Chapter 3 Installing the Switch

Rack-Mounting the Chassis

Attaching the Rack-Mount Brackets to the Chassis

Two rack-mount brackets are included as part of the rack-mount kit (69-2037-xx) supplied with both switch chassis. The rack-mount brackets can be installed either on the front sides of the chassis or on the rear sides of the chassis. The rack-mount brackets are intended for use in mounting the chassis in a standard 19-inch (48.3 cm). This rack-mount kit is not suitable for racks with obstructions (such as power strips) that could impair access to the switch.

Note If you are installing the Catalyst 4948E-F switch chassis in a hot isle and cold isle data center environment and plan on using the optional modular ToR switch inlet duct kit (Panduit model CDE2), you must install the rack-mount brackets to the front of the chassis.

To install the rack-mount brackets on the front sides of the chassis, follow these steps:

Step 1 Remove the two rack-mount brackets and eight M4 x 8 mm Phillips flat-head screws from the accessory kit.

Step 2 Position one of the rack-mount brackets against one side of the chassis, and align the countersunk screw holes with the M4 holes in the chassis. (See Figure 3-1.)

Note In Figure 3-1, the top view shows the rack-mount brackets being attached to the front of the chassis. The bottom view shows the rack-mount brackets being attached to the rear of the chassis.

Step 3 Secure the rack-mount bracket to the chassis with four M4 x 8 mm Phillips flat-screws. Step 4 Repeat Steps 2 and 3 for the second rack-mount bracket on the opposite side of the chassis.

Catalyst 4948E and Catalyst 4948E-F Switch Installation Guide