ENTER READING CONFIGURATION MENU:
Press a 1) Press a, if necessary, until CNFG prompt appears. Press d 2) Display advances to INPT Input Menu.
Press a 3) Display advances to RDG Reading Configuration Menu. Press d 4) Display advances to DEC Decimal Point.
DECIMAL POINT SUBMENU:
Press d 5) Display flashes previous selection for Decimal location.
Press b 6) Scroll though the available selections and choose Decimal location: FFFF or FFF.F (also FF.FF and F.FFF — if PROC
Process type was selected in the Input Type Menu).
Press d 7) Display shows STRD stored message momentarily and then advances to TEMP Temperature Unit.
Decimal Point for Process Input Type is passive.
TEMPERATURE UNIT SUBMENU:
Press d 8) Display flashes previous Temperature Unit selection.
Press b 9) Scroll though the available selections to the Temperature Unit of your choice: °F or °C.
Press d 10) Display shows STRD stored message momentarily and then advances to FLTR Filter Constant.
FILTER CONSTANT SUBMENU:
Press d 11) Display flashes previous selection for Filter Constant.
Press b 12) Scroll though the available selections: 0001, 0002, 0004, 0008, 0016, 0032, 0064, 0128. - Default is 0004
Press d 13) Display shows STRD stored message momentarily only, if a change was made, otherwise press a to advance to the next menu.
If Process was selected in the Input Type Menu the display will advance to IN.RD Input/Reading Submenu, otherwise the display advances to the ALR1 Alarm 1 Menu.
The Filter Constant Submenu allows the user to specify the number of readings stored in the Digital Averaging Filter.
For PID control select filter value