UPS CHARACTERISTICS (Smart-UPS and Matrix UPS, Cont.)

Setting

Description

 

 

 

Sensitivity of the UPS to power line fluctuation. Set this

 

value according to the type and magnitude of expected

 

fluctuation and the susceptibility of the load. Values range

Sensitivity

from high to low sensitivity. Use lower sensitivity settings

 

when running from a less stable power source, e.g., an

 

inexpensive fuel-powered gen erator, when you have deter-

 

mined that the connected devices can handle the instability.

 

 

 

Time interval between issuance of a UPS turn off command

Shutdown

and actual shutdown of the load. Since the UPS notifies the

Delay

computer of the impending shutdown, Shutdown Delay

 

allows for graceful turn off.

 

 

 

Time interv al after which the UPS turns on after restoration

Return Delay

of utility power. Use return delay to prevent branch circuit

 

overloads.

 

 

UPS Self Test

Time intervals between UPS battery self-tests.

 

 

Audible Alarm

Function of the UPS audible alarm.

 

 

Low Battery

Time interval between low-battery warning and shutdown of

Duration

the UPS. Select from values between 2 and 10 minutes.

 

 

 

Battery capacity desired for UPS restart after a power

Return

outage. Select from values between 0% and 90%. At 0%,

Battery

the UPS will restart as soon as utility line power returns to

Capacity

normal. With other settings, the UPS will charge the

 

batteries to the specified level prior to restart.

 

 

Reset UPS to

Returns the UPS to its default state. Type YES (all

Default

uppercase) and press ENT ER when prompted to confirm

Settings

resetting. Any other entry stops resetting.

 

 