Cisco Systems WSC4500X24XIPB A-11, Specification, “Calculating DC Input Current” section on page

Models: WSC4500XF16SFP WSC4500XF32SFP WSC4500X24XIPB

1 194
Download 194 pages 36.02 Kb
Page 177
Image 177
“Calculating DC Input Current” section on page 2-13.

Appendix A Specifications

Catalyst 4500 Series Power Supplies

Table A-8

1400 W DC-Input Power Supply Specifications (continued)

 

 

 

 

 

Item

 

Specification

 

 

 

 

DC-input current

Data only: 31 A @ –60 VDC

 

 

 

Data and inline devices: 180 A maximum @ –48 VDC input

 

 

 

Note The input power is configurable in the CLI. The Cisco

 

 

 

 

IOS command is power dc input. The Catalyst

 

 

 

 

Operating Sysytem command is set power DC input.

 

 

 

 

Configure the switch software to match the

 

 

 

 

requirements of your switch. To learn how to calculate

 

 

 

 

the DC input current for your system, refer to the

 

 

 

 

“Calculating DC Input Current” section on page 2-13.

 

Input power

 

1866

W (Data only)

 

Current draw At –40.5 V (min voltage)

46 A

 

 

 

 

Current draw at –72 V (max voltage)

25.9 A

 

Max heat dissipation at 1866 W

5760

BTUs

 

 

 

179 A max @ 48 VDC

 

Maximum KVA rating

1.87 (data)

 

 

 

9.15 (data and voice)

 

Power supply output (DC supply)

Data: 12 V @120 A, 3.3 V @ 10 A

 

 

 

Inline devices: 140 A total maximum (35 A maximum each

 

 

 

per 5 channels) @–48 to 60 VDC input

 

 

 

1367

W+ 40 W redundant mode (Data)

 

 

 

2267

W maximum in combined mode (Data)

 

 

 

7500

W maximum each in redundant mode (PoE)

 

 

 

7280

W maximum in combined mode (PoE)

 

DC input terminal block

Accepts FCI p/n YAV25L2TC14FX90 or equivalent,

 

 

 

barrel-type lug terminals with 90-degree angle, two- hole

 

 

 

tongue, which accommodates 1/0 AWG size copper wire. The

 

 

 

connector tongue width is 0.82 in, the stud hole spacing is 5/8 in,

 

 

 

and the hole size is 1/4 in.

 

Output holdup time

4 ms

 

 

 

 

Max heat dissipation

1591

BTUs/hr (data)

 

 

 

2905

BTUs/hr (data and voice)

 

 

 

 

 

 

 

 

 

 

 

Catalyst 4500 Series Switches Installation Guide

 

 

 

 

 

 

 

 

78-14409-08

 

 

 

 

A-11

 

 

 

 

 

Page 177
Image 177