APC AP9208 With Symmetra Power Array, UPS Status and Diagnostics Symmetra Power Array Description

Models: AP9608 AP9208

1 52
Download 52 pages 47.53 Kb
Page 19
Image 19

With Symmetra Power Array

Type 1, then ENTER at the Main menu to display the Status and Diagnos- tics screen of the connected Symmetra Power Array.

-----------------------------

SYMMETRA STATUS

-------------------------------

IM Status: On & Ok

 

 

 

Last Xfer: None

 

RIM Status: Off & Failed

 

Last Self test: OK

 

------------------------------

INPUT/OUTPUT ---------------------------------

 

Input:

246.0 V at 60.04 Hz

Load Assuming No Redundancy: 000 %

Output:

000.0 V at 60.04 Hz

Allowing for n+1 Redundancy: 000 %

Load Current:

00.0 A

 

 

 

Capacity:

16.0 kVA

 

 

 

 

 

Alarm if Over: 06.0 kVA

-----------------------------

POWER MODULES ---------------------------------

 

Installed:

05

 

 

 

Fault Tolerance:

n+0

Bad:

00

 

 

 

Alarm if Under:

n+2

-------------------------------

BATTERIES -----------------------------------

 

Installed:

004

Voltage:

137.1 VDC

Runtime: 0244 min.

Bad:

000

Capacity:

98.0 %

Alarm if Under: 015 min.

System Status:On-Line

1- Main Frame Information

2- External Battery Frame Information for frame(s): 1, 2, 3, 6, 7 <ENTER>=Refresh, <ESC>=Main menu>, ?=Help>

The following table describes the items on the UPS Status and Diagnos- tics screen when Call-UPSII is used with a Symmetra Power Array. The table continues on the next page.

UPS STATUS AND DIAGNOSTICS (Symmetra Power Array)

Item

Description

 

 

IM Status

Status of the Intelligence Module.

 

 

RIM Status

Status of the Redundant Intelligence Module.

 

 

 

Reason for the last UPS transfer to battery. Possible

Last Xfer

results are: Test, Low Voltage, HiVoltage, Rate of

 

Change, and Notch/Spike.

 

 

Last Self Test

Results of the last Self Test. Possible results are listed

in earlier Self Test Table in this section.

 

 

 

Input

Utility line input, in volts AC RMS and in hertz.

 

 

Output

UPS output to the load, in volts AC RMS and in hertz.

 

 

Load Current

Amount of current being drawn by the load, in amps.

 

 

15

Page 19
Image 19
APC AP9208, AP9608 manual With Symmetra Power Array, UPS Status and Diagnostics Symmetra Power Array Description