Allied Telesis AT-DC2552XS, AT-FAN06 Installing and Replacing AT-PWR06 Power Supply Module

Models: AT-FAN06 AT-DC2552XS AT-PWR06

1 84
Download 84 pages 30.01 Kb
Page 48
Image 48
Installing and Replacing AT-PWR06 Power Supply Module

Chapter 3: Installing the Switch and Modules

Installing and Replacing AT-PWR06 Power Supply Module

Installing Power Supply Module

The AT-PWR06 power supply module may be installed in one of the two power supply slots - PSU1 and PSU2. See Figure 1 on page 19 for the location of these slots.

The AT-DC2552XS L2 Data Center Switch can operate under full load with one power supply module installed. However, if you want power supply redundancy, a second power supply may be installed.

There is no functional difference between the two available power supply slots. Operation of the AT-DC2552XS is the same when installed in either slot. If you want to use only one power supply, Allied Telesis recommends that you install it in the PSU1 slot.

The following procedures are included in this section:

“Installing Power Supply Module” on page 48

“Replacing Power Supply Module” on page 50

“Installing Power Supply Blank Cover” on page 51

Install the AT-PWR06 power supply module by performing the following procedure:

1.Identify the power supply slot where you are installing the AT-PWR06 power supply module.

2.Loosen the captive screw on the blank cover panel of the power supply slot blank cover and remove the cover. See Figure 18.

Figure 18. Loosen Power Supply Captive Screws

3. Store the blank cover in a safe place for future use.

48

Page 48
Image 48
Allied Telesis AT-DC2552XS manual Installing and Replacing AT-PWR06 Power Supply Module, Installing Power Supply Module