Appendix A

Glossary of Alarms

AC Fail

All rectifiers are reporting loss of AC power.

ACD Fan Fail

The AC Distribution cooling system or fan controller has failed.

Aux Temp High

The auxiliary temperature sensor is at a temperature above the high

 

temperature set point.

Aux Temp Low

The auxiliary temperature sensor is at a temperature below the low

 

temperature set point.

Aux Temp Sensor Fail

The auxiliary temperature sensor is incorrectly configured,

 

disconnected, not fitted or faulty.

Batt Temp High

This alarm indicates either thermal runaway of the batteries or that

 

the batteries are operating at a temperature that may cause reduced

 

battery life.

Batt Temp Low

This alarm indicates a risk to the battery standby power system.

 

Note that lower temperatures reduce the battery capacity.

Battery Fuse Fail

The batteries may no longer be powering the load.

(displayed as Batt Fuse Fail)

 

Battery Test Active

A Battery Test is active.

Battery Test Fail

The batteries do not have the required capacity or are not operating

 

in a fully charged state.

Equalize Active

An Equalize process is active.

Fast Charge Active

A Fast Charge process is active.

High Float

The float voltage is above its normal range.

High Load

The bus voltage is higher than the range that is safe for a reliable

 

load.

In Discharge

The batteries are discharging.

Load Fuse Fail

The Load Fuse Fail digital input to the SM45 is active.

Low Float

The float voltage is below its normal range.

Low Load

The bus voltage is below its normal range.

Copyright © 2005-2006 Eaton Corporation. All Rights Reserved.

A-1

IPN 997-00012-41D December 2006

 