ENTER READING CONFIGURATION MENU:

Press a 1) Press a, if necessary, until CNFG prompt appears. Press d 2) Display advances to INPT Input Menu.

Press a 3) Display advances to RDG Reading Configuration Menu. Press d 4) Display advances to DEC Decimal Point.

DECIMAL POINT SUBMENU:

Press d 5) Display flashes previous selection for Decimal location.

Press b 6) Scroll though the available selections and choose Decimal location: FFFF or FFF.F (also FF.FF and F.FFF — if PROC

Process type was selected in the Input Type Menu).

Press d 7) Display shows STRD stored message momentarily and then advances to TEMP Temperature Unit.

Decimal Point for Process Input Type is passive.

TEMPERATURE UNIT SUBMENU:

Press d 8) Display flashes previous Temperature Unit selection.

Press b 9) Scroll though the available selections to the Temperature Unit of your choice: °F or °C.

Press d 10) Display shows STRD stored message momentarily and then advances to FLTR Filter Constant.

FILTER CONSTANT SUBMENU:

Press d 11) Display flashes previous selection for Filter Constant.

Press b 12) Scroll though the available selections: 0001, 0002, 0004, 0008, 0016, 0032, 0064, 0128. - Default is 0004

Press d 13) Display shows STRD stored message momentarily only, if a change was made, otherwise press a to advance to the next menu.

If Process was selected in the Input Type Menu the display will advance to IN.RD Input/Reading Submenu, otherwise the display advances to the ALR1 Alarm 1 Menu.

The Filter Constant Submenu allows the user to specify the number of readings stored in the Digital Averaging Filter.

For PID control select filter value 0001-0004. A filter value of 2 is approximately equal to 1 second RC low pass time constant.

22

Page 26
Image 26
a/d/s/ iSeries Enter Reading Configuration Menu, Decimal Point Submenu, Temperature Unit Submenu, Filter Constant Submenu