Connecting the DC Load Cables

APS3-06X (Desktop Versions)

Before proceeding check you have:

4 x load cable clamps

8 x 25mm blunt ended screws

8 x 5mm and 4 x 10mm cable sleeves (50mm long)

Depending on the cables sizes, not all sleeves will be required.

1mm2 (18 AWG) cable for connection to 6A outlets

4mm2 (12 AWG) cable for connection to 25A outlets

Step 1 - Fit load cable clamps

Insert the square ends of the load cable clamps into the holes in the back of the system.

Engage two turns of each retaining screw. This will ensure that the clamp does not move when the wires and sleeves are inserted.

Fit all clamps even if you do not use them all. Tighten unused clamps to prevent access to the DC outputs.

Step 2 - Strip cable ends

Strip approximately 10mm (3/8”) from the cable ends. We recommend fitting cable ferrules over the cable ends.

Copyright © 2005-2006 Eaton Corporation. All Rights Reserved.

3-5

IPN 997-00012-41D December 2006

 

Page 25
Image 25
Eaton Electrical SC200 manual Fit load cable clamps, Connecting the DC Load Cables