18) Use band cto enter Alarm 1 Low Value.
Press d19) Display shows STRD storage message momentarily and
then advances to ALR.H only, if it was changed, otherwise press
ato advance to ALR.HAlarm 1 Hi Value Submenu.
ALARM 1 HI VALUE SUBMENU:
Press d20) Display flashes 1st digit of previous value. Use band cto
enter new value.
Press b& c21) Use band cto enter Alarm1 Hi Value.
Press d22) Display shows STRD stored message momentarily and then
advances to the next menu only, if it was changed, otherwise
press ato advance to the next menu.