PART 5 FACTORY PRESET VALUES

Table 5.1 Factory preset value

MENU ITEMS

FACTORY PRESET VALUES

NOTES

Set Point 1 (SP1)

000.0

 

Set Point 2 (SP2)

000.0

 

Input:

 

 

Input Type (INPT)

TC, type K

 

Reading Configuration (RDG):

 

 

Decimal Point (DEC.P)

FFF.F

 

Temperature unit (TEMP)

°F

 

Filter value (FLTR)

0004

 

Alarm 1 & 2:

 

 

Alarm 1 (ALR1)

Disable (DSBL)

 

Alarm 2 (ALR2)

Enable (ENBL)

 

Absolute/Deviation (ABSO/DEV)

Absolute (ABSO)

 

Latch/Unlatch (LTCH/UNLT)

Unlatch (UNLT)

 

Contact Closure (CT.CL)

Normally Open (N.O.)

 

Active (ACTV)

Above (ABOV)

 

Alarm At Power On (A.P.ON)

Disable (DSBL)

Alarm 1 only

Alarm Low (ALR.L)

-100.0

 

Alarm High (ALR.H)

400.0

 

LOOP:

 

 

Loop Break Time (LOOP)

Disable (DSBL)

 

Loop Value (B.TIM)

00:59

 

Reading Adjust Value (R.ADJ)

000.0

 

Setpoint Deviation (SP.dV)

Disable (DSBL)

 

OUTPUT 1:

 

 

Self (SELF)

Disabled (DSBL)

 

% Low Value (%LO)

0000

 

% High Value (%HI)

0099

 

Control Type (CTRL)

On/Off

 

Action Type (ACTN)

Reverse (RVRS)

 

Dead Band (DEAD)

020.0

 

PID Auto (AUTO)

Disable (DSBL)

 

Anti Integral (ANTI)

Disable (DSBL)

 

Proportion Value (PROP)

020.0

 

Reset Value (REST)

0180

 

Rate Value (RATE)

0000

 

Cycle Value (CYCL)

0007

 

Damping Factor (DPNG)

0003

 

ANALOG OUTPUT (Retransmission)

 

 

Analog Output (ANLG)

Enabled (ENBL)

 

Current/Voltage (CURR/VOLT)

Voltage (VOLT)

 

Scale and Offset

Reading: 0 - 999.9 cts, Output: 0 - 10 V

 

 

 

58

Page 62
Image 62
a/d/s/ iSeries manual Part 5 Factory Preset Values, Factory preset value