ALARM ENABLE/DISABLE AT POWER ON:
Press d 15) Display flashes previous selection. Press b to ENBL enable or DSBL disable.
Press d 16) Display shows STRD stored message. momentarily and
then advances to ALR.L only, if it was changed, otherwise press a to advance to the ALR.L Alarm 1 Low Value Submenu.
If the alarm is enabled at Power On, the alarm will be active right after reset. If the alarm is disabled at Power On, the alarm will become enabled when the process value enters the non alarm area. The alarm is not active while the process value is approaching Setpoint 1.
ALARM 1 LOW VALUE SUBMENU:
Press d 17) Display flashes 1st digit of previous value. Use b and c to enter new value.
Press b & c 18) Use b and c to enter Alarm 1 Low Value.
Press d 19) Display shows STRD storage message momentarily and then advances to ALR.H only, if it was changed, otherwise press a to advance to ALR.H Alarm 1 Hi Value Submenu.
ALARM 1 HI VALUE SUBMENU:
Press d 20) Display flashes 1st digit of previous value. Use b and c to enter new value.
Press b & c 21) Use b and c to enter Alarm1 Hi Value.
Press d 22) Display shows STRD stored message momentarily and then advances to the next menu only, if it was changed, otherwise press a to advance to the next menu.
28