Axis Communications A1001 Create a New Hardware Configuration, Configure Locks and Door Monitors

Models: A1001

1 63
Download 63 pages 10.98 Kb
Page 14
Image 14

AXIS A1001 Network Door Controller & AXIS Entry Manager

System Configuration

Create a New Hardware Configuration

To create a new hardware configuration from the beginning:

1.Go to Setup > Hardware Configuration and click Start new hardware configuration .

If the product’s hardware has not been configured before or has been deleted, Hardware Configuration will be available in the notification panel in the Overview page.

2.Select a door option depending on the number of doors, one (1) or two (2), that will be connected to the Axis product.

3.Enter a descriptive name for each door and click Next. It is recommended to provide the doors with unique descriptive names so that they easily can be identifed by anyone who will administrate the system.

You can also edit the name of the Axis product. The default name includes the serial number for easy identification.

4.Select the door monitor and lock options that match the requirements and the type of lock connections that will be used and click Next. For more information, see Configure Locks and Door Monitors on page 14 and Lock Options on page 15.

5.Select the types of readers that will be used and click Finish. For more information, see Configure Readers and REX Devices on page 16 and Reader and REX Device Options on page 16.

6.In the dialog that appears after completing the configuration, click OK or click the link to view the hardware pin chart. To print the hardware pin chart, click Print Hardware Pin Chart on the Hardware Pin Chart page.

To cancel the hardware configuration, click Cancel. This can be done in any of the hardware configuration pages.

Configure Locks and Door Monitors

1.If a door monitor will be used, select Door monitor and then select the option that matches how the door monitor circuits will be connected.

2.If the door lock shall lock immediately after the door has been opened, select Cancel access time once door is opened.

3.Specify the door monitor time options or, if no door monitor will be used, the lock time options.

4.Select the options that match how the lock circuits will be connected.

5.If a lock monitor will be used, select Lock monitor and then select the options that match how the lock monitor circuits will be connected.

6.If the input connections from readers, REX devices, and door monitors shall be supervised, select Enable supervised inputs. For more information, see Use Supervised Inputs on page 16.

Note

Most lock, door monitor, and reader options can be changed without resetting and starting a new hardware configuration. Go to Setup > Hardware Reconfiguration .

You can connect one lock monitor per door controller. So if you use double-lock doors, only one of the locks can have a lock monitor. If two doors are connected to the same door controller, lock monitors cannot be used.

Motorized locks must be configured as secondary locks.

Door Monitor Options

The following door monitor options are available:

Door monitor – Selected by default. Each door has its own door monitor that, for example, will signal when the door has been forced open or open too long. Deselect if no door monitor will be used.

-Open circuit = Closed door – Select if the door monitor circuit is normally open. The door monitor gives the door open signal when the circuit is closed. The door monitor gives the door closed signal when the circuit is open.