Appendix A Power Supply Specifications

300 W DC-Input Power Supply (PWR-C49-300DC)

300 W DC-Input Power Supply (PWR-C49-300DC)

Figure A-12shows the 300 W DC-input power supply with the major features identified. The PWR-C49-300DC DC-input power supply is supported only on the Catalyst 4948E switch chassis.

Figure A-12 300 W DC-Input Power Supply (PWR-C49-300DC)

1

2

PWR-C49-300DC

3

4

196261

1

Source DC terminal block

3

Power supply LEDs

 

 

 

 

2

Captive installation screw

4

Power supply handle

 

 

 

 

Table A-6lists the specifications for the 300 W DC-input power supply (PWR-C49-300DC).

Table A-6 300 W DC-Input Power Supply Specifications

 

 

 

 

Item

Specification

 

 

 

 

 

 

 

 

 

 

DC-input voltage

–48 VDC @ 8.33 A for nominal –48 V battery backup system

 

 

 

 

 

(operating range: –40.5 VDC to –56 VDC)

 

 

 

 

 

–60 VDC @ 6.66 A for nominal –60 V battery backup system

 

 

 

 

 

(operating range: –55 VDC to –72 VDC)

 

 

 

 

 

 

 

 

 

 

DC-input current

Nominal range is 6.66 A to 8.33 A

 

 

 

 

 

 

 

 

 

 

Power supply output capacity

300 W

 

 

 

 

 

 

 

 

 

 

Power supply output

25 A @ 12 VDC

 

 

 

 

 

 

 

 

 

 

Output holdup time

8 ms (minimum)

 

 

 

 

 

 

 

 

 

 

Heat dissipation

341 BTU/hour (power supply only)

 

 

 

 

 

 

 

 

 

Catalyst 4948E and Catalyst 4948E-F Switch Installation Guide

 

 

 

 

 

 

 

 

 

 

 

A-12

 

 

 

OL-21561-02

 

 

 

 

 

 

Page 88
Image 88
Cisco Systems 4948E-F manual Figure A-12 300 W DC-Input Power Supply PWR-C49-300DC