3.2.11 Ramp & Soak
Alarm must be DISABLED if Ramp is ENABLED.
It is required that you put the controller in the Standby Mode for any configuration change other than Set Points & Alarms.
Figure 3.10 Flow Chart for Ramp and Soak
ENTER RAMP AND SOAK MENU:
Press a 1) Press a, if necessary, until CNFG prompt appears. Press d 2) Display advances to INPT Input Menu.
Press a 3) Press a, if necessary, until Display advances to RAMP Ramp and SOAK Soak Menu.
RAMP ENABLE/DISABLE SUBMENU:
Press d 4) Display advances to “Ramp Enable/Disable” Submenu and flashes ENBL or DSBL.
Press b 5) Scroll through the available selections: “Enable” or “Disable”. Press d 6) Display shows STRD stored message momentarily and then advances to SOAK Soak Enable/Disable Menu.
If RAMP Disable was selected, display skips to the next menu item (ID Code).
SOAK ENABLE/DISABLE SUBMENU:
Press d 7) Display flashes ENBL or DSBL.
Press b 8) Scroll through the available selections: “Enable” or “Disable”. Press d 9) Display shows STRD stored message momentarily and then
advances to “Ramp Value” Submenu.
41