APC AP9208, AP9608 manual Paging Setup, Setting

Models: AP9608 AP9208

1 52
Download 52 pages 47.53 Kb
Page 37
Image 37

-----------------------

PAGING SETUP

------------------------

1-

Paging: ON

 

 

 

2- Dial String 1: DT9,5551212@

 

 

 

3- Dial String 2: DT9,5551212@

 

 

 

4-

Repeat 1:

1

8-

Site ID:

12345678

5-

Repeat 2:

1

9- Space Char:

*

6- Page Interval:

1 min

 

 

10- Dial Speed: Slow

 

7- Message Delay:

15 sec

 

11- End String:

 

 

 

--- EVENT ------ NUM:

 

1

2

CODE -- EVENT--NUM:

1

2

CODE

12- UPS ON-BATTERY

Y

N

0

20- ZONE 1

Y

N

8

13-

ON & LOW BATTER

Y

N

1

21- ZONE 2

Y

N

9

14-

UPS SHUT DOWN

 

Y

N

2

22- ZONE 3

Y

N 10

15- UPS ON-LINE

 

Y

N

3

23- ZONE 4

Y

N 11

16-

REPLACE BATTERY

Y

N

4

24- ZONES CLEARY

N 12

17-

UPS FAULT

 

Y

N

5

25- PROBE 1

Y

N 13

18-

LOST COM W/ UPS

Y

N

6

26- PROBE 2

Y

N 14

19-

BYPASS

 

Y

N

7

27- PROBES CLEARY N 15

-------------------------------------------------------------

?- Help <ENTER> Display menu

<ESC> Return to Previous menu

>

 

 

PAGING SETUP

 

 

 

Setting

Default

Description

 

 

 

Paging

OFF

To enable paging, enter 1 when prompted. Enter 0 to

disable.

 

 

 

 

 

 

 

Dial string for the pager (the first pager if two are

 

 

used). Use standard modem commands such as:

Dial

D T9,

DP — dial in pulse mode; DT — dial in tone mode

String 1

5551212@

W — wait for second dial tone; , (Comma) — pause

 

 

(typically for 2 seconds); @ — wait for a quiet

 

 

answer (5 seconds of silence)

 

 

 

Dail

D T9,

Dial string for a second pager number.

String 2

5551212@

 

 

 

 

 

 

Number of times, from 0–4, that the page for the first

 

 

pager number is repeated. Call-UPS II cycles through

 

 

Repeat 1, Repeat 2, and Page Interval for each report-

Repeat 1

1

able event. Events are buffered and p rioritized during

paging to keep the operator updated with the best

 

 

 

 

information. Note: paging is also controlled on an

 

 

event basis (see later chart). Set Repeat to 0 to dis-

 

 

able a pager without having to disable all the events.

 

 

 

Repeat 2

1

Same as Repeat 1, for pager associated with Dial

String 2.

 

 

 

 

 

33

Page 37
Image 37