21
Input Type (Process)
ENTER INPUT TYPE MENU:
Press a1) Press a, if necessary, until CNFGprompt appears.
Press d2) Display advance to INPT Input Menu.
Press d3) Display flashes T.ç, RTD or PROC (Thermocouple, RTD or
Process). If the displayed input type is PROC, press ato skip to
step 6 (PROC stops flashing).
PROCESS SUBMENU:
Press b4) Scroll through the available selection to PROC (flashing).
Press d5) Display shows STRD stored message momentarily and then
PROC (not flashing).
Press d6) Display flashes previous Process type selection. i.e. 0-10
(see below for Process types selection).
Press b7) Scroll through the available Process types to the selection of
your choice.
Press d8) Display shows STRD stored message and then advances to
RDG Reading Configuration Menu.
Process Types: 100 mV 1 V 10 V 0 – 20 mA
Display: 0-0.1 0-1.0 0-10 0-20
For 4-20 mAInput select 0-20 mA and adjust the Input/Reading accordingly.
To adjust 4-20 mAinput, see example under Input/Reading Submenu.
3.2.5 Reading Configuration MenuFigure 3.4 Flow Chart for Reading Configuration Menu
It is required that you put the controller in the Standby Mode for any
configuration change other than Set Points & Alarms.