26 en Configuring the DeviceHigh Speed Pan/Tilt System

7.2

Protocol Switches

 

 

 

There is no need to set any particular protocol, the UPH is auto-sensing. The protocols sup-

 

ported are:

 

 

 

 

 

 

 

 

 

Protocol

Baud Rate

Menu setup (OSD)

 

 

 

 

 

 

 

Pelco D

2400

Preset 95

 

 

(8N 1)

 

 

 

 

 

 

 

 

 

 

 

Biphase and

Auto

AUX-On 200

 

 

Bilinx

 

 

 

 

 

 

 

 

 

 

 

 

Table 7.2 Supported Protocols

 

 

7.3

Setting the Address

 

 

The UPH address can have a setting from 1 to 255. Binary code is used to select the address, using the 8 DIP switches on the far right. The up position represents binary value “1”, while the down position represents binary value “0”.

See Figure 7.2 for all possible combinations (the white rectangle represents the position of the switch).

Serial Lines

Address

Table 7.3 All Possible Settings for Setting the UPH Address

Serial Lines Switches:

Dip-switches 10 and 9 are not used; the unit has fixed serial line mode.

Serial Lines Termination Switches:

Dip-switch 1 is not used (the RS485-1 line is not available).

Dip-switch 2 is used to enable the line termination of RS485-2 serial line.

Bilinx and Biphase Switches:

Dip-switch 1 is used to enable the line termination of Biphase serial line.

Dip-switch 2 is used to select the video format (ON = PAL, OFF = NTSC).

F01U.073.990 Version 1.0 2007.07