21

If the UPS is powered off when UPS Control is selected from the Main
menu, Call-UPS II responds with an abbreviated control menu:

Type 1 to turn the UPS on, then press ESC to return to the Main menu or

press ENTER to re-display the full UPS Control menu.

UPS CONTROL (Continued)Com mand Description

Graceful Turn

OFF

Causes the UPS to shut down. Call-UPS II immediately
signals that the UPS is on battery and that the battery is
nearly exhausted. Graceful Turn OFF uses the value set for
Low Battery Duration. See UPS Characteristics table in
Sec. 4.4.

Start(Stop)

Runtime

Calibration

Starts and stops runtime calibration on the UPS.
Calibration starts only if the UPS has a 100% battery
charge. If the UPS accepts the command to start runtime
calibration, Call-UPS II reports “Runtime Calib: OK.” If
the UPS does not accept the command, Call-UPS II
reports “Runtime Calib: NO.” Runtime is displayed on the
UPS Status [and Diagnostics] Screen. Note : Smart-UPS
products with serial numbers that begin with the letter W
do not support runtime calibration.

Put UPS in

(Return from)

Bypass

For Matrix-UPS and Symmetra Power Array only. Puts the
UPS in Bypass mode and returns the UPS from Bypass
mode.
--------------------- CONTROL MENU ----------------------
1- Turn UPS ON
2- Turn UPS OFF
?- Help
<ENTER> Display menu
<ESC> Return to Previous menu
>