22
ENTER READING CONFIGURATION MENU:
Press a1) Press a, if necessary, until CNFGprompt appears.
Press d2) Display advances to INPT Input Menu.
Press a3) Display advances to RDG Reading Configuration Menu.
Press d4) Display advances to DEC Decimal Point.
DECIMAL POINT SUBMENU:
Press d5) Display flashes previous selection for Decimal location.
Press b6) Scroll though the available selections and choose Decimal
location: FFFF or FFF.F (also FF.FF and F.FFF — if PROC
Process type was selected in the Input Type Menu).
Press d7) Display shows STRD stored message momentarily and then
advances to TEMP Temperature Unit.
Decimal Point for Process Input Type is passive.
TEMPERATURE UNIT SUBMENU:
Press d8) Display flashes previous Temperature Unit selection.
Press b9) Scroll though the available selections to the Temperature Unit
of your choice: °F or °C.
Press d10) Display shows STRD stored message momentarily and then
advances to FLTR Filter Constant.
FILTER CONSTANT SUBMENU:
Press d11) Display flashes previous selection for Filter Constant.
Press b12) Scroll though the available selections: 0001,0002,0004,
0008,0016,0032,0064,0128. - Default is 0004
Press d13) Display shows STRD stored message momentarily only, if a
change was made, otherwise press ato advance to the next menu.
If Process was selected in the Input Type Menu the display will
advance to IN.RD Input/Reading Submenu, otherwise the
display advances to the ALR1Alarm 1 Menu.
The Filter Constant Submenu allows the user to specify the
number of readings stored in the Digital Averaging Filter.
For PID control select filter value 0001-0004. Afilter value of 2 is
approximately equal to 1 second RC low pass time constant.