1 - General Information
Additionally, a single supply of sufficient amperage may be shared among multiple mainframes that are connected to a common power bus - provided that the total current can be supplied while meeting the voltage specification at the power bus terminals at the rear of the Agilent MCCD.
NOTE: If the external dc power source has an overvoltage protection circuit, it must be set higher than 30 volts to avoid the possibility of shutting itself down during the discharge cycle.
Multiple Agilent MCCD Configuration
The following figure illustrates an Agilent E4370A MCCD system with eight fully loaded mainframes.
25.6kW
Power Source
(24 V @
1067A)
Agilent E4370A
MCCD (256 channels)
Agilent E4370A
MCCD (256 channels)
Agilent E4370A
MCCD (256 channels)
Agilent E4370A
MCCD (256 channels)
POWERBUS
Agilent E4371A Powerbus Load
Agilent E4371A Powerbus Load
Agilent E4371A Powerbus Load
Agilent E4371A Powerbus Load
Agilent E4370A
MCCD (256 channels)
Agilent E4370A
MCCD (256 channels)
Agilent E4370A
MCCD (256 channels)
Agilent E4370A
MCCD (256 channels)
Figure 1-6. Maximum System Block Diagram
14