3.2.11 Ramp & Soak

Alarm must be DISABLED if Ramp is ENABLED.

It is required that you put the controller in the Standby Mode for any configuration change other than Set Points & Alarms.

Figure 3.10 Flow Chart for Ramp and Soak

ENTER RAMP AND SOAK MENU:

Press a 1) Press a, if necessary, until CNFG prompt appears. Press d 2) Display advances to INPT Input Menu.

Press a 3) Press a, if necessary, until Display advances to RAMP Ramp and SOAK Soak Menu.

RAMP ENABLE/DISABLE SUBMENU:

Press d 4) Display advances to “Ramp Enable/Disable” Submenu and flashes ENBL or DSBL.

Press b 5) Scroll through the available selections: “Enable” or “Disable”. Press d 6) Display shows STRD stored message momentarily and then advances to SOAK Soak Enable/Disable Menu.

If RAMP Disable was selected, display skips to the next menu item (ID Code).

SOAK ENABLE/DISABLE SUBMENU:

Press d 7) Display flashes ENBL or DSBL.

Press b 8) Scroll through the available selections: “Enable” or “Disable”. Press d 9) Display shows STRD stored message momentarily and then

advances to “Ramp Value” Submenu.

41