15

The following table describes the items on the UPS Status and Diagnos-
tics screen when Call-UPS II is used with a Symmetra Power Array. The

table continues on the next page.

With Symmetra Power Array

Type 1, then ENTER at the Main menu to display the Status and Diagnos-

tics screen of the connected Symmetra Power Array.

UPS STATUS AND DI A GNO ST ICS ( Sym me t ra Po we r Ar ray )
Item Description
IM Status Status of the Intelligence Module.
RIM Status Status of the Redundant Intelligence Module.

Last Xfer Reason for the last UPS transfer to battery. Possible

results are: Test, Low Voltage, HiVoltage, Rate of
Change, and Notch/Spike.

Last Self Test Results of the last Self Test. Possible results are listed

in earlier Self Test Table in this section.
Input Utility line input, in volts AC RMS and in hertz.
Output UPS output to the load, in volts AC RMS and in hertz.
Load Current Amount of current being drawn by the load, in amps.
----------------------------- SYMMETRA STATUS -------------------------------
IM Status: On & Ok Last Xfer: None
RIM Status: Off & Failed Last Self test: OK
------------------------------ INPUT/OUTPUT ---------------------------------
Input: 246.0 V at 60.04 Hz Load Assuming No Redundancy: 000 %
Output: 000.0 V at 60.04 Hz Allowing for n+1 Redundancy: 000 %
Load Current: 00.0 A Capacity: 16.0 kVA
Alarm if Over: 06.0 kVA
----------------------------- POWER MODULES ---------------------------------
Installed: 05 Fault Tolerance: n+0
Bad: 00 Alarm if Under: n+2
------------------------------- BATTERIES -----------------------------------
Installed: 004 Voltage: 137.1 VDC Runtime: 0244 min.
Bad: 000 Capacity: 98.0 % Alarm if Under: 015 min.
System Status:On-Line
1- Main Frame Information
2- External Battery Frame Information for frame(s): 1, 2, 3, 6, 7
<ENTER>=Refresh, <ESC>=Main menu>, ?=Help>