Setting Up SNMP Traps

The SM45 supervisory module can be configured to send alarms as SNMP traps to up to eight different SNMP trap receivers.

To send alarms as SNMP traps, first set up Ethernet communications (see page 6-3for details), and then use DCTools to set up SNMP traps as follows:

1From the DCTools System Summary (Home) screen, click the Configuration and then Communications hotlink to display the Communications view.

2Click the button to the left of SNMP to display the SNMP configuration view.

3Do not change the default settings of SNMP Read Community (public) and SNMP Write Community (private), unless requested by the network administrator.

4Configure Trap Repeat and Trap Repeat Rate as appropriate.

5For each receiver, configure the following parameters using the configuration guidelines.

Parameter

Configuration Guidelines

Name

Enter the name of the SNMP trap receiver (20 characters

 

maximum).

 

 

Level

SNMP Trap Level – controls reporting of specific events for each

 

receiver as follows:

 

Select All Events And Alarms to receive events and urgent

 

and non-urgent alarms. (Typically events are status

 

messages such as Equalize Active.)

 

Select Urgent And Non Urgent Alarms to receive both

 

urgent and non-urgent alarm notifications.

 

Select Urgent Alarms Only to receive only urgent alarm

 

notifications.

 

Select Disabled to temporarily disable notifications to the

 

receiver.

 

 

IP Address

Enter the IP address of the trap receiver that has been assigned

 

by the network administrator.

 

 

Port

Enter the port number of the trap receiver that has been

 

assigned by the network administrator.

 

 

Trap Community

A form of password. Use public, unless the network

 

administrator has assigned a new password.

 

 

Mode

Select:

 

Normal Traps for sending traps to any network

 

management system, except PowerManagerII

 

Acknowledged Summary Trap for sending traps to

 

PowerManagerII only

 

 