Chapter 2 Preparing for Installation

Site Requirement Guidelines

Table 2-1 Specifications for Operating and Nonoperating Environments

Specification

Minimum

Maximum

 

 

 

Temperature, ambient operating

32°F (0°C)

104°F (40°C)

 

 

 

Temperature, ambient nonoperating and storage

–4°F (–20°C)

149°F (65°C)

 

 

 

Humidity, ambient (noncondensing) operating

10%

90%

 

 

 

Humidity, ambient (noncondensing) nonoperating

5%

95%

and storage

 

 

 

 

 

Altitude, operating and nonoperating

Sea level

10,000 ft.

 

 

(3050 m)

 

 

 

Vibration, operating

5–200 Hz, 0.5 g (1 octave/min.)

 

 

 

Vibration, nonoperating

5–200 Hz, 1 g (1 octave/min.)

 

200–500 Hz, 2 g (1 octave/min.)

 

 

 

 

Power Connection Guidelines

Follow these precautions and recommendations when planning power connections to a Cisco uBR7100 series router:

Check the power at your site before installation and periodically after installation to ensure that you are receiving clean power. Install a power conditioner if necessary.

The AC power supply includes the following features:

Autoselects either 110V or 220V operation.

All units include a 6-foot (1.8-meter) electrical power cord that is appropriate for the country of operation.

Warning This product relies on the building’s installation for short-circuit (overcurrent) protection. Ensure that the protective device is rated not greater than: 15A minimum, 60VDC. Statement 1005

Warning This equipment must be grounded. Never defeat the ground conductor or operate the equipment in the absence of a suitably installed ground conductor. Contact the appropriate electrical inspection authority or an electrician if you are uncertain that suitable grounding is available. Statement 1024

Use a grounded AC power outlet and install proper grounding to avoid damage from lightning and power surges.

The AC-input power supply operates on input voltage and frequency within the ranges of 100 to 240 VRMS and 50/60 Hz without the need for operator adjustments. This power supply also incorporates an active power factor corrector that minimizes the unwanted generation of line current harmonics that can cause overload of site electrical distribution systems.

Note We recommend an uninterruptible power source to protect against power failures at your site. We recommend powering a Cisco uBR7100 series router from a 15A receptacle at the power source.

Cisco uBR7100 Series and Cisco uBR7100E Series Universal Broadband Router Hardware Installation Guide

 