UPS CONTROL (Continued)

 

 

Command

Description

 

 

 

Causes the UPS to shut down. Call-UPS II immediately

Graceful Turn

signals that the UPS is on battery and that the battery is

nearly exhausted. Graceful Turn OFF uses the value set for

OFF

Low Battery Duration. See UPS Characteristics table in

 

 

Sec. 4.4.

 

 

 

Starts and stops runtime calibration on the UPS.

 

Calibration starts only if the UPS has a 100% battery

 

charge. If the UPS accepts the command to start runtime

Start(Stop)

calibration, Call-UPS II reports “Runtime Calib: OK.” If

Runtime

the UPS does not accept the command, Call-UPS II

Calibration

reports “Runtime Calib: NO.” Runtime is displayed on the

 

UPS Status [and Diagnostics] Screen. Note: Smart-UPS

 

products with serial numbers that begin with the letter W

 

do not support runtime calibration.

 

 

Put UPS in

For Matrix-UPS and Symmetra Power Array only. Puts the

(Return from)

UPS in Bypass mode and returns the UPS from Bypass

Bypass

mode.

 

 

If the UPS is powered off when UPS Control is selected from the Main menu, Call-UPSII responds with an abbreviated control menu:

--------------------- CONTROL MENU ----------------------

1- Turn UPS ON

2- Turn UPS OFF ?- Help

<ENTER> Display menu

<ESC> Return to Previous menu

>

Type 1 to turn the UPS on, then press ESC to return to the Main menu or press ENTER to re-display the full UPS Control menu.

21

Page 25
Image 25
APC AP9208, AP9608 manual UPS Control