Press

Press

OV

30

Program the OVP to 30 volts, which is less than the output voltage.

0.000

 

OVP voltage entered is less than the output voltage. This causes the

 

 

 

OVP circuit to trip. The output drops to zero, CV turns off, and Prot

 

 

turns on.

 

 

 

Press

Press

Press

OV - - - - -

0.000

Shows that the power supply shuts down because the OVP circuit has tripped.

Return display to meter mode (optional step).

Program the OVP to 45 volts, which is greater than the output voltage. Note: You cannot clear an OVP trip until you have first removed the cause of the condition.

Press Prot Clear

()*

40.00

The OVP circuit is cleared, restoring the output. Prot turns off and

 

CV turns on.

 

 

*

is the unlabeled blue key.

 

 

Checking the Current Function

The tests in Table 3-2 check the basic current functions with a short connected across the power supply output. Do not program maximum output currents unless the shorting wire is capable of handling the current (see "Supplemental Characteristics" and Table 4-2). The AMPS display will show various readings. Ignore the VOLTS display.

Table 3-2. Checking the Current Functions (Output Terminals Shorted)

Procedure

Display

Explanation

Turn off the power supply and connect a #14 AWG or larger wire across the output (+) and (–) terminals. If you intend to test at full-rated output current, use a wire or wires of sufficient size to carry the maximum current of the unit (see "Supplemental Characteristics" in Chapter l and Table 4-2 in Chapter 4).

Turn on the unit.

Press

Press

Press

Press several times

Press the same number of times

Meter mode

VOLT 80.00

CURR 1.000

1.000

Essentially zero output with Dis annunciator on.

Program output to 80 volts.

Program output to 1 ampere.

Dis annunciator turns off, CC annunciator turns on, and AMPS display shows the programmed current.

*Current decreases several milliamperes each time you press the key.

*Current increases several milliamperes each time you press the key.

Rotate the Current control counterclockwise and then clockwise

Press

*The number of milliamperes is determined by the current programming resolution of the power supply (see "Supplemental Characteristics" in Chapter 1).

Control operates similarly to the and keys. The control is rate sensitive. Turning it more quickly causes a more rapid change in current.

You have enabled the overcurrent protection circuit. The circuit then tripped because of the output short. The CC annunciator turns off and the OCP and Prot annunciators come on. Output current is near zero.

Turn-On Checkout 23

Page 23
Image 23
Agilent Technologies E4356A manual Checking the Current Function, Press Prot Clear