Chapter 2. Installation

mentary equipment grounding conductor shall be in compli- ance with the rules for terminating bonding jumpers at Part K or Article 250 of the National Electrical Code, ANSI/NFPA 70. Termination of the supplementary equipment grounding con- ductor is permitted to be made to building steel, to a metal electrical raceway system, or to any grounded item that is per- manently and reliably connected to the electrical service equip- ment ground.

Bare, covered, or insulated grounding conductors are accept- able. A covered or insulated grounding conductor shall have a continuous outer finish that is either green, or green with one or more yellow stripes.

The supplemental grounding conductor shall be connected to the equipment using a number 8 ring terminal. The terminal should be fastened to the grounding lug provided on the rear panel of the equipment. The ring terminal should be installed using the appropriate crimping tool (AMP P/N 59250 T-EAD Crimping Tool or equivalent).

61202129L1-1