UPS CHARACTERISTICS (Symmetra Power Array)
Setting | Description | |
|
| |
Output | Output voltage of the UPS, in volts AC. | |
|
| |
Output Freq | Output frequency range of the UPS, in hertz. | |
Range | ||
| ||
|
| |
Output Voltage | Desired output voltage setting. The default setting, Auto, | |
indicates that output voltage equals the nominal input | ||
Reporting base | ||
voltage. Other settings are 208 VAC and 240 VAC. | ||
| ||
|
| |
| Instructs the UPS to go to bypass mode or to drop the | |
If UPS fails … | load in the event the UPS fails and the frequency or | |
voltage is out of range of their settings (see 1 and 2 on | ||
| ||
| this menu). | |
|
| |
Low Battery | Time interval between | |
shutdown of the UPS. Select from values between 2 and | ||
Duration | ||
10 minutes. | ||
| ||
|
| |
| Time interval between the issuance of a UPS turn off | |
Shutdown Delay | command and actual shutdown of the load. Since the | |
UPS notifies the computer of the impending shutdown, | ||
| ||
| Shutdown Delay allows for graceful turn off. | |
|
| |
| Time interval after which the UPS turns on after | |
Return Delay | restoration of utility power. Use Return Delay to prevent | |
| branch circuit overloads. | |
|
| |
| Battery capacity desired for UPS restart after a power | |
Return Battery | outage. Select from values between 0% and 90%. At | |
0%, the UPS will restart as soon as utility line power | ||
Capacity | ||
returns to normal. With other settings, the UPS will | ||
| ||
| charge the batteries to the specified level prior to restart. | |
|
| |
Scheduled Self | Time intervals between UPS battery | |
Test | ||
| ||
|
| |
| Three alarm thresholds. An alarm will sound if any of | |
Alarm if … | the three alarm settings — calculated runtime, load, and | |
redundancy — is out of range. For a description of these | ||
| ||
| settings, see UPS Status and Diagnostics table, Sec. 4.2. | |
|
| |
Reset UPS to | Returns the UPS to its default state. Type YES (all | |
Default | uppercase) and press ENTER when prompted to confirm | |
Settings | resetting. Any other entry stops resetting. | |
|
|
26