MAXIMUM/PERCENT HIGH SUBMENU:

Specify in percent, the maximum value (99) for control output. If the output is time proportional (Relay, SSR, or Pulse), then the maximum duty-cycle, in percent, is specified.

Press d 12) Display flashes 1st digit of previous “Percent High” setting. Press b & c 13) Use b and c buttons to enter a new value for “Percent High”. Press d 14) Display shows STRD stored message momentarily and then

advances to CTRL Control Type Submenu.

Example: On an Analog Output of 0~10 Vdc, a setting of %LO = 10 and %HI = 90, cause the minimum on the control output to be 1 V and the maximum on the control output to be 9 V. The same setting on a time proportional output, will cause 10% duty cycle for the minimum control output and 90% duty cycle for maximum control output. To disable %LO/HI, set LO to 00 and HI to 99. If %LO/HI is at other values than the default (%LO = 00, %HI = 99), SOAK is disabled.

*CONTROL TYPE OUTPUT: (Relay, SSR, or Pulse)

Press d 15) Display flashes ON.OF On/Off or PID Proportional, Integral, Derivative.

Press b 16) Scroll through the available selections: “ON/OFF” or “PID”. Press d 17) Display flashes STRD stored message momentarily and

then advances to AçTN only, if it was changed, otherwise press a to advance to AçTN Action Type Submenu.

The ON/OFF control is a coarse way of controlling the process. The “Dead Band” improves the cycling associated with the On/Off control. The PID control is best for processes where the set point is continuously changing and/or a tight control of the process variable is required. PID control requires tuning and adjustment of the "Proportional", "Integral or Reset" and "Derivative or Rate" terms by a trial-and-error method. The instrument provides an "Auto Tuning" feature making the tuning process automatic, possibly optimum.

ACTION TYPE SUBMENU:

The error that results from the measurement of the Process Variable may be positive or negative since it may be greater or smaller than the Setpoint. If a positive error should cause the instrument output to increase (i.e. cooling), it would be called Direct Acting. If a negative error should cause the output to increase (i.e. heating), it would be called Reverse Acting.

Press

d

18)

Display flashes DRçT Direct or RVRS Reverse.

Press

b

19)

Scroll through the available selections: “Direct” or “Reverse”.

Press d

20)

Display shows STRD stored message momentarily and then

advances to AUTo only, if it was changed, otherwise press a to advance to AUTo Auto PID Submenu (if PID Control Type was selected).

34

Page 38
Image 38
a/d/s/ iSeries manual MAXIMUM/PERCENT High Submenu, Control Type Output Relay, SSR, or Pulse, Action Type Submenu