3.2.10 Analog Output (Retransmission)
This unit is equipped with three physical outputs that can only be configured as follows:
a)Alarm 1, Alarm 2 & Analog Out
b)Output 1, Alarm 2 & Analog Out
Analog Output is available only if the Analog Output option board is factory installed.
It is required that you put the controller in the Standby Mode for any configuration change other than Set Points & Alarms.
Figure 3.9 Flow Chart for Analog Output (Retransmission)
ENTER ANALOG OUTPUT MENU:
Press a 1) Press a, if necessary, until CNFG prompt appears. Press d 2) Display advances to INPT Input Menu.
Press a 3) Press a, if necessary, until Display advances to ANLG Analog Output Menu.
Press d 4) Display advances to Analog Output CURR or VoLT Current/Voltage Submenu and flashes the previous selection.
CURRENT/VOLTAGE SUBMENU:
Press d 5) Display flashes CURR Current or VoLT Voltage.
Press b 6) Scroll through the available selection: Current or Voltage. (Example VoLT).
Press d 7) Display shows STRD stored message momentarily and then advances to RD1 Submenu only if it was changed, otherwise press a to advance to RD1 Reading 1 Submenu.
39