Agilent Technologies E4370A, E4371A In Case of Trouble, Introduction, Table E-1. Fault Indicators

Models: E4374A E4371A E4370A

1 141
Download 141 pages 7.46 Kb
Page 135
Image 135
In Case of Trouble

E

In Case of Trouble

Introduction

The Agilent E4370A MCCD has a built-in self test capability which is performed at power-on. Additionally a more complete self test can be done by executing the cfSelftest; function or running self test from the Agilent MCCD User Interface. This selftest capability provides an effective diagnostic tools to isolate problems for rapid repair. Refer to chapter 5 under Selftest for more information.

CAUTION: Make sure that no cells are connected when running a user-initiated self test to avoid potentially hazardous voltages from appearing across any cells during the testing process.

Fault LEDs (see Figure 1-2)

If any of the Fault LEDs on the front of an Agilent E4370A/E4374A MCCD System are on, it indicates that there is a fault associated either with the mainframe or a charge/discharger card. Before replacing the card or mainframe, follow the procedures outlined in the following table.

Table E-1. Fault Indicators

Agilent E4370A FAULT

External

Indicates an external fault such as

External digital fault signal,

External power fail shutdown signal,

High power bus voltage after power on,

Low power bus voltage after power-on.

Overtemperature.

To clear the light, first remove the condition that caused the fault. Then either cycle power to the unit, send a Protect Clear API programming command, or press Protect Clear on the Agilent MCCD User Interface to clear the fault register.

Internal

Indicates an internal hardware fault such as

Selftest failure.

Calibration error.

Hardware error.

If the Internal LED is lit without any fault LEDs on the Agilent E4374A Charger/Discharger cards being lit, it indicates that the Agilent E4370A MCCD mainframe is defective. Return the unit for service.

If a fault LED is lit on a charger/discharger card, turn the mainframe off and replace the defective card by loosening its thumbscrews and pulling the card out of its slot.

If you replace a defective card and the Internal LED is still lit on the mainframe, the mainframe is probably defective. Return the unit for service.

135

Page 135
Image 135
Agilent Technologies E4370A, E4371A, E4374A manual In Case of Trouble, Introduction, Table E-1. Fault Indicators