With Symmetra Power Array

Call-UPSII connected to a Symmetra Power Array displays the following UPS Characteristics menu:

------------------------------ UPS CHARACTERISTICS ---------------------------

UPS ID: UPS_IDEN 1- Output: 240 V

2- Output Freq Range: 60/.1 Hz

3- Output Voltage Reporting Base: Auto

4- If UPS fails and freq or voltage is out of range: Go to Bypass

-------------------------------------------------------------------------------

5- Low Battery Duration: 02 min.

6- Shutdown Delay: 020 sec.

7- Return Delay: 000 sec.

8- Return battery Capacity: 10 %

9- Scheduled Self Test: every 14 days

-------------------------------------------------------------------------------

10- Alarm if runtime is less than: 015 min.

11- Alarm if load is greater than: 05.0 kVA

12- Alarm if redundancy is less than: n+1 (0=never)

-------------------------------------------------------------------------------

13- Reset UPS to Default Settings <ENTER> Display menu

<ESC> Return to Previous menu

>

To change a setting, type the number of the menu item and press ENTER. The following screen displays when you enter “9.”

NOTE: Changes May Conflict with monitoring Software

Press <SPACE> To See Next Entry, <ENTER> To Accept

UPS Self Test> 14 Days

The following table gives a description of the settings on the UPS Char- acteristics menu for Call-UPSII connected to the Symmetra Power Array.