4.4 UPS Characteristics
UPS characteristics are set at the factory for normal operation and usually do not need to be changed. However if a change is needed, select items from the UPS Characteristics menu. New settings may conflict with the operation of UPS monitoring software in use, so check the requirements of the system before changing them. Default and optional values for these settings vary from one UPS to another.
Note:
To display or change the characteristics of the UPS, type 3 and press ENTER from the Main menu. The appearance of the UPS Characteristics menu will vary according to the type of the connected UPS. Refer to the appropriate sections and accompanying tables that follow.
With Smart-UPS and Matrix-UPS
UPS ID: UPS_IDEN 1- Output: 240 V
2- Output Freq Range: AUTO
3- Output Voltage Reporting base: Auto
4- If UPS fails and freq or voltage is out of range: Go to Bypass
5- Low Battery Duration: 02 min.
6- Shutdown Delay: 020 sec.
7- Return Delay: 000 sec.
8- Return Battery Capacity: 00 %
9- Scheduled Self Test: every 14 Days
10- Alarm if runtime is less than: 000 min.
11- Alarm if load is greater than: 00.0 kVA
12- Alarm if redundancy is less than: n+2 (0=never)
13- | Reset UPS | to | Default Settings |
?- | Help |
|
|
<ENTER> | Display Menu |
| |
<ESC> | Return to | Previous Menu |
>