CALL-UPS II SETTINGS (Continued)

Setting

Default

Description

 

 

 

 

 

Number of rings before the Call-UPS II modem

 

 

answers a call. After each communication session, the

 

 

modem SO register is set to this value. If the value is

Answer

 

0 (the default), Call-UPS II will send “ATSO=0,” and

0

the modem will not answer calls. Set this value to 0

Ring

 

to use Call-UPS II for paging only. With Answer

 

 

 

 

Ring set to 0, Call-UPS II will not answer a stray call

 

 

and will always be available for paging. Values from

 

 

0 to 15 are accepted.

 

 

 

 

 

Answer Lockout time interval, for use of multiple

 

 

devices (like modems) on the same telephone line as

 

 

Call-UPS II. When set to a non-zero value, the

 

 

modem is prevented from accepting incoming calls

 

 

during the defined interval after a communication

 

 

session. To use Answer Lockout, make sure the

Answer

0 min

modem attached to Call-UPS II is th e first device in

Lockout

the telephone line chain (see figure at end of Sec.

 

 

 

3.5). When this feature is enabled, the next device

 

 

down the chain will get as many rings as it needs to

 

 

answer a call. Make sure that all other automatic

 

 

answering devices on the line with Call-UPS II are set

 

 

to answer in a greater number of rings than Call-UPS

 

 

II. Values from 0 to 99 minutes are accepted.

 

 

 

 

 

States whether Call-UPS II is connected to a UPS.

UPS

ON

Change the default setting (ON) if Call-UPS II is

Present

connected only to Measure-UPS. This shortens the

 

 

 

menu structure and the polling sequence.

 

 

 

Reset …

 

Resets Call-UPS II to factory defaults.

 

 

 